Permit Application Status

PRRES20190262


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20190262
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE UNCOVERED DECK FINISHED AND UNFINISHED BASEMENT
02/06/2019
02/22/2019
12/20/2019
Locations
Contacts
LANDROCK SIGNATURE HOMES LLC, Address:4335 MCGEE ST, Phone:(816) 863-5588  
MIDWEST HEATING COOLING & PLUMBING, Address:13228 HOLMES RD, Phone:(816) 943-8513  
PREMIER ELECTRIC & LIGHTING DESIGN, Address:PO BOX 1311, Phone:(816) 564-7660  
CENTURY PLUMBING, Address:14001 CENTURY LN, Phone:(816) 765-6066  
JP@LANDROCKKC.COM  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 02/08/2019 02/21/2019
Steve Conrick
City infrustructure
Corrective Action Required
02/11/2019

Show all manholes, water valve boxes, fire hydrants, and stormwater structures. ***Missing MH in rear yard***
Lot elevations
Corrective Action Required
02/11/2019

Existing and finish elevations at all property corners must be provided on the plot plan. ***Provide existing and proposed elevations at the edge of the s/e as shown on the MDP***
Miscellaneous Correction
Corrective Action Required
02/11/2019

***The elevations/contours aren't lining up with what was proposed on lots 12 or 14.***
Residential Plan Review Approved 02/08/2019 02/06/2019
Brandon Kalwei
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,471.70 $1,471.70 Paid 02/22/2019
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 02/22/2019
8331507-Sewer Connection Fee $570.00 $570.00 Paid 02/22/2019
8331401-Water Tap Fee $3,409.00 $3,409.00 Paid 02/22/2019
8350015-Water Meter Fee $408.37 $408.37 Paid 02/22/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 3/28/2019 (11:30) 3/28/2019 at 11:45 AM 03/28/2019
Underslab Plumbing Inspection - Residential Not Ready 4/17/2019 4/17/2019 at 8:00 AM 04/17/2019
Misc
Corrective Action Required
04/17/2019
1. NO ADDRESS VISIBLE 2. NO BACKFILL HAS BEEN DONE. 3. NO ACCESS 4. EROSION CONTROL IS NOT IN COMPIANCE
Sewer Service Inspection - R Partial 4/22/2019 4/22/2019 at 1:30 PM 04/22/2019
Misc
Informational
04/22/2019
first 50' of sewer from house. tractor broke down.
Water Service Inspection - R Partial 4/22/2019 04/22/2019
Sewer Service Inspection - R Passed 4/23/2019 4/23/2019 at 9:45 AM 04/23/2019
Misc
Informational
04/22/2019
first 50' of sewer from house. tractor broke down.
Water Service Inspection - R Partial 4/23/2019 04/23/2019
Water Service Inspection - R Passed 4/25/2019 (1:00) 4/25/2019 at 1:15 PM 04/25/2019
Underslab Plumbing Inspection - Residential Passed 4/26/2019 4/26/2019 at 8:35 AM 04/26/2019
Misc
Resolved
04/26/2019
1. NO ADDRESS VISIBLE 2. NO BACKFILL HAS BEEN DONE. 3. NO ACCESS
Electrical Service Inspection Passed 9/4/2019 09/04/2019
Gas Service Inspection - Residential Failed 9/4/2019 09/04/2019
Miscellaneous Correction
Corrective Action Required
09/04/2019
** No pressure on system **
All Rough Inspection - Residential Failed 9/4/2019 09/04/2019
Misc
Corrective Action Required
09/04/2019
** Missing double joist hanger at basement stairs ** Garage is missing rafter ties every 4’ ** Garage ridge beam is too small ** Living room I-beam appears not to be properly supported in the basement
All Rough Inspection - Residential Passed 9/11/2019 9/11/2019 09/11/2019
Misc
Resolved
09/11/2019
** Missing double joist hanger at basement stairs ** Garage is missing rafter ties every 4’ ** Garage ridge beam is too small ** Living room I-beam appears not to be properly supported in the basement
Gas Service Inspection - Residential Passed 9/11/2019 9/11/2019 09/11/2019
Miscellaneous Correction
Resolved
09/11/2019
** No pressure on system **
Driveway Inspection Partial 9/19/2019 9/19/2019 09/18/2019
Misc
Informational
09/18/2019
PRE POUR INSPECTION The forms are set and there appears to be sufficient compacted aggregate.
Sidewalk Inspection Partial 9/26/2019 09/26/2019
Misc
Informational
09/26/2019
SEPTEMBER 26, 2019 PRE POUR INSPECTION SIDEWALK Upon arrival, all forms appear to be within Lees Summit and ADA spec. There has been gravel installed. The gravel is the correct size and it is compacted.
Driveway Inspection Passed 9/27/2019 10/08/2019
Misc
Informational
09/18/2019
PRE POUR INSPECTION The forms are set and there appears to be sufficient compacted aggregate.
Occupancy Inspection - Codes Residential Failed 12/18/2019 12/18/2019
Misc
Corrective Action Required
12/18/2019
- post property address - install range in kitchen - install dishwasher in kitchen - garage door needs to be self closing/latching - finish plumbing in front half bathroom - rear sliding doors need to have second locking devise installed - master shower needs to be complete - handrail needs to be complete for stairs going to basement - hot water heater discharge pipe needs to be installed - check microwave for hardwired - furnace utility room electrical needs to be complete - sheet rock needs to be installed under stair stringers in unfinished basement - I joist in unfinished basement need to be fire protected - downstairs garage doors need to be self closing/latching - plumbing in basement bathroom needs to be complete - anti symphony devise needs to be installed on hose bib in basement - electrical needs to be complete in downstairs bedroom - light fixture above kitchen island needs to be installed - secure electrical meter conduit below meter to foundation - joist hanger on south side of deck needs to nailed completely - seal exterior lights and penetrations
Occupancy Inspection - Codes Residential Failed 12/19/2019 12/19/2019 12/20/2019
Misc
Corrective Action Required
12/18/2019
- garage door needs to be self closing/latching, not latching from halfway point - rear sliding doors need to have second locking devise installed - master shower needs to be complete - I joist in unfinished basement need to be fire protected - plumbing in basement bathroom needs to be complete - secure electrical meter conduit below meter to foundation - joist hanger on south side of deck needs to nailed completely - seal exterior lights and penetrations
Occupancy Inspection - Codes Residential Full C of O 12/20/2019 12/20/2019
Misc
Resolved
12/20/2019
Documents & Images
Date Uploaded File Type Document Name
02/11/2019 Letter Codes Residential Plan Review
02/22/2019 Receipt Receipt for transaction: 2019-000593
02/22/2019 Letter Codes Building Permit
02/22/2019 Plot Plan DOC022219-002
03/13/2019 Engineer Report/Study 4517 SW Nautilius Pl_Lot 13 Creekside at Raintree Final_2019.03.08_SiteObv PierDes_LSMO_ABI
03/28/2019 Letter INSPECTION SUMMARY
03/28/2019 Engineer Report/Study 4517 SW Nautilus Pl_Lot 13 Creekside at Raintree Lake Final_2019.03.25_HPier_LSMO_ABI
04/17/2019 Letter INSPECTION SUMMARY
04/22/2019 Letter INSPECTION SUMMARY
04/22/2019 Letter INSPECTION SUMMARY
04/23/2019 Letter INSPECTION SUMMARY
04/23/2019 Letter INSPECTION SUMMARY
04/25/2019 Letter INSPECTION SUMMARY
04/26/2019 Letter INSPECTION SUMMARY
05/14/2019 Engineer Report/Study 4517 SW Nautilus Pl_Lot 13 Creekside at Raintree Lake Final_2019.04.29_GBSlab_LSMO_Pat Cochran
09/04/2019 Letter INSPECTION SUMMARY
09/04/2019 Letter INSPECTION SUMMARY
09/04/2019 Letter INSPECTION SUMMARY
09/11/2019 Letter INSPECTION SUMMARY
09/11/2019 Letter INSPECTION SUMMARY
09/18/2019 Letter INSPECTION SUMMARY
09/26/2019 SEPTEMBER 26, 2019 PRE-POUR SIDEWALK
09/26/2019 Letter INSPECTION SUMMARY
10/08/2019 Letter INSPECTION SUMMARY
12/18/2019 Letter INSPECTION SUMMARY
12/19/2019 Letter INSPECTION SUMMARY
12/20/2019 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents