Summary
PRRES20151270
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
HOUSE W/ COVERED DECK - 2 STORY - FINISHED WALKOUT BASEMENT *ROOF TRUSSES
06/05/2015
06/15/2015
12/02/2015
03/28/2016
Locations
Contacts
SUMMIT CUSTOM HOMES LLC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
CENTURY PLUMBING, Address:14001 CENTURY LN, Phone:(816) 765-6066  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 06/15/2015 06/12/2015
James Fletchall
Plot Plan Review Rejected 06/11/2015
James Fletchall
Residential Plan Review Approved 06/12/2015 06/10/2015
Tara Mitchell
Plot Plan Review (P&D) Approved 06/09/2015
Ron Seyl
Residential Plan Review Rejected 06/09/2015 06/05/2015
Tara Mitchell
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $1,343.24 $1,343.24 Paid 06/15/2015
Right of Way Permit Fee $75.00 $75.00 Paid 06/15/2015
8331507-Sewer Connection Fee $630.00 $630.00 Paid 06/15/2015
Water Tap Fee $3,198.00 $3,198.00 Paid 06/15/2015
Water Meter Fee $354.05 $354.05 Paid 06/15/2015
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 7/7/2015 (2:45) 7/7/2015 at 12:00 AM 07/07/2015
Foundation Inspection - Residential Failed 7/16/2015 (11:30) 7/16/2015 at 12:00 AM 07/16/2015
Misc
Corrective Action Required
07/16/2015
-NO REINFORCING STEEL IN CERNERS ARE TIED TOGETHER DO NOT POUR
Foundation Inspection - Residential Passed 7/16/2015 (1:00) 7/16/2015 at 12:00 AM 07/16/2015
Misc
Resolved
07/16/2015
-NO REINFORCING STEEL IN CERNERS ARE TIED TOGETHER DO NOT POUR
Underslab Plumbing Inspection - Residential Passed 7/30/2015 7/30/2015 at 12:00 AM 07/30/2015
Sewer Service Inspection - R Passed 7/30/2015 (11:30) 7/30/2015 at 12:00 AM 07/30/2015
Water Service Inspection - R Failed 8/3/2015 (1:00) 8/3/2015 at 12:00 AM 08/03/2015
Misc
Corrective Action Required
08/03/2015
METER IS SET 9" FROM THE LID. 14"-18" ALLOWED
Water Service Inspection - R Passed 8/3/2015 (2:30) 8/3/2015 at 12:00 AM 08/03/2015
Misc
Resolved
08/03/2015
METER IS SET 9" FROM THE LID. 14"-18" ALLOWED
All Rough Inspection - Residential Failed 11/9/2015 11/9/2015 at 12:00 AM 11/09/2015
Misc
Corrective Action Required
11/09/2015
-REAR WALL IS NOT FRAMED IN ACCORDANCE WITH DETAIL S 4.7 2. NO NAILING. TOP AND BOTTOM HOLD DOWNS INSTALLED PER DETAIL. -SOUTH GREAT ROOM WALL NOT FRAMED PER PLAN. 2x6 STUDS SHOULD BE 12" O.C. FULL HEIGHT FLOOR TO CEILING. HINGE CREATED AT DOUBLE TOP PLATE. HAVE ENGINEER ADDRESS OR FRAME PER PLAN. -REAR DINING AND MASTER BED WALLS NOT FRAMED PER STRUCTURAL DETAIL. -FIRESTOP TRIANGULAR DEADSPACES 1st FLOOR HALL/KITCHEN AND OTHER PENETRATIONS IN FIREBLOCKING IN CHASES AND VAULTS. -MAKE SURE 12x12 TUB MOTOR ACCESS WILL BE AVAILABLE. -NEED 3 2x6 SUD SUPPORT SOUTH END LVL GOING INTO DINING. -FIREBLOCK MECHANICAL CHASE BY GARAGE. -ATTIC ACCESS OVER MASTER BED. 2ND FLOOR NORTH BED, SCREWS USED IN HANGER AT GIRDER TRUSS CONNECTION. REPLACE WITH NAILS AS REQUIRED PER PLANS. -SOLID BLOCK FLOOR JOISTS PER PLAN FOR KITCHEN ISLAND. -INSTALL ELECTRICAL FOR SUMP UNDER GARAGE. -SUBMIT INSPECTION FOR SUSPENDED GARAGE SLAB. -ANCHOR COLUMNS UNDER GARAGE SLAB. -INSTALL SECURITY BLOCKS AT EXTERIOR DOORS. -SEAL ALL PENETRATIONS BETWEEN FLOORS. Do not insulate.
Corrective Action Required
11/09/2015
Gas Service Inspection - Residential Passed 11/9/2015 11/9/2015 at 12:00 AM 11/09/2015
Electrical Service Inspection Failed 11/9/2015 11/9/2015 at 12:00 AM 11/09/2015
Misc
Corrective Action Required
11/09/2015
BOND MAIN PANEL ENCLOSURE, NO GREEN SCREW INSTALLED.
Gas Piping Inspection - Residential Passed 11/09/2015
Driveway Inspection Passed 11/12/2015 at 12:00 AM 11/13/2015
All Rough Inspection - Residential Failed 11/17/2015 11/17/2015 at 12:00 AM 11/17/2015
Misc
Corrective Action Required
11/09/2015
-REAR WALL IS NOT FRAMED IN ACCORDANCE WITH DETAIL S 4.7 2. NO NAILING. TOP AND BOTTOM HOLD DOWNS INSTALLED PER DETAIL. -SOUTH GREAT ROOM WALL NOT FRAMED PER PLAN. 2x6 STUDS SHOULD BE 12" O.C. FULL HEIGHT FLOOR TO CEILING. HINGE CREATED AT DOUBLE TOP PLATE. HAVE ENGINEER ADDRESS OR FRAME PER PLAN. -REAR DINING AND MASTER BED WALLS NOT FRAMED PER STRUCTURAL DETAIL. -HALL/KITCHEN AND OTHER PENETRATIONS IN FIREBLOCKING IN CHASES AND VAULTS. -MAKE SURE 12x12 TUB MOTOR ACCESS WILL BE AVAILABLE. Okay insulate
All Rough Inspection - Residential Failed 11/30/2015 at 12:00 AM 11/30/2015
Misc
Corrective Action Required
11/17/2015
-SOUTH LIVING ROOM WALL NOT FRAMED FLOOR TO CEILING. STRAPS INSTALLED AT PLATE LINE. SUBMIT ENGINEER REPORT TO CODES ADMIN. STATING THIS IS AN APPROVED ALTERNATIVE TO THE ORIGINALLY PRESCRIBED FRAMING METHOD. -MAKE SURE 12x12 TUB MOTOR ACCESS WILL BE AVAILABLE. WILL CHECK AT FINAL. OKAY TO COVER AT YOUR OWN RISK PENDING ENGINEER REPORT.
Electrical Service Inspection Passed 12/22/2015 12/22/2015
Misc
Resolved
12/22/2015
BOND MAIN PANEL ENCLOSURE, NO GREEN SCREW INSTALLED.
Sidewalk Inspection Passed 1/5/2016 01/06/2016
All Rough Inspection - Residential Passed 02/22/2016
Misc
Resolved
02/22/2016
-SOUTH LIVING ROOM WALL NOT FRAMED FLOOR TO CEILING. STRAPS INSTALLED AT PLATE LINE. SUBMIT ENGINEER REPORT TO CODES ADMIN. STATING THIS IS AN APPROVED ALTERNATIVE TO THE ORIGINALLY PRESCRIBED FRAMING METHOD. -MAKE SURE 12x12 TUB MOTOR ACCESS WILL BE AVAILABLE. WILL CHECK AT FINAL. OKAY TO COVER AT YOUR OWN RISK PENDING ENGINEER REPORT.
Occupancy Inspection - Codes Residential Failed 2/22/2016 2/22/2016 02/22/2016
Misc
Corrective Action Required
02/22/2016
-INSTALL FINAL GRADE, SOD -BRING WATER METER FLUCH WITH FINAL GRADE FOR INSPECTION -3 2x12 DECK GIRDER HAS NO BEARING AT NORTH END, INSTALL POST -INSTALL SECURITY SCREWS REAR DOORS -MAX FUSE FOR AC UNITS IS 30 AND 40 AMP. INSTALLED 50 AMP FOR BOTH. -LOCATION OF PLUMBING VENT TERMINAL SHALL NOT BE LOCATED LESS THAN 4 FEET BENETH OPENABLE WINDOW OR 10 FEET HORIZONTALLY. NORTH 2ND FLOOR BED.
Occupancy Inspection - Codes Residential Temporary C of O 02/23/2016
Misc
Corrective Action Required
02/23/2016
-INSTALL FINAL GRADE, SOD -OBTAIN IRRIGATION PERMIT -3 2x12 DECK GIRDER HAS NO BEARING AT NORTH END, INSTALL POST
Occupancy Inspection - Codes Residential Full C of O 03/28/2016
Misc
Resolved
03/28/2016
-INSTALL FINAL GRADE, SOD -OBTAIN IRRIGATION PERMIT -3 2x12 DECK GIRDER HAS NO BEARING AT NORTH END, INSTALL POST
Documents & Images
Date Uploaded File Type Document Name
06/15/2015 Letter Codes Building Permit
06/15/2015 Receipt Receipt for transaction: 2015-002880
06/15/2015 Plot Plan DOC061515-010
07/07/2015 Letter Inspection Summary
07/16/2015 Letter Inspection Summary
07/16/2015 Letter Inspection Summary
07/30/2015 Letter Inspection Summary
08/03/2015 Letter Inspection Summary
08/03/2015 Letter Inspection Summary
09/15/2015 Engineer Report/Study DOC091515-002
11/09/2015 Letter Inspection Summary
11/17/2015 Letter Inspection Summary
11/30/2015 Letter Inspection Summary
12/02/2015 Engineer Report/Study DOC120215-013
12/22/2015 Letter Inspection Summary
01/19/2016 Letter DOC011916-003
02/22/2016 Letter Inspection Summary
02/23/2016 Letter Codes Temporary Certificate of Occupancy
03/07/2016 Engineer Report/Study DOC030716
03/22/2016 Engineer Report/Study DOC032216-006
03/28/2016 Letter Field Certificate of Occupancy
03/29/2016 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home