Permit Application Status

PRCOM20242210


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20242210
Building Permit - Commercial
Certificate of Occupancy
NEW TENANT FINISH
30HOP - NEW TENANT FINISH FOR BAR AND RESTAURANT
05/02/2024
07/17/2024
12/01/2024
01/02/2025
Locations
Contacts
Goebel Mitts Construction, Address:6600 College Blvd. Suite 320 , Phone:(913) 787-1738  
Will Mitts , Address:6600 College Blvd. Suite 320 , Phone:(913) 787-1738  
B&C Mechanical Services LLC, Address:19403 W 335th St, Phone:(913) 244-7693  
THREE DIAMOND ELECTRIC LLC, Address:27606 E PINK HILL RD, Phone:(816) 228-5470  
INTEGRITY PLUMBING SERVICES LLC, Address:405 SW Nelson Dr., Phone:(816) 803-9032  
Schwerdt Design Group, Address:2231 SW Wanamaker Rd, Phone:(785) 273-7540  
Jeff Renterghem - Pappa George Haymes, Address:640 N. LaSalle St., Suite 400, Phone:(312) 650-7315  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 08/21/2024 08/21/2024
Craig Hill
Construction documents for fire alarm systems
Corrective Action Required
08/14/2024

Released for construction: Call 969-1300 to schedule an alarm test.
Sprinkler Plan Review Released for Construction 08/19/2024 08/19/2024
Craig Hill
Alarm Plan Review Rejected 08/09/2024 08/07/2024
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
08/07/2024

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide PE stamped plans.
Building Plan Review Approved with Conditions 07/15/2024 07/15/2024
Joe Frogge
License Tax - Payment
Corrective Action Required
07/08/2024

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is informational. The fee will be $29,766.00 6/3/2024 - Acknowledged in letter.
Project cost
Resolved
07/15/2024

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is informational. 6/3/2024 - Not addressed.
Health Dept Inspection
Corrective Action Required
07/08/2024

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7162. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 6/3/2024 - Not addressed.
Fire Plan Review Approved with Conditions 07/15/2024 07/12/2024
Jim Eden
Portable fire extinguishers for commercial cooking equipment.
Resolved
07/12/2024

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Provide a K Class fire extinguisher and signage at the manual pull station for the hood system. The location shown is not at the manual pull station for the hood system. Verified at inspection.
Portable fire extinguishers - general
Resolved
07/12/2024

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Show the location of ABC type fire extinguishers. Provide more than one, in a conspicuous location in a normal path of travel.
Miscellaneous Correction
Resolved
07/12/2024

Construction documents - Fire protection systems
Corrective Action Required
07/12/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide plans for extending the automatic fire sprinkler to the patio.
Licensed Contractors Approved 07/15/2024 07/08/2024
Joe Frogge
LC - General Contractor
Resolved
07/12/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and the name, email address & phone number for the on-site contact which is where inspection reports will be sent. 6/3/2024 - Acknowledged in letter.
LC - MEP Subs
Resolved
07/12/2024

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 6/3/2024 - Acknowledged in letter.
Health Department Review Approved 06/11/2024
Joe Frogge
Fire Plan Review Rejected 06/11/2024 06/03/2024
Jim Eden
Construction documents for fire alarm systems
Resolved
06/03/2024

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for tenant finish alarm system.
Construction documents - Fire protection systems
Resolved
06/03/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for tenant finish sprinkler system.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
06/03/2024

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Provide a K Class fire extinguisher and signage at the manual pull station for the hood system. The location shown is not at the manual pull station for the hood system. Verified at inspection.
Portable fire extinguishers - general
Corrective Action Required
06/03/2024

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Show the location of ABC type fire extinguishers. Provide more than one, in a conspicuous location in a normal path of travel.
Miscellaneous Correction
Resolved
06/03/2024

5307.3 Insulated liquid carbon dioxide systems used in beverage dispensing applications. Insulated liquid carbon dioxide systems with more than 100 pounds (45.4 kg) of carbon dioxide used in beverage dispensing applications shall comply with Section 5307.3.1. Provide detection our ventilation in CO2 beverage service gas area.
Miscellaneous Correction
Resolved
06/03/2024

Provide outdoor emergency lighting and exit signage on the patio to direct and illuminate the discharge pathway to the exit gates/openings.
Miscellaneous Correction
Resolved
06/03/2024

Several plans in the permit set for construction are marked NOT FOR CONSTRUCTION. Provide revised plans.
Miscellaneous Correction
Corrective Action Required
05/24/2024

Provide a detail for the covering of the patio.
Building Plan Review Rejected 06/11/2024 06/03/2024
Joe Frogge
License Tax - Payment
Corrective Action Required
05/24/2024

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is informational. The fee will be $29,766.00 6/3/2024 - Acknowledged in letter.
Project cost
Corrective Action Required
05/24/2024

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is informational. 6/3/2024 - Not addressed.
Health Dept Review
Resolved
06/11/2024

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 797-7162. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is informational. 6/3/2024 - Not addressed.
Health Dept Inspection
Corrective Action Required
05/24/2024

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7162. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 6/3/2024 - Not addressed.
IBC 602.1 Type of Construction - general
Resolved
06/03/2024

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Update Code Summary to show correct construction type which is 5B. (fyi - if you opt to use wood studs, the wall supporting grease hood must remain non-combustible.)
NEC Article 110.26 (C)(2) Large equipment
Resolved
06/03/2024

2017 NEC Article 110.26 (C)(3) Personnel Doors. Where equipment rated 800 A or more that contains overcurrent devices, switching devices, or control devices is installed and there is a personnel door(s) intended for entrance to and egress from the working space less than 25 feet from the nearest edge of the working space, the door(s) shall open in the direction of egress and be equipped with panic hardware. Action required: Provide panic hardware on door out of mechanical room that contains panel MDP1
Misc
Resolved
06/03/2024

Remove "NOT FOR CONSTRUCTION" note in title block.
Licensed Contractors Rejected 06/11/2024 06/03/2024
Joe Frogge
LC - General Contractor
Corrective Action Required
05/24/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and the name, email address & phone number for the on-site contact which is where inspection reports will be sent. 6/3/2024 - Acknowledged in letter.
LC - MEP Subs
Corrective Action Required
05/24/2024

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 6/3/2024 - Acknowledged in letter.
Fire Plan Review Rejected 05/14/2024 05/14/2024
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
05/14/2024

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for tenant finish alarm system.
Construction documents - Fire protection systems
Corrective Action Required
05/14/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for tenant finish sprinkler system.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
05/14/2024

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Provide a K Class fire extinguisher and signage at the manual pull station for the hood system.
Portable fire extinguishers - general
Corrective Action Required
05/14/2024

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Show the location of ABC type fire extinguishers.
Miscellaneous Correction
Corrective Action Required
05/14/2024

Miscellaneous Correction
Corrective Action Required
05/14/2024

5307.3 Insulated liquid carbon dioxide systems used in beverage dispensing applications. Insulated liquid carbon dioxide systems with more than 100 pounds (45.4 kg) of carbon dioxide used in beverage dispensing applications shall comply with Section 5307.3.1. Provide detection our ventilation in CO2 beverage service gas area.
Miscellaneous Correction
Corrective Action Required
05/14/2024

Provide outdoor emergency lighting and exit signage on the patio to direct and illuminate the discharge pathway to the exit gates/openings.
Miscellaneous Correction
Corrective Action Required
05/14/2024

Several plans in the permit set for construction are marked NOT FOR CONSTRUCTION. Provide revised plans.
Miscellaneous Correction
Corrective Action Required
05/14/2024

Provide a detail for the covering of the patio.
Building Plan Review Rejected 05/14/2024 05/13/2024
Joe Frogge
License Tax - Payment
Corrective Action Required
05/07/2024

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is informational. The fee will be $29,766.00
Project cost
Corrective Action Required
05/07/2024

The project cost, which is used to establish the permit fee, has not been provided. Action required: Comment is informational.
Health Dept Review
Corrective Action Required
05/07/2024

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 797-7162. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is informational.
Health Dept Inspection
Corrective Action Required
05/07/2024

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7162. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational.
IBC 602.1 Type of Construction - general
Corrective Action Required
05/07/2024

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Update Code Summary to show correct construction type which is 5B. (fyi - if you opt to use wood studs, the wall supporting grease hood must remain non-combustible.)
NEC Article 110.26 (C)(2) Large equipment
Corrective Action Required
05/07/2024

2017 NEC Article 110.26 (C)(3) Personnel Doors. Where equipment rated 800 A or more that contains overcurrent devices, switching devices, or control devices is installed and there is a personnel door(s) intended for entrance to and egress from the working space less than 25 feet from the nearest edge of the working space, the door(s) shall open in the direction of egress and be equipped with panic hardware. Action required: Provide panic hardware on door out of mechanical room that contains panel MDP1
Misc
Corrective Action Required
05/14/2024

Remove "NOT FOR CONSTRUCTION" note in title block.
Licensed Contractors Rejected 05/14/2024 05/07/2024
Joe Frogge
LC - General Contractor
Corrective Action Required
05/07/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and the name, email address & phone number for the on-site contact which is where inspection reports will be sent.
LC - MEP Subs
Corrective Action Required
05/07/2024

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $4,461.22 $4,461.22 Paid 07/17/2024
7232302-Commercial License Tax Fee $29,766.00 $29,766.00 Paid 07/17/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 7/19/2024 07/19/2024
THE FOLLOWING AREAS ARE APPROVED
Informational
07/19/2024
-underslab gas line at patio for heater
Underslab Plumbing Inspection - Commercial Partial 7/25/2024 7/25/2024 07/25/2024
THE FOLLOWING AREAS ARE APPROVED
Informational
07/19/2024
-underslab gas line at patio for heater -Bathroom group, sanitary to bar, Kitchen area complete
Underslab Plumbing Inspection - Commercial Passed 7/26/2024 07/26/2024
THE FOLLOWING AREAS ARE APPROVED
Resolved
07/26/2024
-underslab gas line at patio for heater -Bathroom group, sanitary to bar, Kitchen area complete
Underslab Electrical Inspection - Commercial Passed 7/31/2024 07/31/2024
In-wall Inspection Failed 8/14/2024 8/14/2024 08/14/2024
Misc
Corrective Action Required
08/14/2024
-Complete all framing and MEPs **OK to 1 side as needed
In-wall Inspection Failed 8/16/2024 8/16/2024 08/16/2024
Misc
Corrective Action Required
08/14/2024
-Complete all framing and MEPs -Secure water and dwv, install grommets at all metal framing **OK to 1 side as needed
In-wall Inspection Failed 8/20/2024 8/20/2024 08/20/2024
Misc
Corrective Action Required
08/16/2024
-Complete all framing and MEPs -Secure water and dwv, install grommets at all metal framing **OK to 1 side as needed
In-wall Inspection Partial 8/21/2024 8/21/2024 08/21/2024
Misc
Corrective Action Required
08/20/2024
**OK to 1 side as needed -Kitchen 104, corridor and office 105 approved to cover
In-wall Inspection Partial 8/22/2024 8/22/2024 08/22/2024
Misc
Corrective Action Required
08/21/2024
**OK to 1 side as needed -Bar 103,Kitchen 104, corridor and office 105 approved to cover
In-wall Inspection Failed 8/27/2024 8/27/2024 08/27/2024
Misc
Corrective Action Required
08/22/2024
**OK to 1 side as needed -Bar 103,Kitchen 104, corridor and office 105 approved to cover -INSULATE COPPER WATER LINES
In-wall Inspection Passed 8/28/2024 08/28/2024
Misc
Resolved
08/28/2024
**OK to 1 side as needed -Bar 103,Kitchen 104, corridor and office 105 approved to cover -INSULATE COPPER WATER LINES
Rated Assembly Inspection Failed 9/9/2024 9/9/2024 09/09/2024
Above Ceiling Inspection Partial 9/9/2024 9/9/2024 09/09/2024
Miscellaneous Correction
Corrective Action Required
09/09/2024
Areas approved to cover: -soffit at dining area
Above Ceiling Inspection Partial 9/11/2024 9/11/2024 09/11/2024
Miscellaneous Correction
Corrective Action Required
09/09/2024
Areas approved to cover: -soffit at dining area -Hard lids at women’s restroom and kitchen corridor
Rated Assembly Inspection Partial 9/11/2024 9/11/2024 09/11/2024
Misc
Corrective Action Required
09/11/2024
-First layer firewall repair at men's room ok
Underslab Plumbing Inspection - Commercial Passed 9/12/2024 9/12/2024 09/12/2024
Rated Assembly Inspection Failed 9/12/2024 9/12/2024 09/12/2024
Misc
Corrective Action Required
09/11/2024
-First layer firewall repair at men's room ok
Above Ceiling Inspection Partial 9/12/2024 9/12/2024 09/12/2024
Miscellaneous Correction
Corrective Action Required
09/11/2024
Areas approved to cover: -soffit at dining area -Hard lids at women’s restroom and kitchen corridor
Above Ceiling Inspection Partial 9/16/2024 09/16/2024
Miscellaneous Correction
Corrective Action Required
09/12/2024
Areas approved to cover: -soffit at dining area -Hard lids at women’s restroom and kitchen corrido -Hard lids at men's restroom - Sofit hard lid front entry
Hood/Duct Inspection Failed 9/16/2024 09/16/2024
Misc
Corrective Action Required
09/16/2024
- pin hole at corner at flange on 5 foot secion inspected on ground
Hood/Duct Inspection Partial 9/25/2024 09/23/2024
Misc
Informational
09/23/2024
5’ welded roof transition piece approved on ground
Rated Assembly Inspection Partial 9/23/2024 9/23/2024 09/23/2024
Misc
Corrective Action Required
09/12/2024
-First layer firewall repair at men's room ok
Underslab Plumbing Inspection - Commercial Passed 9/23/2024 9/23/2024 09/23/2024
Hood/Duct Inspection Failed 10/2/2024 09/26/2024
Misc
Informational
09/23/2024
5’ welded roof transition piece approved on ground
Miscellaneous Correction
Corrective Action Required
09/26/2024
Correct (3) pinholes in welded connection to captive air system
Above Ceiling Inspection Failed 9/26/2024 09/26/2024
Miscellaneous Correction
Corrective Action Required
09/16/2024
Areas approved to cover: -soffit at dining area -Hard lids at women’s restroom and kitchen corrido -Hard lids at men's restroom - Sofit hard lid front entry **9/26/24 -Not ready
Hood/Duct Inspection Failed 9/27/2024 9/27/2024 09/27/2024
Misc
Informational
09/26/2024
5’ welded roof transition piece approved on ground
Miscellaneous Correction
Corrective Action Required
09/26/2024
Correct pinhole in welded connection to captive air system at SE corner
Above Ceiling Inspection Partial 9/27/2024 9/27/2024 09/27/2024
Miscellaneous Correction
Corrective Action Required
09/26/2024
Areas approved to cover: -soffit at dining area -Hard lids at women’s restroom and kitchen corrido -Hard lids at men's restroom -Soffit hard lid front entry -Office area -Kitchen area from equipment line north except at west wall -PVC not allowed in open air plenum
Hood/Duct Inspection Partial 10/2/2024 10/2/2024 10/02/2024
Misc
Informational
09/27/2024
-5’ welded roof transition piece approved on ground -welded connection to captive air system Ok
Miscellaneous Correction
Resolved
10/02/2024
Correct pinhole in welded connection to captive air system at SE corner
Rough Electrical Inspection - Commercial Failed 10/03/2024
Misc
Corrective Action Required
10/03/2024
-Install 200 amp breaker per plan panel P3
Hood/Duct Inspection Partial 10/8/2024 10/8/2024 10/07/2024
Misc
Informational
10/02/2024
-5’ welded roof transition piece approved on ground -welded connection to captive air system Ok -1st layer at welded connection ok
Above Ceiling Inspection Partial 10/11/2024 10/11/2024 10/11/2024
Miscellaneous Correction
Corrective Action Required
09/27/2024
Areas approved to cover: -soffit at dining area -Hard lids at women’s restroom and kitchen corrido -Hard lids at men's restroom -Soffit hard lid front entry -Office area -Kitchen area from equipment line north except at west wall -PVC not allowed in open air plenum
Misc
Corrective Action Required
10/11/2024
-Complete truss reinforcement per plans at bar area *OK for borders
Gas Service Inspection - Commercial Passed 10/18/2024 10/18/2024 10/18/2024
Above Ceiling Inspection Failed 10/21/2024 10/21/2024 10/21/2024
Miscellaneous Correction
Corrective Action Required
10/11/2024
Areas approved to cover: -soffit at dining area -Hard lids at women’s restroom and kitchen corrido -Hard lids at men's restroom -Soffit hard lid front entry -Office area -Kitchen area from equipment line north except at west wall -PVC not allowed in open air plenum
Misc
Corrective Action Required
10/11/2024
-Secure all mc, support lv wires off of grid *OK for borders
Above Ceiling Inspection Partial 10/22/2024 10/22/2024 10/22/2024
Miscellaneous Correction
Informational
10/22/2024
Areas approved to cover: -soffit at dining area -Hard lids at women’s restroom and kitchen corrido -Hard lids at men's restroom -Soffit hard lid front entry -Office area -Kitchen area from equipment line north except at west wall -Dinning area excluding bar footprint
Misc
Corrective Action Required
10/21/2024
-PVC not allowed in open air plenum
Above Ceiling Inspection Failed 11/22/2024 11/22/2024 11/22/2024
Miscellaneous Correction
Informational
10/22/2024
Areas approved to cover: -soffit at dining area -Hard lids at women’s restroom and kitchen corrido -Hard lids at men's restroom -Soffit hard lid front entry -Office area -Kitchen area from equipment line north except at west wall -Dinning area excluding bar footprint
Misc
Corrective Action Required
10/22/2024
-PVC not allowed in open air plenum
Above Ceiling Inspection Partial 11/25/2024 11/25/2024 11/25/2024
Miscellaneous Correction
Informational
11/22/2024
Areas approved to cover: -soffit at dining area -Hard lids at women’s restroom and kitchen corrido -Hard lids at men's restroom -Soffit hard lid front entry -Office area -Kitchen area -Dinning area excluding bar footprint
Misc
Resolved
11/25/2024
Above Ceiling Inspection Passed 11/27/2024 11/27/2024 11/27/2024
Miscellaneous Correction
Resolved
11/27/2024
Areas approved to cover: -soffit at dining area -Hard lids at women’s restroom and kitchen corrido -Hard lids at men's restroom -Soffit hard lid front entry -Office area -Kitchen area -Dinning area excluding bar footprint
Hood/Duct Inspection Passed 12/23/2024
Misc
Resolved
12/23/2024
-5’ welded roof transition piece approved on ground -welded connection to captive air system Ok -1st layer at welded connection ok
Rough Electrical Inspection - Commercial Passed 11/25/2024 12/23/2024
Misc
Resolved
12/23/2024
-Install 200 amp breaker per plan panel P3
Rated Assembly Inspection Passed 12/23/2024
Misc
Resolved
12/23/2024
-First layer firewall repair at men's room ok
Occupancy Inspection - Codes Commercial Failed 12/23/2024 12/23/2024 12/23/2024
Misc
Corrective Action Required
12/23/2024
-Obtain approval from Jackson County Health Department -Breaker at P2 sec 2 to be 200 amp per plan -Provide air gap at sink drain in bar area -Urinal screen to be min 15" from centerline of urinal
Alarm Test Passed 12/24/2024
Alternate Protection Systems Inspection Passed 12/24/2024
Sprinkler - Hydrostatic Test Passed 12/24/2024
Sprinkler - Flow Test Passed 12/24/2024
Occupancy Inspection - Fire Passed 12/23/2024 12/20/2024 12/24/2024
Occupancy Inspection - Codes Commercial Failed 12/24/2024 12/24/2024 12/24/2024
Misc
Corrective Action Required
12/23/2024
-Obtain approval from Jackson County Health Department
Occupancy Inspection - Codes Commercial Full C of O 01/02/2025
Misc
Resolved
01/02/2025
-Obtain approval from Jackson County Health Department
Documents & Images
Date Uploaded File Type Document Name
05/02/2024 Application Form APPLICATION
05/02/2024 Plans 2024-05-02 30hop SOWP Issue for Permit
05/03/2024 Letter License Tax Bill
05/15/2024 Letter DS P/R Corrections Document
05/24/2024 Specifications 2024-05-24 30hop Lees Summit Exterior Exit Sign
05/24/2024 Plans 2024-05-24 ARCH 30hop Lees Summit Permit Revision 01
05/24/2024 Letter 2024-05-24 DS P_R Corrections Document - Response Comments
05/24/2024 Plans 2024-05-24 MEP 30hop Lees Summit Permit Revision 01
06/04/2024 Letter DS P/R Corrections Document
06/11/2024 Letter Health Dept Approval
07/05/2024 Application Form 30hop SOWP Commercial Permit Application_SOWP_Updated
07/05/2024 Letter 2024-07-05 DS P_R Corrections Document-Response Comments
07/05/2024 Certificate/License GMC LC License Certificate
07/05/2024 Drawing 2024-07-05 30hop SOWP Issue for Permit Sheet A001-R2
07/05/2024 Drawing 2024-07-05 30hop SOWP Issue for Permit Sheet A002-R2
07/05/2024 Drawing 2024-07-05 30hop SOWP Issue for Permit Sheet A205-R2
07/05/2024 Drawing 2024-07-05 30hop SOWP Issue for Permit Sheet E101-R2
07/05/2024 Drawing 2024-07-05 30hop SOWP Issue for Permit Sheet E102-R2
07/05/2024 Drawing 2024-07-05 30hop SOWP Issue for Permit Sheet E201-R2
07/05/2024 Drawing 2024-07-05 30hop SOWP Issue for Permit Sheet E301-R2
07/05/2024 Drawing 2024-07-05 30hop SOWP Issue for Permit Sheet E302-R2
07/05/2024 Drawing 235008 SOWP Lot 13_S602 FOR REFERENCE ONLY
07/15/2024 Plans 2024-07-15 30hop SOWP Issue for Permit Final Consolidated Set
07/15/2024 Approved Plans Approved building plans
07/17/2024 Receipt Receipt for transaction:2024-005884
07/17/2024 Letter DS Building Permit
07/19/2024 Letter INSPECTION SUMMARY
07/25/2024 Letter 2024-07-25 30hop SOWP Permit Revision ASI #4 Narrative
07/25/2024 Plans 2024-07-23 30hop SOWP Permit Revision ASI #4 Plans
07/26/2024 Letter INSPECTION SUMMARY
07/26/2024 Approved Plans Approved revisions
08/05/2024 Drawing 30Hop SOWP FP Plan
08/07/2024 Letter Fire (Alarm) Plan Review Notice
08/14/2024 AFP_FA_SOWP_30HOP_PE_STAMPED
08/14/2024 Letter INSPECTION SUMMARY
08/16/2024 Letter INSPECTION SUMMARY
08/21/2024 Letter INSPECTION SUMMARY
08/21/2024 Letter Fire (Alarm) Plan Review Notice
08/27/2024 Letter INSPECTION SUMMARY
08/28/2024 Letter INSPECTION SUMMARY
09/11/2024 Letter INSPECTION SUMMARY
09/11/2024 Letter INSPECTION SUMMARY
09/12/2024 Letter INSPECTION SUMMARY
09/12/2024 Letter INSPECTION SUMMARY
09/12/2024 Letter INSPECTION SUMMARY
09/17/2024 Plans 2024-09-17 30hop SOWP Permit Revision-Electrical Distribution
09/23/2024 Letter INSPECTION SUMMARY
09/23/2024 Letter INSPECTION SUMMARY
09/23/2024 Letter INSPECTION SUMMARY
09/27/2024 Letter INSPECTION SUMMARY
09/27/2024 Letter INSPECTION SUMMARY
10/02/2024 Letter INSPECTION SUMMARY
10/03/2024 Letter INSPECTION SUMMARY
10/07/2024 Letter INSPECTION SUMMARY
10/11/2024 Letter INSPECTION SUMMARY
10/18/2024 Letter INSPECTION SUMMARY
10/21/2024 Letter INSPECTION SUMMARY
10/22/2024 Letter INSPECTION SUMMARY
10/24/2024 D1044 - Streets of West Pryor 2401009 Sealed (1)
11/25/2024 Letter INSPECTION SUMMARY
12/23/2024 Letter INSPECTION SUMMARY
12/23/2024 Letter INSPECTION SUMMARY
12/23/2024 Letter INSPECTION SUMMARY
12/23/2024 Letter INSPECTION SUMMARY
01/02/2025 Health Inspection
01/02/2025 Letter Codes Final Certificate of Occupancy
01/02/2025 Letter Field Certificate of Occupancy
09/03/2024 Approved Plans Approved patio heating
08/30/2024 Plans 2024-08-30 30hop SOWP Permit Revision-Patio Heater Substitution
08/22/2024 Letter INSPECTION SUMMARY
08/20/2024 Letter INSPECTION SUMMARY
07/31/2024 Letter INSPECTION SUMMARY
07/26/2024 AFP_EQUIPMENT_SOWP_30HOP
07/26/2024 AFP_FA_SOWP_30HOP_NICET_III
07/25/2024 Letter INSPECTION SUMMARY
09/17/2024 Approved Plans Approved Revision-Electrical Distribution
09/17/2024 Email Re_ 30HOP - PRCOM20242210
12/24/2024 Letter INSPECTION SUMMARY
11/27/2024 Letter INSPECTION SUMMARY
11/22/2024 Letter INSPECTION SUMMARY
10/29/2024 Knauf Fiberglass Pipe Insulation Submittal sheet
10/29/2024 Proto PVC Submittal Sheet
09/26/2024 Letter INSPECTION SUMMARY
09/26/2024 Letter INSPECTION SUMMARY
09/16/2024 Letter INSPECTION SUMMARY
09/16/2024 Letter INSPECTION SUMMARY
09/09/2024 Letter INSPECTION SUMMARY
09/09/2024 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home