Summary
PRRES20210626
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - ENGINEERED FLOOR SYSTEM - COVERED AND UNCOVERED DECK
02/16/2021
02/19/2021
08/17/2021
01/30/2023
Locations
Contacts
PFEIFER HOMES INC, Address:1550 SW MARKET ST STE 210, Phone:(816) 524-5245  
AUBREY@PFEIFERHOMES.COM  
MIKE BRYANT HEATING & COOLING , Address:1711 E 123RD , Phone:(913) 441-7807  
PREMIER ELECTRIC & LIGHTING DESIGN, Address:PO BOX 1311, Phone:(816) 564-7660  
CENTURY PLUMBING, Address:14001 CENTURY LN, Phone:(816) 765-6066  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 02/22/2021 02/18/2021
Brandon Kalwei
Right-of-way
Corrective Action Required
02/18/2021

The right-of-way with dimensions must be provided on the plot plan.
Residential Plan Review Approved 02/22/2021 02/18/2021
Brandon Kalwei
Plot Plan Review Rejected 02/19/2021 02/17/2021
Brandon Kalwei
Right-of-way
Corrective Action Required
02/17/2021

The right-of-way with dimensions must be provided on the plot plan.
Residential Plan Review Approved 02/19/2021 02/17/2021
Brandon Kalwei
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,581.62 $1,581.62 Paid 02/19/2021
8331507-Sewer Connection Fee $630.00 $630.00 Paid 02/19/2021
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 02/19/2021
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 02/19/2021
8331401-Water Tap Fee $3,581.00 $3,581.00 Paid 02/19/2021
8350015-Water Meter Fee $455.54 $455.54 Paid 02/19/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 04/05/2022
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 01/09/2023
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 2/26/2021 (11:00) 2/26/2021 02/26/2021
Sewer Service Inspection - R Passed 3/24/2021 03/24/2021
Water Service Inspection - R Partial 3/24/2021 03/24/2021
Misc
Informational
03/24/2021
partial water approval from structure to metallic connection customer side of meter
Water Service Inspection - R Passed 3/25/2021 (9:30) 3/25/2021 03/25/2021
Misc
Resolved
03/25/2021
partial water approval from structure to metallic connection customer side of meter
Underslab Plumbing Inspection - Residential Failed 3/30/2021 3/30/2021 03/30/2021
Misc
Corrective Action Required
03/30/2021
unable to access, backfill foundation and reschedule inspection
Erosion Control Inspection Residential Failed 3/30/2021 03/30/2021
Misc
Corrective Action Required
03/30/2021
-Erosion control requires continuous maintenance. Repair damaged sections within 48 hours -immediate street cleanup required -provide and maintain gravel filter -no further inspections until issues are resolved
Miscellaneous Inspection Failed 3/30/2021 03/30/2021
Misc
Corrective Action Required
03/30/2021
post site address
Underslab Plumbing Inspection - Residential Failed 4/8/2021 4/8/2021 04/08/2021
Misc
Corrective Action Required
03/30/2021
inspection denied, no site address posted and non compliance with erosion control report. See erosion control report and miscellaneous inspection reports from 03/30/2021
Miscellaneous Inspection Failed 4/8/2021 04/08/2021
Misc
Corrective Action Required
03/30/2021
post site address second notice
Erosion Control Inspection Residential Failed 4/8/2021 04/08/2021
Misc
Corrective Action Required
03/30/2021
-Erosion control requires continuous maintenance. Repair damaged sections within 48 hours -immediate street cleanup required -no further inspections until issues are resolved second notice
Underslab Plumbing Inspection - Residential Passed 4/12/2021 4/12/2021 04/12/2021
Misc
Resolved
04/12/2021
inspection denied, no site address posted and non compliance with erosion control report. See erosion control report and miscellaneous inspection reports from 03/30/2021
Erosion Control Inspection Residential Failed 5/18/2021 05/18/2021
Misc
Corrective Action Required
04/08/2021
-Erosion control requires continuous maintenance. Repair damaged sections within 48 hours -no further inspections until issues are resolved
Electrical Service Inspection Passed 9/23/2021 9/23/2021 09/23/2021
Gas Service Inspection - Residential Failed 9/23/2021 9/23/2021 09/23/2021
Misc
Corrective Action Required
09/23/2021
Complete all gas lines throughout, install fireplaces, pressure test required after completion
All Rough Inspection - Residential Failed 9/23/2021 9/23/2021 09/23/2021
Misc
Corrective Action Required
09/23/2021
-Tension straps at garage PFH -Anchor bolts required within 12” of plate break at garage -Bocca protection plates at DWV top plate garage- protect DWV at plate and 2” below plate -Support all vertical DWV 2” or less at mid point -Fireblock all tub traps -Add joist hanger garage attic access -Joist hangers at ceiling joist NW garage to dbl lvl connection, provide lateral restraint -Complete DWV at laundry 1st floor -Fireblock deadspace garage entry -Address cut I joist for DWV at 1st floor pantry -Tighten bolts at beam pantry -Land NM to box at pantry, kitchen, great room, 2nd floor bedroom closet -Dbl top plate requires 24” min offset between plate breaks - strap plates- see pantry, great room, master closet -Bocca protection plate at bottom plate, pex fridge pantry -Install fireplaces -complete all gas lines, fireplace, kitchen -seal bottom plate penetration gas lines kitchen -Protect NM at kitchen island 6” AFF -Fireblock Deadspace kitchen bump out at beam/column -Terminate all bath exhaust fans to exterior -Great room, master bed windows require tempered glazing -Flash, snow block at great room -collar ties every 48” oc -Nail protection plates on NM (romex) less than 1 1/4” from end of stud-see master bedroom -Fireblock below top plate master bed, master shower, garage wall open to eave/soffit -12” oc nailing at all abutting and intersecting braced wall corners -Joist hanger at attic access master closet -seal top plate penetration 2nd floor hall -finish DWV and pex at basement windows -Anchor all SCH 40 steel columns to floor at basement
All Rough Inspection - Residential Not Ready 10/5/2021 10/5/2021 10/05/2021
Misc
Corrective Action Required
09/23/2021
10/5/21 - INSPECTION DENIED, HOUSE HAS BEEN INSULATED WITHOUT APPROVAL, REMOVE INSULATION -Tension straps at garage PFH -Anchor bolts required within 12” of plate break at garage -Bocca protection plates at DWV top plate garage- protect DWV at plate and 2” below plate -Support all vertical DWV 2” or less at mid point -Fireblock all tub traps -Add joist hanger garage attic access -Joist hangers at ceiling joist NW garage to dbl lvl connection, provide lateral restraint -Complete DWV at laundry 1st floor -Fireblock deadspace garage entry -Address cut I joist for DWV at 1st floor pantry -Tighten bolts at beam pantry -Land NM to box at pantry, kitchen, great room, 2nd floor bedroom closet -Dbl top plate requires 24” min offset between plate breaks - strap plates- see pantry, great room, master closet -Bocca protection plate at bottom plate, pex fridge pantry -Install fireplaces -complete all gas lines, fireplace, kitchen -seal bottom plate penetration gas lines kitchen -Protect NM at kitchen island 6” AFF -Fireblock Deadspace kitchen bump out at beam/column -Terminate all bath exhaust fans to exterior -Great room, master bed windows require tempered glazing -Flash, snow block at great room -collar ties every 48” oc -Nail protection plates on NM (romex) less than 1 1/4” from end of stud-see master bedroom -Fireblock below top plate master bed, master shower, garage wall open to eave/soffit -12” oc nailing at all abutting and intersecting braced wall corners -Joist hanger at attic access master closet -seal top plate penetration 2nd floor hall -finish DWV and pex at basement windows -Anchor all SCH 40 steel columns to floor at basement
Gas Service Inspection - Residential Passed 10/8/2021 10/8/2021 10/08/2021
Misc
Resolved
10/08/2021
Complete all gas lines throughout, install fireplaces, pressure test required after completion
All Rough Inspection - Residential Failed 10/8/2021 10/8/2021 10/08/2021
Misc
Corrective Action Required
10/05/2021
10/5/21 - INSPECTION DENIED, HOUSE HAS BEEN INSULATED WITHOUT APPROVAL, REMOVE INSULATION , insulation was not removed or addressed. do not insulate without approval. Remove all insulation at inspection items. --Dryer vent over span. 35'max lenght. -Tension straps at garage PFH , doesn not extennd to top plates. -Anchor bolts required within 12” of plate break at gprotect DWV at plate and 2” below plate , covered bottom plates with insulation -Joist hangers at ceiling joist NW garage to dbl lvl connection, provide lateral restraint , insulated uncover. -Complete DWV at laundry 1st floor -Fireblock deadspace garage entry -Fireblock Deadspace kitchen bump out at beam/column , open to joist space. -Great room, master bed windows require tempered glazing ? -finish DWV and pex at basement windows , incomplete to mstr tub.
Driveway Inspection Partial 1/18/2022 1/18/2022 01/18/2022
Misc
Informational
01/18/2022
Forms were placed and aggregate was present and compacted. Blankets are on site and will be used due to cold weather upcoming. RP 1-18-22
Occupancy Inspection - Codes Residential Failed 1/25/2022 1/25/2022 01/25/2022
Miscellaneous Correction
Corrective Action Required
01/25/2022
- Handrail front steps - final grading and sod - Gutters - Splash blocks - Complete front door - Open electrical box master bathroom - Lock and secondary locks for sliding door - Label non GFCI outlets in garage and basement - Repair strap on dryer vent in basement - Install water heater - Connect water - Provide backflow preventer in basement - Seal penetration around gas meter - Caulk top of meter can and a/c disconnect
Driveway Inspection Passed 1/28/2022 1/28/2022 01/28/2022
Misc
Informational
01/18/2022
Forms were placed and aggregate was present and compacted. Blankets are on site and will be used due to cold weather upcoming. RP 1-18-22
Misc
Informational
01/28/2022
Driveway meets LS specs. 1-28-22 ES
All Rough Inspection - Residential Passed 10/14/2021 10/14/2021 02/04/2022
Misc
Resolved
02/04/2022
--Dryer vent over span. 35'max lenght.
Misc
Resolved
02/04/2022
Occupancy Inspection - Codes Residential Temporary C of O 2/4/2022 2/4/2022 02/04/2022
Miscellaneous Correction
Corrective Action Required
01/25/2022
- final grading and sod Pay all fees Provide pier inspection
Erosion Control Inspection Residential Failed 06/08/2022
Misc
Corrective Action Required
05/18/2021
-Erosion control requires continuous maintenance. Repair damaged sections within 48 hours -no further inspections until issues are resolved
Misc
Corrective Action Required
06/08/2022
Erosion control measures are ineffective and allowing silt and mud into roadway. 6/8/22 ES
Erosion Control Inspection Residential Passed 08/08/2022
Misc
Resolved
08/08/2022
-Erosion control requires continuous maintenance. Repair damaged sections within 48 hours -no further inspections until issues are resolved
Misc
Resolved
08/08/2022
Erosion control measures are ineffective and allowing silt and mud into roadway. 6/8/22 ES
Plot Plan Inspection Passed 3/30/2021 08/08/2022
Occupancy Inspection - Codes Residential Ready for Temp CO 8/8/2022 8/8/2022 08/08/2022
Miscellaneous Correction
Corrective Action Required
02/04/2022
Obtain an irrigation permit. pay TCO fee
Occupancy Inspection - Codes Residential Full C of O 1/30/2023 01/30/2023
Miscellaneous Correction
Resolved
01/30/2023
Documents & Images
Date Uploaded File Type Document Name
02/16/2021 Application Form APPLICATION
02/16/2021 Application Form excise tax
02/16/2021 WV1485 Caruthers - Sealed Plans (February 16, 2021)
02/16/2021 Final Sealed Plot Plan - Troy Approved
02/17/2021 Approved Plans APPROVED PLANS
02/17/2021 Letter Codes Residential Plan Review
02/18/2021 Lot 1485 (1)
02/18/2021 Plot Plan APPROVED PLOT PLAN
02/19/2021 Receipt Receipt for transaction: 2021-000796
02/19/2021 Letter DS Building Permit
02/26/2021 Letter INSPECTION SUMMARY
03/24/2021 Letter INSPECTION SUMMARY
03/24/2021 Letter INSPECTION SUMMARY
03/25/2021 Letter INSPECTION SUMMARY
03/30/2021 Letter INSPECTION SUMMARY
03/30/2021 Letter INSPECTION SUMMARY
03/30/2021 Letter INSPECTION SUMMARY
04/08/2021 Letter INSPECTION SUMMARY
04/08/2021 Letter INSPECTION SUMMARY
04/08/2021 Letter INSPECTION SUMMARY
04/12/2021 Letter INSPECTION SUMMARY
05/18/2021 Letter INSPECTION SUMMARY
09/23/2021 Letter INSPECTION SUMMARY
09/23/2021 Letter INSPECTION SUMMARY
09/23/2021 Letter INSPECTION SUMMARY
10/05/2021 Letter INSPECTION SUMMARY
10/08/2021 Letter INSPECTION SUMMARY
10/14/2021 Letter INSPECTION SUMMARY
10/14/2021 Letter INSPECTION SUMMARY
01/18/2022 Letter INSPECTION SUMMARY
01/25/2022 Letter INSPECTION SUMMARY
01/28/2022 Letter INSPECTION SUMMARY
02/04/2022 Letter INSPECTION SUMMARY
02/04/2022 Letter Codes Temporary Certificate of Occupancy
04/05/2022 Receipt Receipt for transaction: 2022-001883
06/08/2022 Letter INSPECTION SUMMARY
08/08/2022 Letter INSPECTION SUMMARY
01/09/2023 Certificate/License Codes Temporary Certificate of Occupancy
01/09/2023 Receipt Receipt for transaction: 2023-000126
01/30/2023 Letter Field Certificate of Occupancy
01/30/2023 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home