Review Type |
Outcome |
Est. Completion Date |
Completed |
Fire Plan Review
|
Approved
|
07/14/2022
|
07/13/2022
|
|
Jim Eden
|
|
Installation acceptance testing
2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Call (816) 969-1300 to schedule a test.
|
|
Portable fire extinguishers - general
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Action required- Provide fire extinguishers of appropriate size in correct locations.
|
|
Miscellaneous Correction
How will fire suppression be provided to the paint booth?
Action required-
Provide plans and specification sheets for review and approval.
|
|
|
Building Plan Review
|
Approved
|
07/14/2022
|
07/07/2022
|
|
Joe Frogge
|
|
|
Licensed Contractors
|
Approved
|
07/07/2022
|
07/07/2022
|
|
Joe Frogge
|
|
|
Fire Plan Review
|
Rejected
|
07/05/2022
|
07/06/2022
|
|
Jim Eden
|
|
Installation acceptance testing
2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Call (816) 969-1300 to schedule a test.
|
|
Portable fire extinguishers - general
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Action required- Provide fire extinguishers of appropriate size in correct locations.
|
|
Miscellaneous Correction
Corrective Action Required
How will fire suppression be provided to the paint booth?
Action required-
Provide plans and specification sheets for review and approval.
07/06/2022- Still awaiting fire suppression plans.
|
|
Misc
2404.3.3.5 Clear space. Spray booths shall be installed so that all parts of the booth are able to be accessed forbcleaning. A clear space of not less than 3 feet (914 mm) shall be maintained on all sides of the spray booth. This clear space shall be kept free of any storage or combustible construction.
Exceptions:
1. This requirement shall not prohibit locating a spray booth closer than 3 feet (914 mm) to or directly against an interior partition, wall or floor/ceiling assembly that has a fire-resistance rating of not less than 1 hour, provided that the spray booth can be adequately maintained and cleaned.
2. This requirement shall not prohibit locating a
spray booth closer than 3 feet (914 mm) to an
exterior wall or a roof assembly, provided that
the wall or roof is constructed of noncombustible
material and the spray booth can be adequately
maintained and cleaned.
Action required- How will this be met?
|
|
|
Licensed Contractors
|
Approved
|
07/05/2022
|
06/27/2022
|
|
Joe Frogge
|
|
|
Building Plan Review
|
Approved
|
07/05/2022
|
06/27/2022
|
|
Joe Frogge
|
|
|
Fire Plan Review
|
Rejected
|
06/21/2022
|
06/21/2022
|
|
Jim Eden
|
|
Installation acceptance testing
Corrective Action Required
2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
|
|
Portable fire extinguishers - general
Corrective Action Required
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Action required- Provide fire extinguishers of appropriate size in correct locations.
|
|
Miscellaneous Correction
Corrective Action Required
How will fire suppression be provided to the paint booth?
Action required-
Provide plans and specification sheets for review and approval.
|
|
Misc
Corrective Action Required
2404.3.3.5 Clear space. Spray booths shall be installed
so that all parts of the booth are able to be accessed forbcleaning. A clear space of not less than 3 feet (914 mm) shall be maintained on all sides of the spray booth. This clear space shall be kept free of any storage or combustible construction.
Exceptions:
1. This requirement shall not prohibit locating a spray booth closer than 3 feet (914 mm) to or directly against an interior partition, wall or floor/ceiling assembly that has a fire-resistance rating of not less than 1 hour, provided that the spray booth can be adequately maintained and cleaned.
2. This requirement shall not prohibit locating a
spray booth closer than 3 feet (914 mm) to an
exterior wall or a roof assembly, provided that
the wall or roof is constructed of noncombustible
material and the spray booth can be adequately
maintained and cleaned.
Action required- How will this be met?
|
|
|
Building Plan Review
|
Approved
|
06/21/2022
|
06/17/2022
|
|
Joe Frogge
|
|
|
Licensed Contractors
|
Approved
|
06/21/2022
|
06/10/2022
|
|
Joe Frogge
|
|
|