Permit Application Status

PRCOM20251165


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20251165
Building Permit - Commercial
Issued
NEW MULTI-FAMILY
THE REUNION AT BLACKWELL - BUILDING 23, TYPE C -PLEX PLAN REVIEW COMPLETED UNDER PRCOM20250089
03/31/2025
06/17/2025
Locations
Contacts
Avital Homes, LLC, Address:7500 W 151st Street, #23100, Phone:(816) 914-7128  
RED DOG ELECTRIC SERVICES, Address:PO BOX 1, Phone:(913) 208-4816  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
COLLINS WEBB ARCHITECTURE LLC, Address:307 SW MARKET ST, Unit B, Phone:(816) 249-2270  
Doug Jenson - Avital Homes, Phone:(816) 266-0685  
Reviews
Review Type Outcome Est. Completion Date Completed
Final Development Plan Review Approved 04/14/2025 03/31/2025
Mike Weisenborn
Building Plan Review Approved with Conditions 04/14/2025 03/31/2025
Mike Weisenborn
Miscellaneous Correction
Resolved
06/17/2025

Foundation and underlsab plumbing only released at this time. Substantial completion on the santiary and water before private connections can be made. Full access and live hydrants required prior to release of vertical construction.
Licensed Contractors Approved 04/14/2025 03/31/2025
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
Water Tap Fee $10,595.00 $10,595.00 Paid 04/03/2025
Water Meter Fee $1,066.76 $1,066.76 Paid 04/03/2025
Sanitary Sewer Development Fee $6,101.00 $6,101.00 Paid 04/03/2025
Valuation Fee for New 3 or 4 Family $4,451.71 $4,451.71 Paid 04/03/2025
Residential Excise Tax Fee $2,480.64 $2,480.64 Paid 04/03/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Piers/Caissons Inspection - Commercial Pending
Erosion Control Inspection Pending
PW-Devices for Erosion and Sediment Control
Corrective Action Required
05/05/2025
5-5-25 Dustin A, Erosion control had been installed and construction entrances are being installed.
Electrical Service Inspection Pending
Water Service Inspection Pending
Rated Assembly Inspection Pending
Misc
Corrective Action Required
06/30/2025
No inspection performed discussed with contractor on site
All Rough Inspection - Commercial Pending
Misc
Corrective Action Required
07/31/2025
Not a complete inspection complete all items for re-inspection -Remove all insulation -complete electrical -seal all penetrations in top plates -outlet spacing to comply with code section figure E3901.2 -anchor bolts to be in the middle 1/3 of sill plate -anchor bolts to be within 12” of plate breaks but not closer than 7x the diameter of the bolt -protect dryer vents at top plate and extend 2” below plate -provide 2hr rated electrical boxes at party wall -install putty packs where required per design -provide blocking on sheathing breaks -provide wet rated conductors to under slab electrical -no more than 2 NM to penetrate together through holes -repair all holes and gaps in rated wall -fire rated roof sheathing needs to extend 4’ either side of rated wall -rated wall to be contentious from floor to ceiling -complete all bracing per truss and structural plans -screw rated wall to ul design 8” OC -protect all electrical within 6’ of attic access
Footing Inspection - Commercial Partial 4/23/2025 4/23/2025 04/23/2025
Misc
Informational
04/23/2025
Footings okay excluding grade beam. (Grade beam not dug)
Footing Inspection - Commercial Passed 4/24/2025 4/24/2025 04/24/2025
Misc
Resolved
04/24/2025
Footings okay excluding grade beam. (Grade beam not dug)
Footing Inspection - Commercial Passed 04/28/2025
Misc
Informational
04/28/2025
Grade beam stem wall
Erosion Control Inspection Partial 5/5/2025 5/5/2025 05/05/2025
PW-Devices for Erosion and Sediment Control
Corrective Action Required
05/05/2025
5-5-25 Dustin A, Erosion control had been installed and construction entrances are being installed.
Underslab Plumbing Inspection - Commercial Failed 5/13/2025 5/13/2025 05/13/2025
Misc
Corrective Action Required
05/13/2025
Provide documentation showing compliance with sec 706 & 708 of the ipc
Underslab Plumbing Inspection - Commercial Passed 5/16/2025 5/16/2025 05/16/2025
Misc
Resolved
05/16/2025
Provide documentation showing compliance with sec 706 & 708 of the ipc
Rated Assembly Inspection Failed 6/30/2025 6/30/2025 06/30/2025
Misc
Corrective Action Required
06/30/2025
No inspection performed discussed with contractor on site
Sewer Service Inspection Passed 7/18/2025 7/18/2025 07/18/2025
Misc
Corrective Action Required
07/18/2025
7-18-25 Dustin A, both sewer stubs for duplex are attached to existing 6 in sewer stub. Pass
All Rough Inspection - Commercial Failed 7/24/2025 7/24/2025 07/24/2025
Misc
Corrective Action Required
07/24/2025
Not a complete inspection -Provide city stamped truss plans on site -Remove all insulation -complete electrical -seal all penetrations in top plates -outlet spacing to comply with code section figure E3901.2 -anchor bolts to be in the middle 1/3 of sill plate -provide Boca plate protection for dryer vents at top plate -provide 2hr rated electrical boxes at party wall -install putty packs where required per design
All Rough Inspection - Commercial Failed 7/31/2025 7/31/2025 07/31/2025
Misc
Corrective Action Required
07/24/2025
Not a complete inspection complete all items for re-inspection -Remove all insulation -complete electrical -seal all penetrations in top plates -outlet spacing to comply with code section figure E3901.2 -anchor bolts to be in the middle 1/3 of sill plate -anchor bolts to be within 12” of plate breaks but not closer than 7x the diameter of the bolt -protect dryer vents at top plate and extend 2” below plate -provide 2hr rated electrical boxes at party wall -install putty packs where required per design -provide blocking on sheathing breaks -provide wet rated conductors to under slab electrical -no more than 2 NM to penetrate together through holes -repair all holes and gaps in rated wall -fire rated roof sheathing needs to extend 4’ either side of rated wall -rated wall to be contentious from floor to ceiling -complete all bracing per truss and structural plans -screw rated wall to ul design 8” OC -protect all electrical within 6’ of attic access
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home