Permit Application Status

PRCOM20236408


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20236408
Building Permit - Commercial
Certificate of Occupancy
PEREGRINE VALLEY INVESTMENTS LLC
CHANGE OF TENANT
CHANGE OF TENANT FOR MEDICAL OFFICE
12/07/2023
12/20/2023
02/23/2024
Locations
Contacts
PEREGRINE VALLEY INVESTMENTS LLC, Address:3730 NE TROON DR  
NEXUS 5 GROUP, Address:8500 SHAWNEE MISSION PKWY STE 130, Phone:(913) 671-3361  
Katie Reed, Address:8500 Shawnee Mission Pkwy.  
NEXUS 5 GROUP, Address:8500 SHAWNEE MISSION PKWY STE 130, Phone:(913) 671-3361  
M & S ELECTRIC, Address:PO BOX 1147, Phone:(816) 427-5913  
PLUMBING PLUS INC, Address:13117 S 71 HWY, Phone:(816) 761-5757  
Multis Design, Address:1100 mAIN sT, fl 4, Phone:(913) 689-9449  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 02/13/2024 02/12/2024
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
02/12/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received 1/30/2024.
Installation acceptance testing
Corrective Action Required
02/12/2024

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule a test.
Sprinkler Plan Review Released for Construction 01/30/2024 01/30/2024
Jim Eden
Installation acceptance testing
Corrective Action Required
01/30/2024

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. A visual inspection will be completed at the occupancy inspection.
Fire Plan Review Approved with Conditions 12/19/2023 12/18/2023
Jim Eden
Miscellaneous Correction
Corrective Action Required
12/18/2023

The entire space is calculated as a B occupancy at 150sq.ft./person. The total occupant load for the space is 11.
Construction documents - Fire protection systems
Corrective Action Required
12/18/2023

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide plans for maintaining sprinkler coverage in the newly created spaces.
Building Plan Review Approved with Conditions 12/19/2023 12/11/2023
Joe Frogge
License Tax - Payment
Corrective Action Required
12/11/2023

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is informational. After credit for previous office occupant the fee will be $2,079.00.
Licensed Contractors Approved 12/07/2023 12/07/2023
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Change of Tenant $316.22 $316.22 Paid 12/20/2023
Commercial Excise Tax Fee $3,960.00 $3,960.00 Paid 12/20/2023
$1,881.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 1/18/2024 1/18/2024 01/18/2024
Misc
Corrective Action Required
01/18/2024
-All wiring methods in patient exam rooms, new or existing, must comply with NEC article 517 **OK to cover non patient areas
Above Ceiling Inspection Failed 1/18/2024 1/18/2024 01/18/2024
Misc
Corrective Action Required
01/18/2024
-All wiring methods in patient exam rooms, new or existing, must comply with NEC article 517 -Cover open J boxes -Secure all mc and lv off of grid -Install knockout cover at opening in J box above office area
Above Ceiling Inspection Partial 1/22/2024 1/22/2024 01/22/2024
Misc
Corrective Action Required
01/18/2024
-All wiring methods in patient exam rooms, new or existing, must comply with NEC article 517 308 exam room okay
In-wall Inspection Partial 1/22/2024 1/22/2024 01/22/2024
Misc
Corrective Action Required
01/18/2024
-All wiring methods in patient exam rooms, new or existing, must comply with NEC article 517 **OK to cover non patient areas and exam room 308
In-wall Inspection Passed 1/30/2024 1/30/2024 01/30/2024
Misc
Resolved
01/30/2024
-All wiring methods in patient exam rooms, new or existing, must comply with NEC article 517 **OK to cover non patient areas and exam room 308
Misc
Informational
01/30/2024
Approved plans have been updated to omit second exam room
Above Ceiling Inspection Passed 2/23/2024 02/23/2024
Misc
Resolved
02/23/2024
-All wiring methods in patient exam rooms, new or existing, must comply with NEC article 517 308 exam room okay
Occupancy Inspection - Codes Commercial Full C of O 2/23/2024 2/23/2024 02/23/2024
Documents & Images
Date Uploaded File Type Document Name
12/07/2023 Application Form APPLICATION
12/07/2023 Plans Gameday Building Permit 231025
12/19/2023 Plans gameday resub
12/20/2023 Receipt Receipt for transaction:2023-009222
12/20/2023 Plans Gameday Permit Resubmittal 231220
12/20/2023 Approved Plans approved plans
12/20/2023 Letter DS Building Permit
01/16/2024 Sealed Fire Sprinkler - Gameday Men's Health
01/18/2024 Letter INSPECTION SUMMARY
01/18/2024 Letter INSPECTION SUMMARY
01/22/2024 Letter INSPECTION SUMMARY
01/22/2024 Letter INSPECTION SUMMARY
01/26/2024 Plans Gameday ASI-1 240125
01/26/2024 Approved Plans approved - Gameday ASI-1 240125
01/27/2024 Letter Gameday Accessibility Upgrades Letter 240126
01/30/2024 Gameday Mens Health - FA Plans
01/30/2024 Gameday Mens Health - FA Submittal
01/30/2024 Sealed Fire Sprinkler - Gameday Men's Health APPROVED
01/30/2024 Letter Fire (Sprinkler) Plan Review
01/30/2024 Letter INSPECTION SUMMARY
02/12/2024 Letter Fire (Alarm) Plan Review Notice
02/12/2024 Approved Plans Gameday Mens Health - FA Plans APPROVED
02/23/2024 Letter Field Certificate of Occupancy
02/23/2024 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home