| Inspection |
Outcome |
Requested |
Scheduled |
Date Inspected |
|
Water Service Inspection
|
Pending
|
|
|
|
|
Electrical Service Inspection
|
Pending
|
|
|
|
|
Above Ceiling Inspection
|
Pending
|
|
|
|
|
Storm Sewer Construction Inspection
|
Pending
|
|
|
|
|
|
Misc
|
|
|
Misc
|
|
Sanitary Sewer Construction Inspection
|
Pending
|
|
|
|
|
|
Misc
|
|
Water Line - Hydrostatic Test
|
Pending
|
|
|
|
|
Piers/Caissons Inspection - Commercial
|
Pending
|
|
|
|
|
Gas Service Inspection - Commercial
|
Pending
|
|
|
|
|
In-wall Inspection
|
Pending
|
|
|
|
|
Grading/Excavation/Fill Inspection
|
Pending
|
|
|
|
|
Water Line - Construction Inspection
|
Pending
|
|
|
|
|
Pavement-Surface
|
Pending
|
|
|
|
|
Install Street and Stop Signs
|
Pending
|
|
|
|
|
Pavement-Curb Construction
|
Pending
|
|
|
|
|
Pavement-Stabilized Subgrade
|
Pending
|
|
|
|
|
Storm Sewer Construction Inspection
|
Pending
|
|
|
|
|
Footing Inspection - Commercial
|
Pending
|
|
|
|
|
|
Misc
|
|
Pavement-Proof Roll
|
Pending
|
|
|
|
|
Underground Electrical Inspection - Commercial
|
Pending
|
|
|
|
|
|
Misc
|
|
Sprinkler - Hydrostatic Test
|
Pending
|
|
|
|
|
Sprinkler - Flow Test
|
Pending
|
|
|
|
|
Site Visit
|
Pending
|
|
|
|
|
|
Misc
|
|
Erosion Control Inspection
|
Pending
|
|
|
|
|
|
Misc
|
|
Underground Plumbing Inspection - Commercial
|
Pending
|
|
|
|
|
Sprinkler - Hydrostatic Test
|
Pending
|
|
|
|
|
All Rough Inspection - Commercial
|
Pending
|
|
|
|
|
|
Misc
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
STAIR TOWER 1
Corrective Action Required
|
|
|
STAIR TOWER 2
Corrective Action Required
|
|
Rated Assembly Inspection
|
Pending
|
|
|
|
|
|
Misc
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
Sprinkler - Hydrostatic Test
|
Pending
|
|
|
|
|
Rough Framing Inspection - Commercial
|
Pending
|
|
|
|
|
|
FOURTH FLOOR
|
|
Erosion Control Inspection
|
Partial
|
10/30/2024
|
10/30/2024
|
10/30/2024
|
|
|
Misc
|
|
Site Visit
|
Partial
|
10/30/2024
|
10/30/2024
|
10/30/2024
|
|
|
Misc
|
|
Site Visit
|
Partial
|
12/2/2024
|
12/2/2024
|
12/02/2024
|
|
|
Misc
|
|
Erosion Control Inspection
|
Partial
|
12/5/2024
|
12/5/2024
|
12/05/2024
|
|
|
Misc
|
|
Storm Sewer Construction Inspection
|
Partial
|
12/18/2024
|
12/18/2024
|
12/18/2024
|
|
|
Misc
|
|
Erosion Control Inspection
|
Partial
|
12/23/2024
|
12/23/2024
|
12/23/2024
|
|
|
Misc
|
|
Storm Sewer Construction Inspection
|
Partial
|
12/20/2024
|
12/20/2024
|
12/23/2024
|
|
|
Misc
|
|
Erosion Control Inspection
|
Partial
|
12/23/2024
|
12/23/2024
|
12/23/2024
|
|
|
Misc
|
|
Storm Sewer Construction Inspection
|
Partial
|
12/24/2024
|
12/24/2024
|
12/24/2024
|
|
|
Misc
|
|
Storm Sewer Construction Inspection
|
Partial
|
1/2/2025
|
1/2/2025
|
01/02/2025
|
|
|
Misc
|
|
|
Misc
|
|
Storm Sewer Construction Inspection
|
Partial
|
1/13/2025
|
1/13/2025
|
01/14/2025
|
|
|
Misc
|
|
|
Misc
|
|
Storm Sewer Construction Inspection
|
Partial
|
1/14/2025
|
1/14/2025
|
01/14/2025
|
|
|
Misc
|
|
|
Misc
|
|
Erosion Control Inspection
|
Partial
|
1/14/2025
|
1/14/2025
|
01/14/2025
|
|
|
Misc
|
|
Storm Sewer Construction Inspection
|
Partial
|
1/15/2025
|
1/15/2025
|
01/15/2025
|
|
|
Misc
|
|
|
Misc
|
|
Storm Sewer Construction Inspection
|
Partial
|
1/17/2025
|
1/17/2025
|
01/21/2025
|
|
|
Misc
|
|
|
Misc
|
|
Sanitary Sewer Construction Inspection
|
Partial
|
1/24/2025
|
1/24/2025
|
01/28/2025
|
|
|
Misc
|
|
Water Line - Construction Inspection
|
Partial
|
1/28/2025
|
1/28/2025
|
01/28/2025
|
|
|
Misc
|
|
Water Line - Construction Inspection
|
Partial
|
1/29/2025
|
1/29/2025
|
01/29/2025
|
|
|
Misc
|
|
Fire Line Construction Inspection
|
Partial
|
2/3/2025
|
2/3/2025
|
02/06/2025
|
|
|
Misc
|
|
Fire Line Construction Inspection
|
Passed
|
2/4/2025
|
2/4/2025
|
02/06/2025
|
|
|
Misc
|
|
Fire Line Construction Inspection
|
Passed
|
|
|
02/06/2025
|
|
|
Misc
|
|
Fire Line - Hydrostatic Test
|
Passed
|
2/5/2025
|
2/5/2025
|
02/06/2025
|
|
|
Misc
|
|
Erosion Control Inspection
|
Partial
|
2/6/2025
|
2/6/2025
|
02/06/2025
|
|
|
Misc
|
|
Water Line - Construction Inspection
|
Passed
|
2/6/2025
|
2/6/2025
|
02/06/2025
|
|
|
Misc
|
|
Fire Line - Hydrostatic Test
|
Passed
|
2/25/2025
|
2/25/2025
|
02/26/2025
|
|
|
Misc
|
|
Erosion Control Inspection
|
Partial
|
2/25/2025
|
2/25/2025
|
02/26/2025
|
|
|
Misc
|
|
Underground Electrical Inspection - Commercial
|
Partial
|
|
2/28/2025
|
02/28/2025
|
|
|
Misc
|
|
Footing Inspection - Commercial
|
Partial
|
2/28/2025
|
2/28/2025
|
02/28/2025
|
|
|
Misc
|
|
Footing Inspection - Commercial
|
Partial
|
3/11/2025
|
3/11/2025
|
03/11/2025
|
|
|
Misc
|
|
Footing Inspection - Commercial
|
Partial
|
|
3/13/2025
|
03/13/2025
|
|
|
Misc
|
|
Footing Inspection - Commercial
|
Failed
|
3/25/2025
|
3/25/2025
|
03/25/2025
|
|
|
Misc
|
|
|
Misc
Corrective Action Required
|
|
Footing Inspection - Commercial
|
Partial
|
3/25/2025
|
3/25/2025
|
03/25/2025
|
|
|
Misc
|
|
|
Misc
|
|
Erosion Control Inspection
|
Partial
|
3/26/2025
|
3/26/2025
|
03/26/2025
|
|
|
Misc
|
|
Footing Inspection - Commercial
|
Partial
|
3/28/2025
|
3/28/2025
|
03/28/2025
|
|
|
Misc
|
|
Footing Inspection - Commercial
|
Partial
|
|
3/31/2025
|
03/31/2025
|
|
|
Misc
|
|
Footing Inspection - Commercial
|
Partial
|
4/1/2025
|
4/1/2025
|
04/01/2025
|
|
|
Misc
|
|
|
Misc
Corrective Action Required
|
|
Footing Inspection - Commercial
|
Partial
|
4/3/2025
|
4/3/2025
|
04/03/2025
|
|
|
Misc
|
|
|
Misc
|
|
Footing Inspection - Commercial
|
Partial
|
4/7/2025
|
4/7/2025
|
04/07/2025
|
|
|
Misc
|
|
Underslab Plumbing Inspection - Commercial
|
Partial
|
|
4/8/2025
|
04/08/2025
|
|
|
Misc
Corrective Action Required
|
|
Underslab Plumbing Inspection - Commercial
|
Partial
|
4/14/2025
|
4/14/2025
|
04/14/2025
|
|
|
Misc
Corrective Action Required
|
|
Underslab Plumbing Inspection - Commercial
|
Partial
|
4/15/2025
|
4/15/2025
|
04/15/2025
|
|
|
Misc
Corrective Action Required
|
|
Sewer Service Inspection
|
Passed
|
3/10/2025
|
3/10/2025
|
04/18/2025
|
|
|
Misc
|
|
Site Visit
|
Partial
|
4/16/2025
|
4/16/2025
|
04/18/2025
|
|
|
Misc
|
|
Erosion Control Inspection
|
Partial
|
4/16/2025
|
4/16/2025
|
04/18/2025
|
|
|
Misc
|
|
Footing Inspection - Commercial
|
Partial
|
4/21/2025
|
4/21/2025
|
04/21/2025
|
|
|
Misc
|
|
Underslab Plumbing Inspection - Commercial
|
Passed
|
4/22/2025
|
4/22/2025
|
04/22/2025
|
|
|
Misc
|
|
Underslab Electrical Inspection - Commercial
|
Passed
|
4/22/2025
|
4/22/2025
|
04/22/2025
|
|
Erosion Control Inspection
|
Partial
|
5/16/2025
|
5/16/2025
|
05/16/2025
|
|
|
Misc
|
|
Erosion Control Inspection
|
Partial
|
6/3/2025
|
6/3/2025
|
06/03/2025
|
|
|
Misc
|
|
Footing Inspection - Commercial
|
Partial
|
6/23/2025
|
6/23/2025
|
06/23/2025
|
|
|
Misc
|
|
Footing Inspection - Commercial
|
Partial
|
7/10/2025
|
7/10/2025
|
07/10/2025
|
|
|
Misc
|
|
Curb - Proof Roll
|
Passed
|
|
|
07/16/2025
|
|
|
Miscellaneous Correction
|
|
Rough Framing Inspection - Commercial
|
Passed
|
8/15/2025 (A.M.)
|
8/15/2025
|
08/15/2025
|
|
Pavement-Aggregate Base
|
Passed
|
|
|
09/11/2025
|
|
|
Misc
|
|
Pavement-Proof Roll
|
Partial
|
|
|
09/11/2025
|
|
|
Misc
|
|
All Rough Inspection - Commercial
|
Failed
|
10/1/2025
|
10/1/2025
|
10/01/2025
|
|
|
Misc
Corrective Action Required
|
|
All Rough Inspection - Commercial
|
Failed
|
|
10/2/2025
|
10/02/2025
|
|
|
Misc
Corrective Action Required
|
|
All Rough Inspection - Commercial
|
Failed
|
|
10/7/2025
|
10/07/2025
|
|
|
Misc
Corrective Action Required
|
|
All Rough Inspection - Commercial
|
Failed
|
10/8/2025
|
10/8/2025
|
10/08/2025
|
|
|
Misc
Corrective Action Required
|
|
All Rough Inspection - Commercial
|
Failed
|
10/9/2025
|
10/9/2025
|
10/09/2025
|
|
|
Misc
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
STAIR TOWER 1
Corrective Action Required
|
|
|
STAIR TOWER 2
Corrective Action Required
|
|
All Rough Inspection - Commercial
|
Failed
|
10/10/2025
|
10/10/2025
|
10/10/2025
|
|
|
Misc
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
STAIR TOWER 1
Corrective Action Required
|
|
|
STAIR TOWER 2
Corrective Action Required
|
|
Erosion Control Inspection
|
Partial
|
|
10/12/2025
|
10/13/2025
|
|
|
Misc
|
|
All Rough Inspection - Commercial
|
Failed
|
10/13/2025
|
10/13/2025
|
10/13/2025
|
|
|
Misc
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
STAIR TOWER 1
Corrective Action Required
|
|
|
STAIR TOWER 2
Corrective Action Required
|
|
All Rough Inspection - Commercial
|
Failed
|
|
10/14/2025
|
10/14/2025
|
|
|
Misc
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
STAIR TOWER 1
Corrective Action Required
|
|
|
STAIR TOWER 2
Corrective Action Required
|
|
All Rough Inspection - Commercial
|
Partial
|
10/16/2025
|
10/16/2025
|
10/16/2025
|
|
|
Misc
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
STAIR TOWER 1
Corrective Action Required
|
|
|
STAIR TOWER 2
Corrective Action Required
|
|
All Rough Inspection - Commercial
|
Failed
|
10/17/2025
|
10/17/2025
|
10/17/2025
|
|
|
Misc
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
STAIR TOWER 1
Corrective Action Required
|
|
|
STAIR TOWER 2
Corrective Action Required
|
|
All Rough Inspection - Commercial
|
Failed
|
10/20/2025
|
10/20/2025
|
10/20/2025
|
|
|
Misc
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
STAIR TOWER 1
Corrective Action Required
|
|
|
STAIR TOWER 2
Corrective Action Required
|
|
Rated Assembly Inspection
|
Partial
|
10/20/2025
|
10/20/2025
|
10/20/2025
|
|
|
Misc
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
Rated Assembly Inspection
|
Failed
|
10/20/2025
|
10/21/2025
|
10/21/2025
|
|
|
Misc
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
All Rough Inspection - Commercial
|
Failed
|
10/22/2025
|
10/22/2025
|
10/22/2025
|
|
|
Misc
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
STAIR TOWER 1
Corrective Action Required
|
|
|
STAIR TOWER 2
Corrective Action Required
|
|
Rated Assembly Inspection
|
Failed
|
10/22/2025
|
10/22/2025
|
10/22/2025
|
|
|
Misc
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
Rated Assembly Inspection
|
Failed
|
|
10/22/2025
|
10/22/2025
|
|
|
Misc
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
Rated Assembly Inspection
|
Failed
|
|
10/22/2025
|
10/22/2025
|
|
|
Misc
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
Rated Assembly Inspection
|
Partial
|
10/24/2025
|
10/24/2025
|
10/24/2025
|
|
|
Misc
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
Rated Assembly Inspection
|
Partial
|
10/27/2025
|
10/27/2025
|
10/27/2025
|
|
|
Misc
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
All Rough Inspection - Commercial
|
Failed
|
10/27/2025
|
10/28/2025
|
10/28/2025
|
|
|
Misc
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
STAIR TOWER 1
Corrective Action Required
|
|
|
STAIR TOWER 2
Corrective Action Required
|
|
Erosion Control Inspection
|
Partial
|
|
10/29/2025
|
10/29/2025
|
|
|
Misc
|
|
Rated Assembly Inspection
|
Partial
|
10/30/2025
|
10/30/2025
|
10/30/2025
|
|
|
Misc
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
Rated Assembly Inspection
|
Partial
|
10/31/2025
|
10/31/2025
|
10/31/2025
|
|
|
Misc
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
All Rough Inspection - Commercial
|
Failed
|
10/31/2025
|
10/31/2025
|
10/31/2025
|
|
|
Misc
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
STAIR TOWER 1
Corrective Action Required
|
|
|
STAIR TOWER 2
Corrective Action Required
|
|
Site Visit
|
Partial
|
|
10/30/2025
|
10/31/2025
|
|
|
Misc
|
|
Rated Assembly Inspection
|
Partial
|
11/4/2025
|
11/4/2025
|
11/04/2025
|
|
|
Misc
Corrective Action Required
|
|
|
FIRST FLOOR
Corrective Action Required
|
|
|
SECOND FLOOR
Corrective Action Required
|
|
|
THIRD FLOOR
Corrective Action Required
|
|
|
FOURTH FLOOR
Corrective Action Required
|
|
Rough Framing Inspection - Commercial
|
Partial
|
11/10/2025
|
11/10/2025
|
11/10/2025
|
|
|
FOURTH FLOOR
|
|
Erosion Control Inspection
|
Partial
|
|
11/11/2025
|
11/12/2025
|
|
|
Misc
|