Summary
PRRES20193251
Building Permit - Residential
Issued
ROSS WILLIAM R & JANETTE O
NEW SINGLE FAMILY
NEW SINGLE FAMILY OWNER BUILDER THIRD PARTY INSPECTIONS REQUIRED - CHECK WITH DESIGN ARCHITECT/ENGINEER-
11/05/2019
01/17/2020
05/04/2020
Locations
Contacts
ROSS WILLIAM R & JANETTE O, Address:402 SW 3RD ST  
SHANE VERITASI, Address:4 SW 3RD ST, Phone:(816) 838-0100  
VERITASI DESIGN + BUILD, Address:4 SW 3RD ST, Phone:(816) 838-0100  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 01/22/2020 01/17/2020
Steve Conrick
Signed and sealed
Corrective Action Required
01/17/2020

Plot plan must drawn, signed, and sealed by a licensed surveyor or engineer.
Legal description
Corrective Action Required
01/17/2020

The legal description, including plat or phase number and lot number, and street address must be provided on the plot plan.
Property boundary
Corrective Action Required
01/17/2020

Property boundary distances and bearings, as shown on the recorded plat, must be provided on the plot plan.
Right-of-way
Corrective Action Required
01/17/2020

The right-of-way with dimensions must be provided on the plot plan.
Easements
Corrective Action Required
01/17/2020

All easements with dimensions must be provided on the plot plan.
Building elevations
Corrective Action Required
01/17/2020

Existing and finished elevations at building footprint corners must be provided on the plot plan.
Lot elevations
Corrective Action Required
01/17/2020

Existing and finish elevations at all property corners must be provided on the plot plan.
Miscellaneous Correction
Corrective Action Required
01/17/2020

Elevation at top of curb at end of driveway and at lot corners to street.
Foundation elevation
Corrective Action Required
01/17/2020

The top of foundation elevation must be provided on the plot plan.
Garage elevation
Corrective Action Required
01/17/2020

The garage floor elevation must be provided on the plot plan.
Basement elevation
Corrective Action Required
01/17/2020

The Basement floor elevation and basement type (e.g. full/standard, daylight, walk-out, etc.)
Drainage swales
Corrective Action Required
01/17/2020

Drainage swales (where required); show spot elevations within the swale as required to conform to the approved master drainage plan (if applicable), must be provide
Spot elevations
Corrective Action Required
01/17/2020

Spot elevations and/or drainage flow arrows shall be provided throughout the lot.
City infrustructure
Corrective Action Required
01/17/2020

Show all manholes, water valve boxes, fire hydrants, and stormwater structures.
Residential Plan Review Approved 01/22/2020 01/17/2020
Steve Conrick
Residential Plan Review Approved 01/07/2020 01/14/2020
Steve Conrick
03 Two (2) plot plans
Corrective Action Required
01/03/2020

Two (2) plot plans Please submit (2) plot plans sealed by an engineer or surveyor
07 Identify emergency escape openings from bedrooms
Corrective Action Required
01/03/2020

Identify emergency escape openings from bedrooms and basement(s). (IRC Section R310 as amended per Ordinance) Label each egress in bedrooms/offices
08 Designate locations of smoke detectors and carbon monoxide detectors
Corrective Action Required
01/03/2020

Designate locations of smoke detectors and carbon monoxide detectors. (IRC Section R314 and R315) Locate and label smoke, carbon monoxide, and combo detectors
09 Identify furnace and water heater locations
Corrective Action Required
01/03/2020

Identify furnace and water heater location(s). (IRC Section G2406)
10 Combustion air
Corrective Action Required
01/03/2020

Provide combustion air calculations and specify transfer air grilles for fuel burning appliances located in confined space(s). (IRC Chapter 17 and Section G2407)
11 Designate R-value(s) for floors, walls, ceilings, roof/ceilings.
Corrective Action Required
01/03/2020

Designate R-value(s) for floors, walls, ceilings, roof/ceilings. (LSCO 7-802)
12 Detail required separation between garage and living area including door
Corrective Action Required
01/03/2020

Detail required separation between garage and living area including door, door closer and gypsum board. (IRC R302.5) Provide details for door to garage
14 Identify roof covering material (IRC Section R905)
Corrective Action Required
01/03/2020

Identify roof covering material (IRC Section R905) What material will be used to seal the roof?
15 Provide size, spacing, species, and grade of rafter, ceiling joist mater
Corrective Action Required
01/03/2020

Provide size, spacing, species, and grade of rafter, ceiling joist materials and ridge and valley members. (IRC Section R802) Provide specs/information on the roof. Is it a suspended slab?
19 Footings, column pads, piers and grade beams - dimensions
Corrective Action Required
01/03/2020

Footings, column pads, piers and grade beams - dimensions. (IRC Section R403)
20 Footings, column pads, piers and grade beams - reinforcement
Corrective Action Required
01/03/2020

Footings, column pads, piers and grade beams - reinforcement size and spacing.
21 Foundation wall thickness and height and reinforcement.
Corrective Action Required
01/03/2020

Concrete wall thickness and height and reinforcement. (IRC Section R404)
22 Beam and column locations, sizes and material.
Corrective Action Required
01/03/2020

Beam and column locations, sizes and material.
23 Location of vertical supports for beams. (point loads)
Corrective Action Required
01/03/2020

Location of vertical supports for beams. (point loads)
24 Concrete reinforcement size and spacing.
Corrective Action Required
01/03/2020

Concrete reinforcement size and spacing.
25 Concrete thickness.
Corrective Action Required
01/03/2020

Concrete thickness.
26 Concrete minimum compressive strength.
Corrective Action Required
01/03/2020

Concrete minimum compressive strength. (IRC Section 402.2)
32 Size, height, spacing of studs. (IRC Section R602)
Corrective Action Required
01/03/2020

Size, height, spacing of studs. (IRC Section R602) Are there any framed walls or is everything concrete. If there are, provide the above information.
36 Identify interior load bearing walls.
Corrective Action Required
01/03/2020

Identify interior load bearing walls. (IRC Section R602) Provide additional information for walls/cieling to support Crow's Nest.
Miscellaneous Correction
Corrective Action Required
01/03/2020

What is the plan for the electrical/plumbing in concrete walls? Will walls be framed in where electrical/plumbing is located or will another method be used? Please clearify.
waiting on answer from water utilites on sanitary easement Steven Conrick 01/09/2020 11:14 AM
Plot Plan Review Rejected 11/07/2019 11/06/2019
Steve Conrick
Signed and sealed
Corrective Action Required
11/05/2019

Plot plan must drawn, signed, and sealed by a licensed surveyor or engineer.
Legal description
Corrective Action Required
11/06/2019

The legal description, including plat or phase number and lot number, and street address must be provided on the plot plan.
Property boundary
Corrective Action Required
11/06/2019

Property boundary distances and bearings, as shown on the recorded plat, must be provided on the plot plan.
Right-of-way
Corrective Action Required
11/06/2019

The right-of-way with dimensions must be provided on the plot plan.
Easements
Corrective Action Required
11/06/2019

All easements with dimensions must be provided on the plot plan.
Building elevations
Corrective Action Required
11/06/2019

Existing and finished elevations at building footprint corners must be provided on the plot plan.
Lot elevations
Corrective Action Required
11/06/2019

Existing and finish elevations at all property corners must be provided on the plot plan.
Miscellaneous Correction
Corrective Action Required
11/06/2019

Elevation at top of curb at end of driveway and at lot corners to street.
Foundation elevation
Corrective Action Required
11/06/2019

The top of foundation elevation must be provided on the plot plan.
Garage elevation
Corrective Action Required
11/06/2019

The garage floor elevation must be provided on the plot plan.
Basement elevation
Corrective Action Required
11/06/2019

The Basement floor elevation and basement type (e.g. full/standard, daylight, walk-out, etc.)
Drainage swales
Corrective Action Required
11/06/2019

Drainage swales (where required); show spot elevations within the swale as required to conform to the approved master drainage plan (if applicable), must be provide
Spot elevations
Corrective Action Required
11/06/2019

Spot elevations and/or drainage flow arrows shall be provided throughout the lot.
City infrustructure
Corrective Action Required
11/06/2019

Show all manholes, water valve boxes, fire hydrants, and stormwater structures.
Residential Plan Review Rejected 11/07/2019 11/05/2019
Steve Conrick
03 Two (2) plot plans
Corrective Action Required
11/05/2019

Two (2) plot plans Please submit (2) plot plans sealed by an engineer or surveyor
07 Identify emergency escape openings from bedrooms
Corrective Action Required
11/05/2019

Identify emergency escape openings from bedrooms and basement(s). (IRC Section R310 as amended per Ordinance) Label each egress in bedrooms/offices
08 Designate locations of smoke detectors and carbon monoxide detectors
Corrective Action Required
11/05/2019

Designate locations of smoke detectors and carbon monoxide detectors. (IRC Section R314 and R315) Locate and label smoke, carbon monoxide, and combo detectors
09 Identify furnace and water heater locations
Corrective Action Required
11/05/2019

Identify furnace and water heater location(s). (IRC Section G2406)
10 Combustion air
Corrective Action Required
11/05/2019

Provide combustion air calculations and specify transfer air grilles for fuel burning appliances located in confined space(s). (IRC Chapter 17 and Section G2407)
11 Designate R-value(s) for floors, walls, ceilings, roof/ceilings.
Corrective Action Required
11/05/2019

Designate R-value(s) for floors, walls, ceilings, roof/ceilings. (LSCO 7-802)
12 Detail required separation between garage and living area including door
Corrective Action Required
11/05/2019

Detail required separation between garage and living area including door, door closer and gypsum board. (IRC R302.5) Provide details for door to garage
14 Identify roof covering material (IRC Section R905)
Corrective Action Required
11/05/2019

Identify roof covering material (IRC Section R905) What material will be used to seal the roof?
15 Provide size, spacing, species, and grade of rafter, ceiling joist mater
Corrective Action Required
11/05/2019

Provide size, spacing, species, and grade of rafter, ceiling joist materials and ridge and valley members. (IRC Section R802) Provide specs/information on the roof. Is it a suspended slab?
19 Footings, column pads, piers and grade beams - dimensions
Corrective Action Required
11/05/2019

Footings, column pads, piers and grade beams - dimensions. (IRC Section R403)
20 Footings, column pads, piers and grade beams - reinforcement
Corrective Action Required
11/05/2019

Footings, column pads, piers and grade beams - reinforcement size and spacing.
21 Foundation wall thickness and height and reinforcement.
Corrective Action Required
11/05/2019

Concrete wall thickness and height and reinforcement. (IRC Section R404)
22 Beam and column locations, sizes and material.
Corrective Action Required
11/05/2019

Beam and column locations, sizes and material.
23 Location of vertical supports for beams. (point loads)
Corrective Action Required
11/05/2019

Location of vertical supports for beams. (point loads)
24 Concrete reinforcement size and spacing.
Corrective Action Required
11/05/2019

Concrete reinforcement size and spacing.
25 Concrete thickness.
Corrective Action Required
11/05/2019

Concrete thickness.
26 Concrete minimum compressive strength.
Corrective Action Required
11/05/2019

Concrete minimum compressive strength. (IRC Section 402.2)
32 Size, height, spacing of studs. (IRC Section R602)
Corrective Action Required
11/05/2019

Size, height, spacing of studs. (IRC Section R602) Are there any framed walls or is everything concrete. If there are, provide the above information.
36 Identify interior load bearing walls.
Corrective Action Required
11/05/2019

Identify interior load bearing walls. (IRC Section R602) Provide additional information for walls/cieling to support Crow's Nest.
Miscellaneous Correction
Corrective Action Required
11/05/2019

What is the plan for the electrical/plumbing in concrete walls? Will walls be framed in where electrical/plumbing is located or will another method be used? Please clearify.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,568.77 $1,568.77 Paid 01/17/2020
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 01/17/2020
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 01/17/2020
8331507-Sewer Connection Fee $480.00 $480.00 Paid 01/17/2020
8331401-Water Tap Fee $3,477.00 $3,477.00 Paid 01/17/2020
8350015-Water Meter Fee $425.02 $425.02 Paid 01/17/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Driveway Inspection Pending
Plot Plan Inspection Pending
Footing Inspection - Residential Pending
Piers/Caissons Inspection - Residential Pending
Occupancy Inspection - Codes Residential Pending
Erosion Control Inspection Residential Pending
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
05/07/2021
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. - PROVIDE PROPER INLET PROTECTION = SILT FENCE/ GUTTER BUDDY, FILTER SOX AT INLET NEAR DRIVEWAY -
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
05/07/2021
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. - PROVIDE INLET PROTECTION - - REMOVE CONSTRUCTION DEBRIS BLOCKING STORM DRAIN AT DRIVEWAY - - SOIL STOCKPILES SHOULD NOT BE LOCATED NEAR THE STREET, STORM INLETS, LOT ACCESS, OR ADJACENT PROPERTY LINES. ALL STOCKPILES MUST EITHER BE STABILIZED, COVERED, OR HAVE ESC AND BMPS INSTALLED AROUND THE BASE OF THE PILE. -
All Rough Inspection - Residential Pending
Misc
Corrective Action Required
02/07/2025
Ok to cover walls on rooftop 12/17/24 -complete all framing and MEPs **Rooftop space exterior walls and ceiling ok for microcement
Erosion Control Inspection Residential Failed 12/15/2020 12/15/2020
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
12/15/2020
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. - PROVIDE SILT FENCE AT DIRT PILE NEXT TO STREET- - PROVIDE SILT FENCE/ GUTTER BUDDY AT INLET -
Erosion Control Inspection Residential Failed 5/3/2021 05/03/2021
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
12/15/2020
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. - PROVIDE SILT FENCE AT DIRT PILE NEXT TO STREET- - PROVIDE SILT FENCE/ GUTTER BUDDY AT INLET -
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
05/03/2021
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. - PROVIDE INLET PROTECTION - - REMOVE CONSTRUCTION DEBRIS BLOCKING STORM DRAIN AT DRIVEWAY - - SOIL STOCKPILES SHOULD NOT BE LOCATED NEAR THE STREET, STORM INLETS, LOT ACCESS, OR ADJACENT PROPERTY LINES. ALL STOCKPILES MUST EITHER BE STABILIZED, COVERED, OR HAVE ESC AND BMPS INSTALLED AROUND THE BASE OF THE PILE. -
Erosion Control Inspection Residential Failed 5/7/2021 05/07/2021
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
05/03/2021
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. - PROVIDE PROPER INLET PROTECTION = SILT FENCE/ GUTTER BUDDY, FILTER SOX AT INLET NEAR DRIVEWAY -
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
05/03/2021
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. - PROVIDE INLET PROTECTION - - REMOVE CONSTRUCTION DEBRIS BLOCKING STORM DRAIN AT DRIVEWAY - - SOIL STOCKPILES SHOULD NOT BE LOCATED NEAR THE STREET, STORM INLETS, LOT ACCESS, OR ADJACENT PROPERTY LINES. ALL STOCKPILES MUST EITHER BE STABILIZED, COVERED, OR HAVE ESC AND BMPS INSTALLED AROUND THE BASE OF THE PILE. -
Miscellaneous Inspection Failed 12/3/2021 12/3/2021 12/03/2021
Misc
Corrective Action Required
12/03/2021
was asked to look at conduit and this would be on Evergy side from pole to house not City.
Underslab Plumbing Inspection - Residential Partial 6/8/2022 6/8/2022 06/08/2022
Misc
Informational
06/08/2022
-First 10' of sanitary just outside of foundation to inside of back of house
Underslab Plumbing Inspection - Residential Partial 6/23/2022 6/23/2022 06/23/2022
Misc
Informational
06/08/2022
-First 10' of sanitary just outside of foundation to inside of back of house -DWV under foam
Underslab Plumbing Inspection - Residential Passed 7/20/2022 7/20/2022 07/20/2022
Misc
Informational
06/23/2022
-First 10' of sanitary just outside of foundation to inside of back of house -DWV under foam -Underslab water lines
Underslab Electrical Inspection - Residential Passed 7/20/2022 07/20/2022
Miscellaneous Inspection Failed 12/7/2022 12/07/2022
Misc
Corrective Action Required
12/03/2021
Talked with Shane 11/30 and he explained that the roof deck was altered to be from 6" to 10" and would be instaled asap. windows and doors are month out. MARK HARDING 12/07/2022 7:11 AM
Miscellaneous Inspection Passed 1/17/2023 1/17/2023 01/17/2023
Misc
Resolved
01/17/2023
Talked with Shane 11/30 and he explained that the roof deck was altered to be from 6" to 10" and would be instaled asap. windows and doors are month out. MARK HARDING 12/07/2022 7:11 AM
Electrical Service Inspection Passed 6/19/2023 6/19/2023 06/19/2023
Miscellaneous Inspection Passed 11/20/2023
Misc
Corrective Action Required
11/20/2023
11/20/23 -Windows and garage doors have been installed, roofing work to begin this week
Sewer Service Inspection - R Passed 04/10/2024
Misc
Informational
04/10/2024
4-10-24 Dustin A, Inspected Cut in Y installation, Talked with MH and had me do sewer service inspection while i was there since it was short. Passed Also had line tv'd to check for existing sewer stubs. After talking with brent decided to install Y 44 ft from DS manhole
Water Service Inspection - R Partial 4/12/2024 04/12/2024
Misc
Corrective Action Required
04/12/2024
Partial from meter location to house
Water Service Inspection - R Passed 4/15/2024 (8:30) 4/15/2024 04/15/2024
Misc
Resolved
04/15/2024
Partial from meter location to house
All Rough Inspection - Residential Partial 7/19/2024 7/19/2024 07/19/2024
Misc
Corrective Action Required
07/19/2024
Ok to cover walls on rooftop
All Rough Inspection - Residential Failed 12/18/2024 12/18/2024 12/18/2024
Misc
Corrective Action Required
07/19/2024
Ok to cover walls on rooftop 12/17/24 -complete all framing and MEPs
Gas Service Inspection - Residential Failed 1/15/2025 1/15/2025 01/15/2025
Misc
Corrective Action Required
01/15/2025
- Pressure test passed - Provide bonding of gas piping.
Gas Service Inspection - Residential Passed 1/16/2025 1/16/2025 01/16/2025
Misc
Resolved
01/16/2025
- Pressure test passed - Provide bonding of gas piping.
All Rough Inspection - Residential Partial 2/7/2025 2/7/2025 02/07/2025
Misc
Corrective Action Required
12/18/2024
Ok to cover walls on rooftop 12/17/24 -complete all framing and MEPs **Rooftop space exterior walls and ceiling ok for microcement
Documents & Images
Date Uploaded File Type Document Name
11/06/2019 Letter Codes Residential Plan Review
01/17/2020 DOC011720-01172020145642
01/17/2020 DOC011720-01172020145722
01/17/2020 Letter DS Building Permit
01/17/2020 Receipt Receipt for transaction: 2020-000215
01/22/2020 Photograph DOC012220-01222020111556
01/22/2020 Letter DOC012220-01222020111606
01/22/2020 Plot Plan DOC012220-01222020111625
11/10/2020 Engineer Report/Study 20193251
12/15/2020 Letter INSPECTION SUMMARY
05/03/2021 Letter INSPECTION SUMMARY
05/07/2021 Letter INSPECTION SUMMARY
07/02/2021 Letter Codes 180 Day Letter
11/10/2021 Letter Codes 180 Day Letter
12/03/2021 Letter INSPECTION SUMMARY
06/08/2022 Letter INSPECTION SUMMARY
06/23/2022 Letter INSPECTION SUMMARY
07/20/2022 Letter INSPECTION SUMMARY
07/20/2022 Letter INSPECTION SUMMARY
11/28/2022 Veritasi Lakeview Roof Structure STAMPED
11/28/2022 PRRES20193251 ROOF DECK STAMPED
11/29/2022 Drawing Lakeview Approved Drawings
11/29/2022 Drawing Lakeview2 Approved Drawings
11/29/2022 Drawing Lakeview3 Approved Drawings
11/29/2022 Drawing Lakeview4 Approved Drawings
11/29/2022 Drawing Lakeview5 Approved Drawings
11/29/2022 Drawing Lakeview6 Approved Drawings
11/29/2022 Drawing Lakeview7 Approved Drawings
11/29/2022 Drawing Lakeview8 Approved Drawings
11/29/2022 Drawing Lakeview9 Approved Drawings
11/29/2022 Drawing Lakeview10 Approved Drawings
11/29/2022 Drawing Lakeview11
12/07/2022 Letter INSPECTION SUMMARY
01/17/2023 Letter INSPECTION SUMMARY
06/06/2023 Letter Codes 140 Day Letter
06/19/2023 Letter INSPECTION SUMMARY
11/08/2023 Letter Codes 140 Day Letter
11/20/2023 Letter INSPECTION SUMMARY
04/02/2024 24-043 Veritasi As-built - SUBMITTAL
04/04/2024 Approved Plans ENGINEER REPORT AND DETAILS FOR SPACE ON ROOF
04/10/2024 Letter INSPECTION SUMMARY
04/10/2024 Letter INSPECTION SUMMARY
04/12/2024 Letter INSPECTION SUMMARY
04/15/2024 Letter INSPECTION SUMMARY
07/19/2024 Letter INSPECTION SUMMARY
12/10/2024 Letter Codes 140 Day Letter
12/18/2024 Letter INSPECTION SUMMARY
01/15/2025 Letter INSPECTION SUMMARY
01/16/2025 Letter INSPECTION SUMMARY
02/07/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home