Permit Application Status

PRCOM20161178


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20161178
Building Permit - Commercial
Certificate of Occupancy
JOHN KNOX VILLAGE
NEW COMMERCIAL
COMMONS BUILDING
05/23/2016
11/22/2016
11/30/2016
02/12/2018
Locations
Contacts
PARIC CORPORATION , Address:77 WESTORT PLAZA STE 250, Phone:(636) 561-9795  
GREEN FIELD ENERGY GROUP INC, Address:5 SW 4TH ST, Phone:(816) 524-5616  
TORGESON ELECTRIC CO INC, Address:3545 SW 6TH AVE, Phone:(785) 233-2213 Ext:101  
LMG CONSTRUCTION, Address:3011 ROANOKE RD, Phone:(816) 474-0333  
JOHN KNOX VILLAGE, Address:400 NW MURRAY RD  
SFCS ARCHITECTS, Address:1927 SOUTH TRYON ST, SUITE 207, Phone:(704) 372-7327  
KRUGER TECHNOLOGIES INC, Address:8271 MELROSE DR, Phone:(913) 498-1114  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 03/27/2017
Joe Dir
03/27/2017

03/27/2017

03/27/2017

Installation acceptance testing
Corrective Action Required
03/27/2017

2016 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: Acceptance testing of the system will be required prior to final occupancy inspection. To schedule testing contact the fire department at 816-969-1300
Alarm Plan Review Rejected 03/07/2017
Joe Dir
Misc
Corrective Action Required
03/07/2017

Origianl fire alarm plans (not alterations) shall come bearing a PE stamp.
Misc
Corrective Action Required
03/07/2017

Check all stairways throughout all buildings all floors to assure there are no strobe notification devices located within the stairways.
Misc
Corrective Action Required
03/07/2017

Check all corridor fire doors throughout all buildings and all floors to assure there is a smoke detector on each side of the doors.
Sprinkler Plan Review Released for Construction 01/17/2017
Joe Dir
Installation acceptance testing
Corrective Action Required
01/17/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTING WILL BE REQUIRED FOR THE SYSTEM PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300.
Misc
Corrective Action Required
01/17/2017

make sure installation crew see the revised drawings about the location of the Inspectors test.
Building Plan Review Approved with Conditions 06/27/2016 11/29/2016
Joe Frogge
License Tax Application
Corrective Action Required
06/20/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Final Development Plan
Corrective Action Required
06/20/2016

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Misc
Resolved
11/29/2016

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections. 6/23/16 - Not included in submittal
Misc
Resolved
06/23/2016

Footings, pads, etc. to be designed per site conditions. Action required: Provide soils report by licensed engineer to verify existing soils conditions. Plans cite 2500 psf while 2000 psf is common in this area.
Misc
Resolved
06/23/2016

Additional information required. Action required: Provide complete details and information for -- U.L. 438 (wall P2) GA #351 (wall HH2) U.L. U905 (walls W, W1, & W2) U.L. unknown (Wall JJ)
Misc
Resolved
06/23/2016

2012 IBC 716.5 Fire door and shutter assemblies. Approved fire door and fire shutter assemblies shall be constructed of any material or assembly of component materials that conforms to the test requirements of Section 716.5.1, 716.5.2 or 716.5.3 and the fire protection rating indicated in Table 716.5. Fire door frames with transom lights, sidelights or both shall be permitted in accordance with Section 716.5.6. Fire door assemblies and shutters shall be installed in accordance with the provisions of this section and the NFPA 80. Action required: Review and update door schedule as concerns minimum fire ratings. Multiple found to be incorrect or missing.
Engineered truss package
Resolved
06/23/2016

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide floor and roof truss packages or request to defer to construction. 6/23/16 - deferred to construction
Screening - Ground mounted equipment
Resolved
06/23/2016

Unified Development Ordinance Article 7, Section 7.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section.
Health Dept Review
Resolved
11/29/2016

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes. 11/29/16 - received 6/23/16 - acknowledged in letter (not yet received)
Health Dept Inspection
Corrective Action Required
06/20/2016

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 6/23/16 - acknowledged in letter
Miscellaneous Correction
Resolved
06/23/2016

2012 IBC 1008.1.3 Door opening force. The force for pushing or pulling open interior swinging egress doors, other than fire doors, shall not exceed 5 pounds (22 N). For other swinging doors, as well as sliding and folding doors, the door latch shall release when subjected to a 15-pound (67 N) force. The door shall be set in motion when subjected to a 30-pound (133 N) force. The door shall swing to a full-open position when subjected to a 15-pound (67 N) force. Action required: Modify specifications to show compliance.
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Resolved
06/23/2016

ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Modify plans to demonstrate compliance at locker doors C143B & C145B and electrical room door C162
Bldg - Occupant load posting 1004.3
Corrective Action Required
06/20/2016

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Comment is for informational purposes. May be verified at inspections. 6/23/16 - acknowledged in letter (field verify)
Misc
Resolved
06/23/2016

2012 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30" (see code section for additional construction requirements) Action required: Provide permanent access to roof.
Misc
Resolved
06/23/2016

2012 IMC 506.5.3 Exhaust fan mounting. An upblast fan shall be hinged and supplied with a flexible weatherproof electrical cable to permit inspection and cleaning. The ductwork shall extend a minimum of 18 inches above the roof surface. Action required: Modify fan detail to show hinge and duct extension.
Misc
Resolved
06/23/2016

506.3.8 Grease duct cleanouts and openings. Grease duct cleanouts and openings shall comply with all of the following: 1. Grease ducts shall not have openings except where required for the operation and maintenance of the system. 2. Sections of grease ducts that are inaccessible from the hood or discharge openings shall be provided with cleanout openings. 3. Cleanouts and openings shall be equipped with tight-fitting doors constructed of steel having a thickness not less than that required for the duct. 4. Cleanout doors shall be installed liquid tight. 5. Door assemblies including any frames and gaskets shall be approved for the application and shall not have fasteners that penetrate the duct. 6. Gasket and sealing materials shall be rated for not less than 1500°F (816°C). 7. Listed door assemblies shall be installed in accordance with the manufacturer’s instructions. Action required: Specify and show locations of grease duct cleanouts.
Misc
Resolved
06/23/2016

Additional information needed for review. Action required: Specify pool heaters including any combustion air requirements.
Miscellaneous Correction
Resolved
06/23/2016

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles in kitchen and bars will by GFCI protected.
Special Inspections Review Approved 11/29/2016
Joe Frogge
Health Department Review Approved 12/14/2016 11/29/2016
Joe Frogge
Licensed Contractors Approved 06/20/2016 11/21/2016
Mike Weisenborn
LC - MEP Subs
Corrective Action Required
06/20/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Final Development Plan Review Approved 12/14/2016 11/21/2016
Mike Weisenborn
Fire Plan Review Approved with Conditions 06/27/2016 06/21/2016
Joe Dir
06/21/2016

06/21/2016

06/21/2016

Misc
Corrective Action Required
06/20/2016

DOORS / HARDWARE NO KEYED LOCKS ON THE EGRESS SIDE OF A MARKED EXIT. ALL ELECTRONICALLY CONTROLLED DOORS WILL DROP OFF UPON LOSS OF POWER AND OR THE ACTIVATION OF THE FIRE ALARM SYSTEM.
Posting of occupant load
Corrective Action Required
06/20/2016

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. POST THE OCCUPANT LOAD IN ALL ROOMS AND ASSEMBLY AREAS WITH A OCCUPANT LOAD OVER 50. (VERIFIED AT INSPECTION)
Material safety and data sheets
Corrective Action Required
06/20/2016

2012 IFC 407.2- Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be readily available on the premises. POST NFPA 704 PLACARDS AT THE STORAGE AREAS, OF POOL CHEMICALS AND OR OTHER POTENTIAL HAZARDOUS MATERIALS TO BE STORED IN THE BUILDINGS.
Construction documents for fire alarm systems
Corrective Action Required
06/20/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS FOR THE FIRE ALARM SYSTEM TO BE INSTALLED.
Address numbers required
Corrective Action Required
06/20/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST HE NUMERIC ADDRESS OF ALL THE BUILDINGS READABLE FROM THE ADDRESSES ROADWAY. MAY REQUIRED POSTING THE ADDRESS ON MORE THAN ONE SIDE OF EACH OF THE BUILDINGS. (VERIFED AT INSPECTION)
Knox box required
Corrective Action Required
06/20/2016

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. PROVIDE A KNOX BOX FOR EACH BUILDING AND EACH ELEVATOR BANK. BOXES CAN BE OBTAINED ON LINE knox.box.com 506.1.2 Key boxes for nonstandardized fire service elevator keys. Key boxes provided for nonstandardized fire service elevator keys shall comply with Section 506.1 and all of the following: 1. The key box shall be compatible with an existing rapid entry key box system in use in the jurisdiction and approved by the fire code official. 2. The front cover shall be permanently labeled with the words “Fire Department Use Only—Elevator Keys.” 3. The key box shall be mounted at each elevator bank at the lobby nearest to the lowest level of fire department access. 4. The key box shall be mounted 5 feet 6 inches (1676 mm) above the finished floor to the right side of the elevator bank. 5. Contents of the key box are limited to fire service elevator keys. Additional elevator access tools, keys and information pertinent to emergency planning or elevator access shall be permitted when authorized by the fire code official. 6. In buildings with two or more elevator banks, a single key box shall be permitted to be used when such elevator banks are separated by not more than 30 feet (9144 mm). Additional key boxes shall be provided for each individual elevator or elevator bank separated by more than 30 feet (9144 mm).
Construction documents - Fire protection systems
Corrective Action Required
06/20/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE SELECTED CONTRACTORS PROVIDE SHOP DRAWINGS FOR THE FIRE SPRINKLER SYSTEM, CLASS 1 STANDPIPE SYSTEM AND THE KITCHEN HOOD SUPRESSION SYSTEMS TO BE INSTALLED.
Installation acceptance testing
Corrective Action Required
06/20/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTING WILL BE REQUIRED FOR THE SPRINKLER, ALARM AND KITCHEN HOOD SUPRESSION SYSTEMS PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
06/20/2016

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. PROVIDE A K-CLASS FIRE EXTINGUISHER FOR THE TYPE 1 KITCHEN HOOD.
Portable fire extinguishers - general
Corrective Action Required
06/20/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. THE MINIMUM SIZED FIRE EXTINGUISHERS WILL BE (5POUND) 2A-10BC
Portable fire extinguishers - conspicuous locations
Corrective Action Required
06/20/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. THE MAXIMUM TRAVEL DISTANCE TO A FIRE EXTINGUISHER WILL BE 75'
Misc
Corrective Action Required
06/20/2016

LABEL ALL DOORS TO SPRINKLER ROOMS, MECHANICAL ROOMS, ELECTRICAL ROOMS, ELEVATOR ROOMS WITH THE ROOM DESIGNATION. (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
06/20/2016

ALL EXTERIOR HORN/STROBE ALARM DEVICES NEED TO BE LOCATED AS CLOSE AS POSSIBLE OR ABOVE THE FDCS (VERIFIED AT INSPECTION)
Misc
Corrective Action Required
06/20/2016

STAIRWAY LANDINGS SHALL TO BE LABELED WITH THE FLOOR LEVEL DESIGNATION. (VERIFIED AT INSPECTION)
Access roads required for building and facilities
Corrective Action Required
06/20/2016

2012 IFC 503.1.1 Buildings and facilities. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 150 feet (45 720 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility. Exception: The fire code official is authorized to increase the dimension of 150 feet (45,720 mm) where: 1.The building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3. 2. Fire apparatus access roads cannot be installed because of location on property, topography, waterways, nonnegotiable grades or other similar conditions, and an approved alternative means of fire protection is provided. 3. There are not more than two Group R-3 or Group U occupancies. PROVIDE DETAILS OF THE ACCESS ROADWAY AS PER THE PDP.
Fire Plan Review Rejected 06/07/2016 06/02/2016
Joe Dir
Misc
Corrective Action Required
06/02/2016

DOORS / HARDWARE: [B] 1008.1 Doors.Means of egress doors shall meet the requirements of this section. Doors serving a means of egress system shall meet the requirements of this section and Section 1020.2. Doors provided for egress purposes in numbers greater than required by this code shall meet the requirements of this section. [B] 1008.1.9.1 Hardware. Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 of the International Building Code shall not require tight grasping, tight pinching or twisting of the wrist to operate. NO KEYED LOCKS ON THE EGRESS SIDE OF A MARKED EXIT. ALL ELECTRONICALLY CONTROLLED DOORS WILL DROP OFF UPON LOSS OF POWER AND OR THE ACTIVATION OF THE FIRE ALARM SYSTEM.
Posting of occupant load
Corrective Action Required
06/02/2016

2012 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. POST THE OCCUPANT LOAD IN ALL ROOMS AND ASSEMBLY AREAS WITH A OCCUPANT LOAD OVER 50.
Material safety and data sheets
Corrective Action Required
06/02/2016

2012 IFC 407.2- Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be readily available on the premises. POST NFPA 704 PLACARDS AT THE STROAGE AREAS, OF POOL CHEMICALS AND OR OTHER POTENTIAL HAZARDOUS MATERIALS TO BE STORED IN THE BUILDINGS.
Construction documents for fire alarm systems
Corrective Action Required
06/02/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS FOR THE FIRE ALARM SYSTEM TO BE INSTALLED.
Address numbers required
Corrective Action Required
06/02/2016

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). POST HE NUMERIC ADDRESS OF ALL THE BUILDINGS READABLE FROM THE ADDRESSES ROADWAY. MAY REQUIRED POSTING THE ADDRESS ON MORE THAN ONE SIDE OF EACH OF THE BUILDINGS.
Knox box required
Corrective Action Required
06/02/2016

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. PROVIDE A KNOX BOX FOR EACH BUILDING AND EACH ELEVATOR BANK. BOXES CAN BE OBTAINED ON LINE knox.box.com 506.1.2 Key boxes for nonstandardized fire service elevator keys. Key boxes provided for nonstandardized fire service elevator keys shall comply with Section 506.1 and all of the following: 1. The key box shall be compatible with an existing rapid entry key box system in use in the jurisdiction and approved by the fire code official. 2. The front cover shall be permanently labeled with the words “Fire Department Use Only—Elevator Keys.” 3. The key box shall be mounted at each elevator bank at the lobby nearest to the lowest level of fire department access. 4. The key box shall be mounted 5 feet 6 inches (1676 mm) above the finished floor to the right side of the elevator bank. 5. Contents of the key box are limited to fire service elevator keys. Additional elevator access tools, keys and information pertinent to emergency planning or elevator access shall be permitted when authorized by the fire code official. 6. In buildings with two or more elevator banks, a single key box shall be permitted to be used when such elevator banks are separated by not more than 30 feet (9144 mm). Additional key boxes shall be provided for each individual elevator or elevator bank separated by more than 30 feet (9144 mm).
Construction documents - Fire protection systems
Corrective Action Required
06/02/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE SELECTED CONTRACTORS PROVIDE SHOP DRAWINGS FOR THE FIRE SPRINKLER SYSTEM, CLASS 1 STANDPIPE SYSTEM AND THE KITCHEN HOOD SUPRESSION SYSTEMS TO BE INSTALLED.
Installation acceptance testing
Corrective Action Required
06/02/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTING WILL BE REQUIRED FOR THE SPRINKLER, ALARM AND KITCHEN HOOD SUPRESSION SYSTEMS PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
06/02/2016

2012 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. PROVIDE A K-CLASS FIRE EXTINGUISHER FOR THE TYPE 1 KITCHEN HOOD.
Portable fire extinguishers - general
Corrective Action Required
06/02/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. THE MINIMUM SIZED FIRE EXTINGUISHERS WILL BE (5POUND) 2A-10BC
Portable fire extinguishers - conspicuous locations
Corrective Action Required
06/02/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. THE MAXIMUM TRAVEL DISTANCE TO A FIRE EXTINGUISHER WILL BE 75'
Misc
Corrective Action Required
06/02/2016

NO STROBES (ALARM NOTIFICATION) IN THE STAIRWAYS.
Misc
Corrective Action Required
06/02/2016

1ST FLOOR EGRESS A-WING STAIRWAY #2, DOOR A102 & A-103 NEED TO SWING IN THE DIRECTION OF EGRESS.
Misc
Corrective Action Required
06/02/2016

LABEL ALL DOORS TO SPRINKLER ROOMS, MECHANICAL ROOMS, ELECTRICAL ROOMS, ELEVATOR ROOMS WITH THE ROOM DESIGNATION.
Misc
Corrective Action Required
06/02/2016

ALL EXTERIOR HORN/STROBE ALARM DEVICES NEED TO BE LOCATED AS CLOSE AS POSSIBLE OR ABOVE THE FDCS
Misc
Corrective Action Required
06/02/2016

NO MENTION OF CO MONITORING BEING PRESENT IN THE GARAGE AREA. CONFIRM IF CO MONITORING WILL BE PRESENT OF NOT.
Misc
Corrective Action Required
06/02/2016

STAIRWAY LANDINGS SHALL TO BE LABELED WITH THE FLOOR LEVEL DESIGNATION.
Access roads required for building and facilities
Corrective Action Required
06/02/2016

2012 IFC 503.1.1 Buildings and facilities. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 150 feet (45 720 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility. Exception: The fire code official is authorized to increase the dimension of 150 feet (45,720 mm) where: 1.The building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3. 2. Fire apparatus access roads cannot be installed because of location on property, topography, waterways, nonnegotiable grades or other similar conditions, and an approved alternative means of fire protection is provided. 3. There are not more than two Group R-3 or Group U occupancies. PROVIDE DETAILS OF THE ACCESS ROADWAY AS PER THE PDP.
Building Plan Review Rejected 06/07/2016 05/27/2016
Joe Frogge
License Tax Application
Corrective Action Required
05/27/2016

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Final Development Plan
Corrective Action Required
05/27/2016

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
05/27/2016

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
Misc
Corrective Action Required
05/27/2016

Footings, pads, etc. to be designed per site conditions. Action required: Provide soils report by licensed engineer to verify existing soils conditions. Plans cite 2500 psf while 2000 psf is common in this area.
Misc
Corrective Action Required
05/27/2016

Additional information required. Action required: Provide complete details and information for -- U.L. 438 (wall P2) GA #351 (wall HH2) U.L. U905 (walls W, W1, & W2) U.L. unknown (Wall JJ)
Misc
Corrective Action Required
05/27/2016

2012 IBC 716.5 Fire door and shutter assemblies. Approved fire door and fire shutter assemblies shall be constructed of any material or assembly of component materials that conforms to the test requirements of Section 716.5.1, 716.5.2 or 716.5.3 and the fire protection rating indicated in Table 716.5. Fire door frames with transom lights, sidelights or both shall be permitted in accordance with Section 716.5.6. Fire door assemblies and shutters shall be installed in accordance with the provisions of this section and the NFPA 80. Action required: Review and update door schedule as concerns minimum fire ratings. Multiple found to be incorrect or missing.
Engineered truss package
Corrective Action Required
05/27/2016

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide floor and roof truss packages or request to defer to construction.
Screening - Ground mounted equipment
Corrective Action Required
05/27/2016

Unified Development Ordinance Article 7, Section 7.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section.
Health Dept Review
Corrective Action Required
05/27/2016

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
05/27/2016

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Miscellaneous Correction
Corrective Action Required
05/27/2016

2012 IBC 1008.1.3 Door opening force. The force for pushing or pulling open interior swinging egress doors, other than fire doors, shall not exceed 5 pounds (22 N). For other swinging doors, as well as sliding and folding doors, the door latch shall release when subjected to a 15-pound (67 N) force. The door shall be set in motion when subjected to a 30-pound (133 N) force. The door shall swing to a full-open position when subjected to a 15-pound (67 N) force. Action required: Modify specifications to show compliance.
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Corrective Action Required
05/27/2016

ICC A117.1-2009 Section 404.2.3.2 Swinging Doors. Swinging doors shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Modify plans to demonstrate compliance at locker doors C143B & C145B and electrical room door C162
Bldg - Occupant load posting 1004.3
Corrective Action Required
05/27/2016

2012 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Comment is for informational purposes. May be verified at inspections.
Misc
Corrective Action Required
05/27/2016

2012 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30" (see code section for additional construction requirements) Action required: Provide permanent access to roof.
Misc
Corrective Action Required
05/27/2016

2012 IMC 506.5.3 Exhaust fan mounting. An upblast fan shall be hinged and supplied with a flexible weatherproof electrical cable to permit inspection and cleaning. The ductwork shall extend a minimum of 18 inches above the roof surface. Action required: Modify fan detail to show hinge and duct extension.
Misc
Corrective Action Required
05/27/2016

506.3.8 Grease duct cleanouts and openings. Grease duct cleanouts and openings shall comply with all of the following: 1. Grease ducts shall not have openings except where required for the operation and maintenance of the system. 2. Sections of grease ducts that are inaccessible from the hood or discharge openings shall be provided with cleanout openings. 3. Cleanouts and openings shall be equipped with tight-fitting doors constructed of steel having a thickness not less than that required for the duct. 4. Cleanout doors shall be installed liquid tight. 5. Door assemblies including any frames and gaskets shall be approved for the application and shall not have fasteners that penetrate the duct. 6. Gasket and sealing materials shall be rated for not less than 1500°F (816°C). 7. Listed door assemblies shall be installed in accordance with the manufacturer’s instructions. Action required: Specify and show locations of grease duct cleanouts.
Misc
Corrective Action Required
05/27/2016

Additional information needed for review. Action required: Specify pool heaters including any combustion air requirements.
Miscellaneous Correction
Corrective Action Required
05/27/2016

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles in kitchen and bars will by GFCI protected.
Licensed Contractors Rejected 06/07/2016 05/27/2016
Joe Frogge
LC - MEP Subs
Corrective Action Required
05/27/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $18,808.42 $18,808.42 Paid 11/22/2016
8331507-Sewer Connection Fee $1,410.00 $1,410.00 Paid 11/22/2016
8331401-Water Tap Fee $10,714.00 $10,714.00 Paid 11/22/2016
8350015-Water Meter Fee $2,816.73 $2,816.73 Paid 11/22/2016
9110073-Right of Way Permit Fee $75.00 $75.00 Paid 11/22/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 12/2/2016 12/2/2016 12/02/2016
Misc
Partial Correction
12/02/2016
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT:FROM WEST END EAST TO 6" BLDG DRAIN + 6" SOUTH TO UNDER FOOTING; NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Underslab Plumbing Inspection - Commercial Partial 12/8/2016 12/08/2016
Misc
Partial Correction
12/08/2016
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT:FROM WEST END EAST TO 6" BLDG DRAIN + 6" SOUTH TO UNDER FOOTING; REMAINDER OF PVC UNDER-SLAB DWV EXCEPT LINES TO POOL & EMPLOYEE RR; NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Underslab Electrical Inspection - Commercial Partial 12/8/2016 12/08/2016
Misc
Partial Correction
12/08/2016
OK TO COVER WHEN READY ONE 3" PVC DATACOMM CONDUIT AT WEST END OF BLDG; INSTALLATION IN PROGRESS OF TWO 3" PVC CONDUITS W>E ACROSS LENGTH OF BLDG;
Underslab Electrical Inspection - Commercial Partial 12/12/2016 12/12/2016
Misc
Partial Correction
12/08/2016
OK TO COVER WHEN READY ONE 3" PVC DATACOMM CONDUIT AT WEST END OF BLDG; INSTALLATION IN PROGRESS OF TWO 3" PVC CONDUITS W>E ACROSS LENGTH OF BLDG;
Underslab Electrical Inspection - Commercial Partial 12/12/2016 12/12/2016
Misc
Partial Correction
12/08/2016
OK TO COVER WHEN READY: ONE 3" PVC DATACOMM CONDUIT AT WEST END OF BLDG; TWO 3" PVC CONDUITS W>E ACROSS LENGTH OF BLDG COMPLETE TO ELECTRICAL ROOM; FIVE 4" + TWO 3" PVC CONDUITS FROM ELECT RM E/SE/S TO THROUGH GRADE BEAM AT S WALL; THREE 1" CONDUITS STUBBED THROUGH GRADE BEAM AT S WALL;
Underslab Plumbing Inspection - Commercial Partial 12/12/2016 12/12/2016 12/12/2016
Misc
Partial Correction
12/08/2016
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT:FROM WEST END EAST TO 6" BLDG DRAIN + 6" SOUTH TO UNDER FOOTING; REMAINDER OF PVC UNDER-SLAB DWV EXCEPT LINES TO POOL & EMPLOYEE RR; NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Misc
Partial Correction
12/12/2016
OK TO COVER WHEN READY UNDER-SLAB C.I. GREASE WASTE PIPING COMPLETE
Underslab Electrical Inspection - Commercial Partial 12/16/2016 12/16/2016 12/16/2016
Misc
Partial Correction
12/12/2016
OK TO COVER WHEN READY: ONE 3" PVC DATACOMM CONDUIT AT WEST END OF BLDG; TWO 3" PVC CONDUITS W>E ACROSS LENGTH OF BLDG COMPLETE TO ELECTRICAL ROOM; FIVE 4" + TWO 3" PVC CONDUITS FROM ELECT RM E/SE/S TO THROUGH GRADE BEAM AT S WALL; THREE 1" CONDUITS STUBBED THROUGH GRADE BEAM AT S WALL; CONDUIT AND BOXES AT BASE COMPLETE FROM (II) TO WEST END;
Underslab Electrical Inspection - Commercial Passed 1/3/2017 1/3/2017 01/03/2017
Misc
Resolved
01/03/2017
OK TO COVER WHEN READY: ONE 3" PVC DATACOMM CONDUIT AT WEST END OF BLDG; TWO 3" PVC CONDUITS W>E ACROSS LENGTH OF BLDG COMPLETE TO ELECTRICAL ROOM; FIVE 4" + TWO 3" PVC CONDUITS FROM ELECT RM E/SE/S TO THROUGH GRADE BEAM AT S WALL; THREE 1" CONDUITS STUBBED THROUGH GRADE BEAM AT S WALL; CONDUIT AND BOXES AT BASE COMPLETE FROM (II) TO WEST END;
Footing Inspection - Commercial Partial 2/2/2017 2/2/2017 02/02/2017
Misc
Partial Correction
02/02/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: C6/DD.1; C7/DD.1; C6/EE.1; C7/EE.1; C4.7/AA3; BB/C.5; CC/C.5; DD/C.5; C5.8/C5.2; C5.8/C5.3; C2.2/DD.1; C2.2/EE; C2.6/DD.1; C2.6/EE; C2.6/GG; C2.6/HH.3;
Pool Steel/Bonding - Commercial Partial 2/7/2017 02/07/2017
Misc
Partial Correction
02/07/2017
POOL SHELL RE-BAR BONDED TO PERIMETER BONDING RING WITH LEADS TO BEYOND SHELL POUR
Underground Plumbing Inspection - Commercial Failed 2/21/2017 02/21/2017
Misc
Resolved
02/21/2017
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT:FROM WEST END EAST TO 6" BLDG DRAIN + 6" SOUTH TO UNDER FOOTING; REMAINDER OF PVC UNDER-SLAB DWV EXCEPT LINES TO POOL & EMPLOYEE RR; NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Misc
Resolved
02/21/2017
OK TO COVER WHEN READY UNDER-SLAB C.I. GREASE WASTE PIPING COMPLETE
Misc
Corrective Action Required
02/21/2017
GREASE INTERCEPTOR SET AND PARTIALLY BACKFILLED WITH CRUSHER-RUN FINES. ANTI-BOUYANCY SLAB SAID NOT TO HAVE BEEN PLACED PER APPROVED DRAWING.
Footing Inspection - Commercial Partial 2/23/2017 02/23/2017
Misc
Partial Correction
02/02/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: C6/DD.1; C7/DD.1; C6/EE.1; C7/EE.1; C4.7/AA3; BB/C.5; CC/C.5; DD/C.5; C5.8/C5.2; C5.8/C5.3; C2.2/DD.1; C2.2/EE; C2.6/DD.1; C2.6/EE; C2.6/GG; C2.6/HH.3;
Misc
Partial Correction
02/23/2017
OK TO POUR WHEN READY FOOTING FOR SCREEN WALL AT SERVICE YARD PER SECTION 1/S3.2
Foundation Inspection - Commercial Partial 2/24/2017 (10:00) 2/24/2017 02/24/2017
Misc
Resolved
02/24/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: C6/DD.1; C7/DD.1; C6/EE.1; C7/EE.1; C4.7/AA3; BB/C.5; CC/C.5; DD/C.5; C5.8/C5.2; C5.8/C5.3; C2.2/DD.1; C2.2/EE; C2.6/DD.1; C2.6/EE; C2.6/GG; C2.6/HH.3;
Misc
Resolved
02/24/2017
OK TO POUR WHEN READY FOOTING FOR SCREEN WALL AT SERVICE YARD PER SECTION 1/S3.2
Misc
Partial Correction
02/24/2017
OK TO POUR WHEN READY RADIUS FOUNDATION WALL AT POOL AREA NORTH
Electrical Service Inspection Partial 3/1/2017 03/01/2017
Misc
Partial Correction
03/01/2017
RELEASE TEMPORARY ELECTRICAL SERVICE
Underslab Plumbing Inspection - Commercial Partial 3/17/2017 03/17/2017
Misc
Partial Correction
03/17/2017
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT:FROM WEST END EAST TO 6" BLDG DRAIN + 6" SOUTH TO UNDER FOOTING; REMAINDER OF PVC UNDER-SLAB DWV EXCEPT LINES TO POOL & EMPLOYEE RR; PIPING & P-TRAPS(ALLOWED IN LIEU OF INDIRECT WASTE) FOR TRENCH DRAINS AT PERMIT PRINT MARKS #1; 2; 3; NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Misc
Resolved
03/17/2017
OK TO COVER WHEN READY UNDER-SLAB C.I. GREASE WASTE PIPING COMPLETE
Underslab Electrical Inspection - Commercial Partial 3/21/2017 03/21/2017
Misc
Partial Correction
02/01/2017
OK TO COVER WHEN READY PVC UNDER-SLAB ELECTRICAL CONDUIT: ONE 3" + ONE 1" FROM ELEVATOR EQUIPMENT ROOM TO MDP LOCATION; LOWER LIFT CONDUIT COMPLETE AT MDP LOCATION; ONE 2" PVC FROM EXIT UNDER BLDG NE SLAB EXTENDED N INTO POOL EQUIPMENT AREA;
Underslab Plumbing Inspection - Commercial Partial 3/21/2017 03/21/2017
Misc
Partial Correction
03/17/2017
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT:FROM WEST END EAST TO 6" BLDG DRAIN + 6" SOUTH TO UNDER FOOTING; REMAINDER OF PVC UNDER-SLAB DWV EXCEPT LINES TO POOL & EMPLOYEE RR; PIPING & P-TRAPS(ALLOWED IN LIEU OF INDIRECT WASTE) FOR TRENCH DRAINS AT PERMIT PRINT MARKS #1; 2; 3; REMAINDER OF PIPING FOR TRENCH DRAINS AT EAST HALF OF POOL BLDG; PIPING AT POOL EQUIPMENT ROOMS YET TO BE INSTALLED & INSPECTED. NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Rough Framing Inspection - Commercial Partial 3/24/2017 03/24/2017
Misc
Partial Correction
03/24/2017
EXTERIOR WALL SHEATHING: NAIL PATTERN SUBSTANTIALLY COMPLETED CORRECTLY; SOME AREAS POINTED OUT TO BE CHECKED AND CORRECTED AS NECESSARY
Underground Electrical Inspection - Commercial Partial 4/18/2017 4/18/2017 04/18/2017
Misc
Partial Correction
04/18/2017
NO ISSUES FOUND WITH PVC CONDUIT TO BE CAST INTO POUR OF ENTRY SLAB AT VESTIBULE 101 PVC CONDUIT IN PLACE BEYOND THE PREP FOR SLAB POUR WILL NEED TO BE PROTECTED IF NOT =>18" BELOW FINAL GRADE
In-wall Inspection Partial 4/21/2017 4/21/2017 04/21/2017
Misc
Partial Correction
04/21/2017
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT: MDP RM C162 EXCEPT NW CORNER WHERE TIE-DOWN HAS YET TO BE APPROVED;
Above Ceiling Inspection Partial 4/25/2017 04/25/2017
Misc
Partial Correction
04/25/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C119; C121; C122; C123; C148; C158;
Concrete Walls and Columns Inspection Passed 4/26/2017 (8:00) 4/26/2017 04/26/2017
Misc
Partial Correction
02/01/2017
OK TO POUR WHEN READY RETAINING WALL AT NORTH PER SECTION 6/S3.4;
Rated Assembly Inspection Partial 4/26/2017 4/26/2017 04/26/2017
Misc
Partial Correction
04/26/2017
OK TO COVER WHEN READY COMPONENTS OF RATED ASSEMBLIES: ONE LAYER 5/8" TYPE X GWB AT C162 NORTH & EAST WALLS;
Above Ceiling Inspection Partial 4/28/2017 4/28/2017 04/28/2017
Misc
Partial Correction
04/25/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C119; C121; C122; C123; C148; C158; [C104; C105; C108; C115; C118;
Above Ceiling Inspection Partial 5/5/2017 5/5/2017 05/05/2017
Misc
Partial Correction
04/28/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C119; C121; C122; C123; C148; C158; [C104; C105; C108; C115; C118; [C102; C104 - C108; C113 - C129; C131 - C134; C137 - C138; C140; C142 - C144; C146; C147 - C149; C154 - C159; C163;
Gas Piping Inspection - Commercial Partial 5/10/2017 5/10/2017 05/10/2017
Misc
Partial Correction
05/10/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #2*; 4; 5; 7*; *GROUND RODS NOT PRESENTLY IN PLACE:
Rough Framing Inspection - Commercial Partial 5/10/2017 05/10/2017
Misc
Partial Correction
03/24/2017
EXTERIOR WALL SHEATHING: NAIL PATTERN SUBSTANTIALLY COMPLETED CORRECTLY; SOME AREAS POINTED OUT TO BE CHECKED AND CORRECTED AS NECESSARY
Misc
Partial Correction
05/10/2017
FRAMER TO INSTALL TRUSS WEB BRACING WHERE MISSING IN ADVANCE OF ABOVE-CEILING INSULATION INSTALLATION; ALSO AT DOUBLE TRUSSES BOTTOM CHORDS ARE TO BE FULLY NAILED TIGHT. THEN OK TO INSULATE AND INSTALL CEILING GWB.
Underground Electrical Inspection - Commercial Partial 5/10/2017 5/10/2017 05/10/2017
Misc
Partial Correction
04/18/2017
NO ISSUES FOUND WITH PVC CONDUIT TO BE CAST INTO POUR OF ENTRY SLAB AT VESTIBULE 101 PVC CONDUIT IN PLACE BEYOND THE PREP FOR SLAB POUR WILL NEED TO BE PROTECTED IF NOT =>18" BELOW FINAL GRADE
Misc
Partial Correction
05/10/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #2*; 4; 5; 7*; *GROUND RODS NOT PRESENTLY IN PLACE.
Gas Piping Inspection - Commercial Partial 5/10/2017 05/10/2017
Misc
Partial Correction
05/10/2017
GAS PIPING PRESSURE TEST HELD STEADY AT >= 10 PSI FOR >=10 MIN. ON PIPING EAST OF (EE) EXCLUDING RISER(S) TO ROOFTOP EQUIPMENT NO ISSUES FOUND ON VISUAL INSPECTION OF SAME
Underground Electrical Inspection - Commercial Partial 5/11/2017 5/11/2017 05/11/2017
Misc
Resolved
05/11/2017
NO ISSUES FOUND WITH PVC CONDUIT TO BE CAST INTO POUR OF ENTRY SLAB AT VESTIBULE 101 PVC CONDUIT IN PLACE BEYOND THE PREP FOR SLAB POUR WILL NEED TO BE PROTECTED IF NOT =>18" BELOW FINAL GRADE
Misc
Partial Correction
05/10/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #2*; 4; 5; 7*; *GROUND RODS NOT PRESENTLY IN PLACE.
Misc
Partial Correction
05/11/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST; ONE 3/4" TO 28' WEST CONN TO EXSTG;
Underground Electrical Inspection - Commercial Partial 5/15/2017 5/15/2017 05/15/2017
Misc
Partial Correction
05/11/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #2*; 4; 5; 7*; *GROUND RODS NOT PRESENTLY IN PLACE.
Misc
Partial Correction
05/11/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL;
In-wall Inspection Not Ready 5/15/2017 5/15/2017 05/15/2017
Misc
Partial Correction
04/21/2017
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT: MDP RM C162 EXCEPT NW CORNER WHERE TIE-DOWN HAS YET TO BE APPROVED;
Underground Electrical Inspection - Commercial Partial 5/16/2017 5/16/2017 05/16/2017
Misc
Partial Correction
05/15/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #2*; 4; 5; 7; 8; *GROUND ROD NOT PRESENTLY IN PLACE.
Misc
Partial Correction
05/15/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS;
Rated Assembly Inspection Partial 5/16/2017 05/16/2017
Misc
Partial Correction
04/26/2017
OK TO COVER WHEN READY COMPONENTS OF RATED ASSEMBLIES: PRE-ROCK ON S WALL OF SPACE 110 ONCE TAPED & MUDDED;
In-wall Inspection Partial 5/17/2017 5/17/2017 05/17/2017
Misc
Partial Correction
05/15/2017
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT: MDP RM C162; 110; 111; 136; 137; 138; 143; 145; 148; 149; 154; 155; 156; COVER NO FRAMED WALLS ALONG NORTH CMU WALL WHERE FIRE-BLOCKING IS NOT DONE & APPROVED.
Footing Inspection - Commercial Partial 5/18/2017 (4:00) 5/18/2017 05/18/2017
Misc
Resolved
05/18/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: C6/DD.1; C7/DD.1; C6/EE.1; C7/EE.1; C4.7/AA3; BB/C.5; CC/C.5; DD/C.5; C5.8/C5.2; C5.8/C5.3; C2.2/DD.1; C2.2/EE; C2.6/DD.1; C2.6/EE; C2.6/GG; C2.6/HH.3;
Misc
Partial Correction
05/18/2017
OK TO POUR WHEN READY: FOOTING FOR SCREEN WALL AT SERVICE YARD PER SECTION 1/S3.2; FOOTING FOR TRASH ENCLOSURE
In-wall Inspection Partial 5/19/2017 5/19/2017 05/19/2017
Misc
Partial Correction
05/17/2017
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT: MDP RM C162; 110; 111; 136; 137; 138; 143; 145; 148; 149; 154; 155; 156; [106; 107; 127; 128; 131; 133; 134; 135; 157; 159; 162;
Rated Assembly Inspection Partial 5/19/2017 5/19/2017 05/19/2017
Misc
Partial Correction
05/16/2017
OK TO COVER WHEN READY COMPONENTS OF RATED WALL ASSEMBLIES: PRE-ROCK ON S WALL OF SPACE 110 ONCE TAPED & MUDDED;
Misc
Partial Correction
05/19/2017
OK TO COVER WHEN READY COMPONENTS OF UL P522 RATED CEILING ASSEMBLIES AT SPACES: 136-138; 159; 162;
Rated Assembly Inspection Partial 5/23/2017 5/23/2017 05/23/2017
Misc
Partial Correction
05/19/2017
OK TO COVER WHEN READY COMPONENTS OF RATED WALL ASSEMBLIES: PRE-ROCK ON S WALL OF SPACE 110 ONCE TAPED & MUDDED;
Misc
Partial Correction
05/19/2017
OK TO COVER WHEN READY COMPONENTS OF UL P522 RATED CEILING ASSEMBLIES AT SPACES: 126; 136-138; 141- 144; 147; 148; 154-158; 159; 161; 162;
Underground Electrical Inspection - Commercial Partial 5/23/2017 5/23/2017 05/23/2017
Misc
Partial Correction
05/16/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #2; 4; 5; 7; 8; 9 - 13;
Misc
Partial Correction
05/16/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS;
In-wall Inspection Partial 5/23/2017 5/23/2017 05/23/2017
Misc
Partial Correction
05/19/2017
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT: MDP RM C162; 110; 111; 136; 137; 138; 143; 145; 148; 149; 154; 155; 156; [106; 107; 127; 128; 131; 133; 134; 135; 157; 159; 162; [104; 105; 108; 109; 112; 117; 118; 119; 121; 123; 129; 132; 141; 142; 144; 146; 147; 158; 161; 163;
In-wall Inspection Partial 5/24/2017 5/24/2017 05/24/2017
Misc
Partial Correction
05/23/2017
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT: C104; 105; 106; 107; 108; 109; 110; 111; 112; 117; 118; 119; 121; 123; 127; 128; 129; 131; 132; 133; 134; 135; 136; 137; 138; 141; 142; 143; 144; 145; 146; 147; 148; 149; 154; 155; 156; 157; 158; 159; 161; 162; 163; [125;
Underground Electrical Inspection - Commercial Partial 5/24/2017 5/24/2017 05/24/2017
Misc
Partial Correction
05/23/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #2; 4; 5; 7; 8; 9 - 13;
Misc
Partial Correction
05/23/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12;
Rated Assembly Inspection Partial 5/25/2017 5/25/2017 05/25/2017
Misc
Partial Correction
05/23/2017
OK TO COVER WHEN READY COMPONENTS OF RATED WALL ASSEMBLIES: 110; 1ST LAYER PRE-ROCK AT 143 & 145;
Misc
Partial Correction
05/23/2017
OK TO COVER WHEN READY COMPONENTS OF UL P522 RATED CEILING ASSEMBLIES AT SPACES: 126; 136-138; 141- 144; 147; 148; 154-158; 159; 161; 162; [108; 110; 117; 118; 125-129; 132; 135;
Underground Electrical Inspection - Commercial Partial 5/25/2017 05/25/2017
Misc
Partial Correction
05/24/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #2; 4; 5; 7; 8; 9 - 13;
Misc
Partial Correction
05/24/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10;
Rated Assembly Inspection Partial 5/26/2017 05/26/2017
Misc
Partial Correction
05/25/2017
OK TO COVER WHEN READY COMPONENTS OF RATED WALL ASSEMBLIES: 110; 1ST LAYER PRE-ROCK AT 143 & 145;
Misc
Partial Correction
05/25/2017
OK TO COVER WHEN READY COMPONENTS OF UL P522 RATED CEILING ASSEMBLIES AT SPACES: 108; 110; 117; 118; 125-129; 132; 135; 136-138; 141- 144; 147; 148; 154-158; 159; 161; 162; [104-107; 121-123;
Footing Inspection - Commercial Passed 5/31/2017 (9:00) 5/31/2017 05/31/2017
Misc
Resolved
05/31/2017
OK TO POUR WHEN READY: FOOTING FOR SCREEN WALL AT SERVICE YARD PER SECTION 1/S3.2; FOOTING FOR TRASH ENCLOSURE
In-wall Inspection Partial 5/26/2017 5/31/2017 05/31/2017
Misc
Partial Correction
05/24/2017
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT: C104; 105; 106; 107; 108; 109; 110; 111; 112; 117; 118; 119; 121; 123; 125; 127; 128; 129; 131; 132; 133; 134; 135; 136; 137; 138; 141; 142; 143; 144; 145; 146; 147; 148; 149; 154; 155; 156; 157; 158; 159; 161; 162; 163; [113; 115 N,W,S; 116;
Rated Assembly Inspection Partial 5/31/2017 05/31/2017
Misc
Partial Correction
05/26/2017
OK TO COVER WHEN READY COMPONENTS OF RATED WALL ASSEMBLIES: 110; 1ST LAYER PRE-ROCK AT 143 & 145;
Misc
Partial Correction
05/26/2017
OK TO TAPE, MUD, & FIRE-STOP WHEN UL P522 RATED CEILING ASSEMBLIES AT SPACES: 104-108; 110; 117; 118; 121-123; 125-129; 132; 135; 136-138; 141- 144; 147; 148; 154-158; 159; 161; 162; [108, 113; 115;
Electrical Service Inspection Passed 6/1/2017 06/01/2017
Misc
Resolved
06/01/2017
RELEASE TEMPORARY ELECTRICAL SERVICE
Underground Electrical Inspection - Commercial Partial 6/2/2017 6/2/2017 06/02/2017
Misc
Partial Correction
05/25/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #2; 4; 5; 7; 8; 9 - 13; #13(REPLACEMENT OF DAMAGED BASE); #14; 15;
Misc
Partial Correction
05/25/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10;
Hood/Duct Inspection Failed 6/2/2017 06/02/2017
Misc
Corrective Action Required
06/02/2017
GREASE DUCT HUNG WITHOUT PRIOR LIGHT TEST OF SEAMS NOT APPROVED FOR USE
Rated Assembly Inspection Partial 6/1/2017 6/2/2017 06/02/2017
Misc
Partial Correction
05/31/2017
OK TO COVER WHEN READY COMPONENTS OF RATED WALL ASSEMBLIES: 110; 1ST LAYER PRE-ROCK AT 143 & 145; [142; 147; 148; 157; 158;
Misc
Partial Correction
05/31/2017
OK TO TAPE, MUD, & FIRE-STOP WHEN UL P522 RATED CEILING ASSEMBLIES AT SPACES: 104-108; 110; 117; 118; 121-123; 125-129; 132; 135; 136-138; 141- 144; 147; 148; 154-158; 159; 161; 162; [108, 113; 115;
Misc
Partial Correction
06/02/2017
PP1 WALLS: SHAFT LINER LAYER APPROVED; OK TO APPLY 5/8" TYPE X AT OPPOSITE FACE AT C113 WEST & C157 EAST;
Underslab Electrical Inspection - Commercial Partial 6/5/2017 06/05/2017
Misc
Partial Correction
03/21/2017
OK TO COVER WHEN READY PVC UNDER-SLAB ELECTRICAL CONDUIT: ONE 3" + ONE 1" FROM ELEVATOR EQUIPMENT ROOM TO MDP LOCATION; LOWER LIFT CONDUIT COMPLETE AT MDP LOCATION; ONE 2" PVC FROM EXIT UNDER BLDG NE SLAB EXTENDED N INTO POOL EQUIPMENT AREA; CONDUIT AT SUBGRADE THROUGHOUT POOL AREA;
Pool Steel/Bonding - Commercial Partial 6/6/2017 06/06/2017
Misc
Partial Correction
06/06/2017
POOL SHELL RE-BAR BONDED TO PERIMETER BONDING RING WITH LEADS TO BEYOND SHELL POUR
Misc
Partial Correction
06/06/2017
POOL DECK REINFORCING MESH BONDED; READY FOR DECK POUR
Underground Electrical Inspection - Commercial Partial 6/7/2017 6/7/2017 06/07/2017
Misc
Partial Correction
06/02/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #2; 4; 5; 7; 8; 9 - 13; #13(REPLACEMENT OF DAMAGED BASE); #14; 15;
Misc
Partial Correction
06/02/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15;
Rated Assembly Inspection Partial 6/7/2017 6/7/2017 06/07/2017
Misc
Partial Correction
06/02/2017
OK TO COVER WHEN READY COMPONENTS OF RATED WALL ASSEMBLIES: 110; 142; 147; 148; 157; 158; [106; 107; 117; 118; 127; 128; 135-138; 143; 145;
Misc
Partial Correction
06/02/2017
OK TO TAPE, MUD, & FIRE-STOP WHEN UL P522 RATED CEILING ASSEMBLIES AT SPACES: 104-108; 110; 117; 118; 121-123; 125-129; 132; 135; 136-138; 141- 144; 147; 148; 154-158; 159; 161; 162; [108, 113; 115;
Misc
Partial Correction
06/02/2017
PP1 WALLS: SHAFT LINER LAYER APPROVED; OK TO APPLY 5/8" TYPE X AT OPPOSITE FACE AT C113 WEST & C157 EAST;
Underground Electrical Inspection - Commercial Partial 6/8/2017 06/08/2017
Misc
Partial Correction
06/07/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #2; 4; 5; 7; 8; 9 - 13; #13(REPLACEMENT OF DAMAGED BASE); #14; 15; #1; #3;
Misc
Partial Correction
06/07/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15;
Hood/Duct Inspection Partial 6/8/2017 6/8/2017 06/08/2017
Misc
Partial Correction
06/08/2017
LIGHT TEST OF GREASE DUCT SHOP WELDS OF SEAMS: ONE HOLE FOUND -- TO BE SPOT-WELDED; THEN OK TO HANG. REQUEST LIGHT TEST OF FIELD WELDS WHEN READY.
In-wall Inspection Partial 6/9/2017 06/09/2017
Misc
Partial Correction
05/31/2017
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT: C104; 105; 106; 107; 108; 109; 110; 111; 112; 113; 116; 117; 118; 119; 121; 123; 125; 127; 128; 129; 131; 132; 133; 134; 135; 136; 137; 138; 141; 142; 143; 144; 145; 146; 147; 148; 149; 154; 155; 156; 157; 158; 159; 161; 162; 163; [115 PERIMETER + KNEE WALL AT BAR;
Rated Assembly Inspection Partial 6/13/2017 6/13/2017 06/13/2017
Misc
Partial Correction
06/07/2017
OK TO COVER WHEN READY COMPONENTS OF RATED WALL ASSEMBLIES: 106; 107; 110; 117; 118; 127; 128; 135-138; 142; 143; 145; 147; 148; 157; 158; [104; 105; 108; 109; 113; 119; 122;
Misc
Partial Correction
06/07/2017
OK TO TAPE, MUD, & FIRE-STOP WHEN UL P522 RATED CEILING ASSEMBLIES AT SPACES: 104-108; 110; 117; 118; 121-123; 125-129; 132; 135; 136-138; 141- 144; 147; 148; 154-158; 159; 161; 162; [108, 113; 115;
Misc
Partial Correction
06/07/2017
PP1 WALLS: SHAFT LINER LAYER APPROVED; OK TO APPLY 5/8" TYPE X AT OPPOSITE FACE AT C113 WEST & C157 EAST;
Underground Electrical Inspection - Commercial Partial 6/13/2017 6/13/2017 06/13/2017
Misc
Partial Correction
06/08/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #15;
Misc
Partial Correction
06/08/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST
Above Ceiling Inspection Partial 6/13/2017 6/15/2017 06/15/2017
Misc
Partial Correction
05/05/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C119; C121; C122; C123; C148; C158; [C104; C105; C108; C115; C118; [C102; C104 - C108; C113 - C129; C131 - C134; C137 - C138; C140; C142 - C144; C146; C147 - C149; C154 - C159; C163; FOUR HANGING SOFFITS AT AEROBICS 217;
Underslab Electrical Inspection - Commercial Passed 6/8/2017 6/30/2017 06/30/2017
Misc
Resolved
06/30/2017
OK TO COVER WHEN READY PVC UNDER-SLAB ELECTRICAL CONDUIT: ONE 3" + ONE 1" FROM ELEVATOR EQUIPMENT ROOM TO MDP LOCATION; LOWER LIFT CONDUIT COMPLETE AT MDP LOCATION; ONE 2" PVC FROM EXIT UNDER BLDG NE SLAB EXTENDED N INTO POOL EQUIPMENT AREA; CONDUIT AT SUBGRADE THROUGHOUT POOL AREA;
Underslab Plumbing Inspection - Commercial Passed 6/30/2017 06/30/2017
Misc
Resolved
06/30/2017
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DRAIN, WASTE, & VENT PIPING AT:FROM WEST END EAST TO 6" BLDG DRAIN + 6" SOUTH TO UNDER FOOTING; REMAINDER OF PVC UNDER-SLAB DWV EXCEPT LINES TO POOL & EMPLOYEE RR; PIPING & P-TRAPS(ALLOWED IN LIEU OF INDIRECT WASTE) FOR TRENCH DRAINS AT PERMIT PRINT MARKS #1; 2; 3; REMAINDER OF PIPING FOR TRENCH DRAINS AT EAST HALF OF POOL BLDG; PIPING AT POOL EQUIPMENT ROOMS YET TO BE INSTALLED & INSPECTED. NOTE IPC 312 / IRC P2503.5.1 REQUIREMENT FOR PRESSURE-TESTING PIPING SYSTEM.
Gas Piping Inspection - Commercial Passed 6/30/2017 06/30/2017
Misc
Resolved
06/30/2017
GAS PIPING PRESSURE TEST HELD STEADY AT >= 10 PSI FOR >=10 MIN. ON PIPING EAST OF (EE) EXCLUDING RISER(S) TO ROOFTOP EQUIPMENT NO ISSUES FOUND ON VISUAL INSPECTION OF SAME
Above Ceiling Inspection Partial 6/30/2017 7/5/2017 07/05/2017
Misc
Partial Correction
06/15/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C119; C121; C122; C123; C148; C158; [C104; C105; C108; C115; C118; [C102; C104 - C108; C113 - C129; C131 - C134; C137 - C138; C140; C142 - C144; C146; C147 - C149; C154 - C159; C163; FOUR CLOUD CEILINGS AT AEROBICS 157;
Above Ceiling Inspection Not Ready 7/10/2017 7/10/2017 07/10/2017
Misc
Partial Correction
07/05/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C119; C121; C122; C123; C148; C158; [C104; C105; C108; C115; C118; [C102; C104 - C108; C113 - C129; C131 - C134; C137 - C138; C140; C142 - C144; C146; C147 - C149; C154 - C159; C163; FOUR CLOUD CEILINGS AT AEROBICS 157;
Above Ceiling Inspection Not Ready 7/11/2017 7/11/2017 07/11/2017
Misc
Partial Correction
07/10/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C119; C121; C122; C123; C148; C158; [C104; C105; C108; C115; C118; [C102; C104 - C108; C113 - C129; C131 - C134; C137 - C138; C140; C142 - C144; C146; C147 - C149; C154 - C159; C163; FOUR CLOUD CEILINGS AT AEROBICS 157;
Rated Assembly Inspection Partial 7/11/2017 7/11/2017 07/11/2017
Misc
Partial Correction
06/13/2017
OK TO COVER WHEN READY COMPONENTS OF RATED WALL ASSEMBLIES: 104; 105; 106; 107; 108; 109; 110; 113; 117; 118; 119; 122; 127; 128; 135-138; 142; 143; 145; 147; 148; 157; 158; [154;
Misc
Partial Correction
06/13/2017
OK TO TAPE, MUD, & FIRE-STOP WHEN UL P522 RATED CEILING ASSEMBLIES AT SPACES: 104-108; 110; 113; 115; 117; 118; 121-123; 125-129; 132; 135; 136-138; 141- 144; 147; 148; 154-158; 159; 161; 162;
Misc
Partial Correction
06/13/2017
PP1 WALLS: SHAFT LINER LAYER APPROVED; OK TO APPLY 5/8" TYPE X AT OPPOSITE FACE AT C113 WEST & C157 EAST;
Rated Assembly Inspection Partial 7/11/2017 07/11/2017
Misc
Partial Correction
07/11/2017
OK TO COVER WHEN READY COMPONENTS OF RATED WALL ASSEMBLIES: 104; 105; 106; 107; 108; 109; 110; 113; 117; 118; 119; 122; 127; 128; 135-138; 142; 143; 145; 147; 148; 157; 158; [154;
Misc
Partial Correction
07/11/2017
OK TO TAPE, MUD, & FIRE-STOP WHEN UL P522 RATED CEILING ASSEMBLIES AT SPACES: 104-108; 110; 113; 115; 117; 118; 121-123; 125-129; 132; 135; 136-138; 141- 144; 147; 148; 154-158; 159; 161; 162;
Misc
Partial Correction
07/11/2017
PP1 WALLS: SHAFT LINER LAYER APPROVED; OK TO APPLY 5/8" TYPE X AT OPPOSITE FACE AT C113 WEST & C157 EAST;
Sprinkler - Hydrostatic Test Passed 7/13/2017 07/13/2017
Above Ceiling Inspection Partial 7/14/2017 7/14/2017 07/14/2017
Misc
Partial Correction
07/11/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C102; C104 - C108; C115; C118; C119; C121 - C129; C131 - C134; C137 - C138; C140; C142 - C144; C146 - C149; C154 - C159; FOUR CLOUD CEILINGS AT AEROBICS 157; C163; [104; 106; 107;
Above Ceiling Inspection Not Ready 7/20/2017 7/20/2017 07/20/2017
Misc
Partial Correction
07/14/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C102; C104 - C108; C115; C118; C119; C121 - C129; C131 - C134; C137 - C138; C140; C142 - C144; C146 - C149; C154 - C159; FOUR CLOUD CEILINGS AT AEROBICS 157; C163; [104; 106; 107;
Misc
Corrective Action Required
07/20/2017
COURTESY PRELIMINARY OBSERVATIONS AT SPACES WITH NO CEILING FRAMING/GRID INSTALLED TO DATE: 119; 121 - 124; NOTE: SECURE FLEX INSULATION AT COLLARS AND JOINTS PER SMACNA & AIR DIFFUSION COUNCIL
Above Ceiling Inspection Partial 7/24/2017 7/24/2017 07/24/2017
Misc
Partial Correction
07/20/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C102; 104; 106; 107; C104 - C108; C115; C118; C119; C121 - C129; 123; C131 - C134; C137 - C138; C140; C142 - C144; C146 - C149; C154 - C159; FOUR CLOUD CEILINGS AT AEROBICS 157; C163; [SOFFITS AT 113 EXCEPT EAST 12'; SOFFITS AT 118; SOFFITS AT 126 EXCEPT S 10'; CEILING @ 129;
Misc
Corrective Action Required
07/20/2017
COURTESY PRELIMINARY OBSERVATIONS AT SPACES WITH NO CEILING FRAMING/GRID INSTALLED TO DATE: 119; 121 - 124; NOTE: SECURE FLEX INSULATION AT COLLARS AND JOINTS PER SMACNA & AIR DIFFUSION COUNCIL
Footing Inspection - Commercial Passed 7/26/2017 (11:00) 7/26/2017 07/26/2017
Gas Piping Inspection - Commercial Partial 7/27/2017 7/27/2017 07/27/2017
Misc
Partial Correction
07/27/2017
GAS FEEDER PIPE FROM DISTRIBUTION LINE AT OBRIEN RD TO S WALL OF BLDG HELD STEADY AT 95 PSI FOR >20 MINUTES. PIPE DEPTH IN TRENCH OK TO COVER WHEN READY.
Above Ceiling Inspection Partial 7/27/2017 07/27/2017
Misc
Partial Correction
07/24/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C102; 104; 106; 107; C104 - C108; C115; C118; C119; C121 - C129; 123; C131 - C134; C137 - C138; C140; C142 - C144; C146 - C149; C154 - C159; FOUR CLOUD CEILINGS AT AEROBICS 157; C163; SOFFITS AT 113 INCLUDING EAST 12' (RD PENETRATION OF RATED WALL AT SOUTH YET TO BE RESOLVED); SOFFITS AT 118; SOFFITS AT 126 EXCEPT S 10'; CEILING @ 129;
Misc
Resolved
07/27/2017
COURTESY PRELIMINARY OBSERVATIONS AT SPACES WITH NO CEILING FRAMING/GRID INSTALLED TO DATE: 119; 121 - 124; NOTE: SECURE FLEX INSULATION AT COLLARS AND JOINTS PER SMACNA & AIR DIFFUSION COUNCIL
Hood/Duct Inspection Failed 7/25/2017 7/27/2017 07/27/2017
Misc
Partial Correction
06/08/2017
LIGHT TEST OF GREASE DUCT SHOP WELDS OF SEAMS: ONE HOLE FOUND -- TO BE SPOT-WELDED; THEN OK TO HANG. REQUEST LIGHT TEST OF FIELD WELDS WHEN READY. LIGHT TEST OF JOINT FIELD WELDS: NOT APPROVED.
Above Ceiling Inspection Partial 7/28/2017 7/28/2017 07/28/2017
Misc
Partial Correction
07/27/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C102; 104; 106; 107; C104 - C108; C115; C118; C119; C121 - C129; 123; C131 - C134; C137 - C138; C140; C142 - C144; C146 - C149; C154 - C159; FOUR CLOUD CEILINGS AT AEROBICS 157; C163; SOFFITS AT 113 INCLUDING EAST 12' (RD PENETRATION OF RATED WALL AT SOUTH YET TO BE RESOLVED); SOFFITS AT 118; SOFFITS AT 126 EXCEPT S 10'; CEILING @ 129; 141; 147; 148;
Hood/Duct Inspection Partial 7/28/2017 7/28/2017 07/28/2017
Misc
Partial Correction
07/27/2017
LIGHT TEST OF GREASE DUCT SHOP WELDS AND FIELD WELDS. OK TO APPLY WRAP AFTER ONE REMAINING HOLE IS SPOT-WELDED.
Foundation Inspection - Commercial Partial 8/1/2017 08/01/2017
Misc
Partial Correction
02/24/2017
OK TO POUR WHEN READY: RADIUS FOUNDATION WALL AT POOL AREA NORTH; PLANTER CURB WALL; BASES FOR FIREPLACE & GRILL; TRELLIS PIERS;
Above Ceiling Inspection Partial 8/1/2017 8/1/2017 08/01/2017
Misc
Partial Correction
07/28/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C102; 104; 106; 107; C104 - C108; C115; C118; C119; C121 - C129; 123; C131 - C134; C137 - C138; C140; C142 - C144; C146 - C149; C154 - C159; FOUR CLOUD CEILINGS AT AEROBICS 157; C163; SOFFITS AT 113 INCLUDING EAST 12' (RD PENETRATION OF RATED WALL AT SOUTH YET TO BE RESOLVED); SOFFITS AT 118; SOFFITS AT 126 EXCEPT S 10'; CEILING @ 129; 141; 147; 148; [111; 112; 116;
In-wall Inspection Partial 8/3/2017 8/3/2017 08/03/2017
Misc
Partial Correction
06/09/2017
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT: C104; 105; 106; 107; 108; 109; 110; 111; 112; 113; 115 PERIMETER + KNEE WALL AT BAR; 116; 117; 118; 119; 121; 123; 125; 127; 128; 129; 131; 132; 133; 134; 135; 136; 137; 138; 141; 142; 143; 144; 145; 146; 147; 148; 149; 154; 155; 156; 157; 158; 159; 161; 162; 163; [GREAT HALL 108 EAST AND WEST WALLS ONLY;
Above Ceiling Inspection Partial 8/3/2017 8/3/2017 08/03/2017
Misc
Partial Correction
08/01/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C102; 104; 106; 107; C104 - C108; 111; 112; C115; 116; C118; C119; C121 - C129; 123; C131 - C134; C137 - C138; C140; C142 - C144; C146 - C149; C154 - C159; FOUR CLOUD CEILINGS AT AEROBICS 157; C163; SOFFITS AT 113 INCLUDING EAST 12' (RD PENETRATION OF RATED WALL AT SOUTH YET TO BE RESOLVED); SOFFITS AT 118; SOFFITS AT 126 EXCEPT S 10'; CEILING @ 129; 141; 147; 148; [CORR 108; 109; REVISIONS @ 124;
Above Ceiling Inspection Partial 8/4/2017 08/04/2017
Misc
Partial Correction
08/03/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C102; 104; 106; 107; C104 - C108; 111; 112; C115; 116; C118; C119; C121 - C129; 123; C131 - C134; C137 - C138; C140; C142 - C144; C146 - C149; C154 - C159; FOUR CLOUD CEILINGS AT AEROBICS 157; C163; SOFFITS AT 113 INCLUDING EAST 12' (RD PENETRATION OF RATED WALL AT SOUTH YET TO BE RESOLVED); SOFFITS AT 118; SOFFITS AT 126 EXCEPT S 10'; CEILING @ 129; 141; 147; 148; CORR 108; 109; REVISIONS @ 124; [CORR 144;
Above Ceiling Inspection Partial 8/8/2017 08/08/2017
Misc
Partial Correction
08/04/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C102; 104; 106; 107; C104 - C108; 111; 112; C115; 116; C118; C119; C121 - C129; 123; C131 - C134; C137 - C138; C140; C142 - C144; C146 - C149; C154 - C159; FOUR CLOUD CEILINGS AT AEROBICS 157; C163; SOFFITS AT 113 INCLUDING EAST 12' (RD PENETRATION OF RATED WALL AT SOUTH YET TO BE RESOLVED); SOFFITS AT 118; SOFFITS AT 126 EXCEPT S 10'; CEILING @ 129; 141; 147; 148; CORR 108; 109; REVISIONS @ 124; CORR 144; [AV 110; WOMEN'S 143; CORR 116;
Hood/Duct Inspection Partial 8/18/2017 8/18/2017 at 9:45 AM 08/18/2017
Misc
Resolved
08/18/2017
LIGHT TEST OF GREASE DUCT SHOP WELDS AND FIELD WELDS. OK TO APPLY WRAP AFTER ONE REMAINING HOLE IS SPOT-WELDED.
Misc
Partial Correction
08/18/2017
DUCT WRAP WAS COMPLETED WITHOUT INSPECTION OF FIRST LAYER. OUTER LAYER HAS BEEN PARTIALLY OPENED AT BOTTOM OF HORIZONTAL RUN TO EXPOSE FIRST LAYER.
Above Ceiling Inspection Partial 8/22/2017 8/22/2017 at 10:20 AM 08/22/2017
Misc
Partial Correction
08/08/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C102; 104; 106; 107; C104 - C108; 111; 112; C115; 116; C118; C119; C121 - C129; 123; C131 - C134; C137 - C138; C140; C142 - C144; C146 - C149; C154 - C159; FOUR CLOUD CEILINGS AT AEROBICS 157; C163; SOFFITS AT 113 INCLUDING EAST 12' (RD PENETRATION OF RATED WALL AT SOUTH YET TO BE RESOLVED); SOFFITS AT 118; SOFFITS AT 126 EXCEPT S 10'; CEILING @ 129; 141; 147; 148; CORR 108; 109; REVISIONS @ 124; CORR 144; AV 110; WOMEN'S 143; CORR 116; MEN'S LOCKER 145 EXCEPT FOR SOUTH SHOWER UNIT;
Above Ceiling Inspection Partial 8/24/2017 8/24/2017 at 2:30 PM 08/24/2017
Misc
Partial Correction
08/22/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C102; 104; 106; 107; C104 - C108; 111; 112; C115; 116; C118; C119; C121 - C129; 123; C131 - C134; C137 - C138; C140; C142 - C144; C146 - C149; C154 - C159; FOUR CLOUD CEILINGS AT AEROBICS 157; C163; SOFFITS AT 113 INCLUDING EAST 12' (RD PENETRATION OF RATED WALL AT SOUTH YET TO BE RESOLVED); SOFFITS AT 118; SOFFITS AT 126 EXCEPT S 10'; CEILING @ 129; 141; 147; 148; CORR 108; 109; REVISIONS @ 124; CORR 144; AV 110; WOMEN'S 143; CORR 116; MEN'S LOCKER 145 INCLUDING SOUTH SHOWER UNIT;
Miscellaneous Inspection Partial 8/30/2017 8/30/2017 at 11:40 AM 08/30/2017
Underground Electrical Inspection - Commercial Partial 8/31/2017 at 9:50 AM 08/31/2017
Misc
Partial Correction
06/13/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #15; #16; 17;
Misc
Partial Correction
06/13/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST
In-wall Inspection Partial 8/31/2017 8/31/2017 at 2:45 PM 08/31/2017
Misc
Partial Correction
08/03/2017
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT: C104; 105; 106; 107; 108; 109; 110; 111; 112; 113; 115 PERIMETER + KNEE WALL AT BAR; 116; 117; 118; 119; 121; 123; 125; 127; 128; 129; 131; 132; 133; 134; 135; 136; 137; 138; 141; 142; 143; 144; 145; 146; 147; 148; 149; 154; 155; 156; 157; 158; 159; 161; 162; 163; [GREAT HALL 108 EAST AND WEST WALLS ONLY; FURRED WALLS AT PERIMETER OF POOL 151;
Above Ceiling Inspection Partial 8/31/2017 8/31/2017 at 3:05 PM 08/31/2017
Misc
Partial Correction
08/24/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C102; 104; 106; 107; C104 - C108; 111; 112; C115; 116; C118; C119; C121 - C129; 123; C131 - C134; C137 - C138; C140; C142 - C144; C146 - C149; C154 - C159; FOUR CLOUD CEILINGS AT AEROBICS 157; C163; SOFFITS AT 113 INCLUDING EAST 12' (RD PENETRATION OF RATED WALL AT SOUTH YET TO BE RESOLVED); SOFFITS AT 118; SOFFITS AT 126 EXCEPT S 10'; CEILING @ 129; 141; 147; 148; CORR 108; 109; REVISIONS @ 124; CORR 144; AV 110; WOMEN'S 143; CORR 116; MEN'S LOCKER 145 INCLUDING SOUTH SHOWER UNIT; PORTE COCHERE;
Underground Electrical Inspection - Commercial Partial 9/7/2017 at 11:25 AM 09/07/2017
Misc
Partial Correction
08/31/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #15; #16; #17; #18; #19; #20;
Misc
Partial Correction
08/31/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST
Above Ceiling Inspection Partial 9/7/2017 at 11:10 AM 09/07/2017
Misc
Partial Correction
08/31/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C102; 104; 106; 107; C104 - C108; 111; 112; C115; 116; C118; C119; C121 - C129; 123; C131 - C134; C137 - C138; C140; C142 - C144; C146 - C149; C154 - C159; FOUR CLOUD CEILINGS AT AEROBICS 157; C163; SOFFITS AT 113 INCLUDING EAST 12' (RD PENETRATION OF RATED WALL AT SOUTH YET TO BE RESOLVED); SOFFITS AT 118; SOFFITS AT 126 EXCEPT S 10'; CEILING @ 129; 141; 147; 148; CORR 108; 109; REVISIONS @ 124; CORR 144; AV 110; WOMEN'S 143; CORR 116; MEN'S LOCKER 145 INCLUDING SOUTH SHOWER UNIT; PORTE COCHERE; 101 CEILING ONLY; SOFFITS AT N & S ENDS OF 102;
Underground Electrical Inspection - Commercial Partial 9/12/2017 at 1:05 PM 09/12/2017
Misc
Partial Correction
09/07/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #15; #16; #17; #18; #19; #20; #21; #22;
Misc
Partial Correction
09/07/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST
All Rough Inspection - Commercial Partial 9/12/2017 9/12/2017 at 1:25 PM 09/12/2017
Misc
Partial Correction
09/12/2017
OK TO COVER WHEN READY WALLS AND CEILINGS WITH 5/8" GWB AT SPACES: PUMP ROOMS 152 & 153;
Above Ceiling Inspection Partial 9/13/2017 9/13/2017 at 10:35 AM 09/13/2017
Misc
Partial Correction
09/07/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C102; 104; 106; 107; C104 - C108; 111; 112; C115; 116; C118; C119; C121 - C129; 123; C131 - C134; C137 - C138; C140; C142 - C144; C146 - C149; C154 - C159; FOUR CLOUD CEILINGS AT AEROBICS 157; C163; SOFFITS AT 113 INCLUDING EAST 12' (RD PENETRATION OF RATED WALL AT SOUTH YET TO BE RESOLVED); SOFFITS AT 118; SOFFITS AT 126 EXCEPT S 10'; CEILING @ 129; 141; 147; 148; CORR 108; 109; REVISIONS @ 124; CORR 144; AV 110; WOMEN'S 143; CORR 116; MEN'S LOCKER 145 INCLUDING SOUTH SHOWER UNIT; PORTE COCHERE; 101 CEILING ONLY; SOFFITS AT N & S ENDS OF 102;
Misc
Partial Correction
09/13/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 118; 119; 121; 122; 163;
Underground Electrical Inspection - Commercial Partial 9/14/2017 9/14/2017 at 9:20 AM 09/14/2017
Misc
Partial Correction
09/12/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #15; 16; 17; 18; 19; 20; 21; 22; [23; 24; 25; 26; 27;
Misc
Partial Correction
09/12/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST
Above Ceiling Inspection Partial 9/14/2017 9/14/2017 at 9:45 AM 09/14/2017
Misc
Partial Correction
09/13/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C102; 104; 106; 107; C104 - C108; 111; 112; C115; 116; C118; C119; C121 - C129; 123; C131 - C134; C137 - C138; C140; C142 - C144; C146 - C149; C154 - C159; FOUR CLOUD CEILINGS AT AEROBICS 157; C163; SOFFITS AT 113 INCLUDING EAST 12' (RD PENETRATION OF RATED WALL AT SOUTH YET TO BE RESOLVED); SOFFITS AT 118; SOFFITS AT 126 EXCEPT S 10'; CEILING @ 129; 141; 147; 148; CORR 108; 109; REVISIONS @ 124; CORR 144; AV 110; WOMEN'S 143; CORR 116; MEN'S LOCKER 145 INCLUDING SOUTH SHOWER UNIT; PORTE COCHERE; 101 CEILING ONLY; SOFFITS AT N & S ENDS OF 102;
Misc
Partial Correction
09/13/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 118; 119; 121; 122; 163; [104; 105; 148;
Above Ceiling Inspection Partial 9/15/2017 9/15/2017 at 8:05 AM 09/15/2017
Misc
Partial Correction
09/14/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C102; 104; 106; 107; C104 - C108; 111; 112; C115; 116; C118; C119; C121 - C129; 123; C131 - C134; C137 - C138; C140; C142 - C144; C146 - C149; C154 - C159; FOUR CLOUD CEILINGS AT AEROBICS 157; C163; SOFFITS AT 113 INCLUDING EAST 12' (RD PENETRATION OF RATED WALL AT SOUTH YET TO BE RESOLVED); SOFFITS AT 118; SOFFITS AT 126 EXCEPT S 10'; CEILING @ 129; 141; 147; 148; CORR 108; 109; REVISIONS @ 124; CORR 144; AV 110; WOMEN'S 143; CORR 116; MEN'S LOCKER 145 INCLUDING SOUTH SHOWER UNIT; PORTE COCHERE; 101 CEILING ONLY; SOFFITS AT N & S ENDS OF 102;
Misc
Partial Correction
09/14/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 118; 119; 121; 122; 163; [147; 158;
Gas Piping Inspection - Commercial Partial 9/15/2017 at 8:25 AM 09/15/2017
Misc
Partial Correction
07/27/2017
GAS FEEDER PIPE FROM DISTRIBUTION LINE AT OBRIEN RD TO S WALL OF BLDG HELD STEADY AT 95 PSI FOR >20 MINUTES. PIPE DEPTH IN TRENCH OK TO COVER WHEN READY.
Misc
Partial Correction
09/15/2017
PRESSURE TEST ON INTERIOR & ROOFTOP GAS PIPING HELD STEADY AT 30 PSI FOR >30 MINUTES. OK FOR USE CONTINENT ON INSPECTION/APPROVAL OF ROOFTOP PIPING.
Above Ceiling Inspection Partial 9/19/2017 9/19/2017 at 4:05 PM 09/19/2017
Misc
Partial Correction
09/14/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C102; 104; 106; 107; C104 - C108; 111; 112; C115; 116; C118; C119; C121 - C129; 123; C131 - C134; C137 - C138; C140; C142 - C144; C146 - C149; C154 - C159; FOUR CLOUD CEILINGS AT AEROBICS 157; C163; SOFFITS AT 113 INCLUDING EAST 12' (RD PENETRATION OF RATED WALL AT SOUTH YET TO BE RESOLVED); SOFFITS AT 118; SOFFITS AT 126 EXCEPT S 10'; CEILING @ 129; 141; 147; 148; CORR 108; 109; REVISIONS @ 124; CORR 144; AV 110; WOMEN'S 143; CORR 116; MEN'S LOCKER 145 INCLUDING SOUTH SHOWER UNIT; PORTE COCHERE; 101 CEILING ONLY; SOFFITS AT N & S ENDS OF 102;
Misc
Partial Correction
09/14/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 104; 105; 118; 119; 121; 122; 148; 163; [136; 137; 138; 141; 143; 145; 146;
Above Ceiling Inspection Partial 9/20/2017 9/20/2017 at 3:25 PM 09/20/2017
Misc
Partial Correction
09/19/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C102; 104; 106; 107; C104 - C108; 111; 112; C115; 116; C118; C119; C121 - C129; 123; C131 - C134; C137 - C138; C140; C142 - C144; C146 - C149; C154 - C159; FOUR CLOUD CEILINGS AT AEROBICS 157; C163; SOFFITS AT 113 INCLUDING EAST 12' (RD PENETRATION OF RATED WALL AT SOUTH YET TO BE RESOLVED); SOFFITS AT 118; SOFFITS AT 126 EXCEPT S 10'; CEILING @ 129; 141; 147; 148; CORR 108; 109; REVISIONS @ 124; CORR 144; AV 110; WOMEN'S 143; CORR 116; MEN'S LOCKER 145 INCLUDING SOUTH SHOWER UNIT; PORTE COCHERE; 101 CEILING ONLY; SOFFITS AT N & S ENDS OF 102; SOUTH PATIO; 101;
Misc
Partial Correction
09/19/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 104; 105; 118; 119; 121; 122; 148; 163; [136; 137; 138; 141; 143; 145; 146; 157 EXCEPT 4' AT N WALL;
Above Ceiling Inspection Partial 9/22/2017 9/22/2017 at 2:25 PM 09/22/2017
Misc
Partial Correction
09/20/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C102; 104; 106; 107; C104 - C108; 111; 112; C115; 116; C118; C119; C121 - C129; 123; C131 - C134; C137 - C138; C140; C142 - C144; C146 - C149; C154 - C159; FOUR CLOUD CEILINGS AT AEROBICS 157; C163; SOFFITS AT 113 INCLUDING EAST 12' (RD PENETRATION OF RATED WALL AT SOUTH YET TO BE RESOLVED); SOFFITS AT 118; SOFFITS AT 126 EXCEPT S 10'; CEILING @ 129; 141; 147; 148; CORR 108; 109; REVISIONS @ 124; CORR 144; AV 110; WOMEN'S 143; CORR 116; MEN'S LOCKER 145 INCLUDING SOUTH SHOWER UNIT; PORTE COCHERE; 101 CEILING ONLY; SOFFITS AT N & S ENDS OF 102; SOUTH PATIO; 101;
Misc
Partial Correction
09/20/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 104; 105; 118; 119; 121; 122; 136; 137; 138; 141; 143; 145; 146; 148; 157 EXCEPT 4' AT N WALL; 163; [113; 125 EXCEPT E 4'; 126;
Gas Piping Inspection - Commercial Partial 9/25/2017 9/25/2017 at 9:40 AM 09/25/2017
Misc
Partial Correction
09/15/2017
GAS FEEDER PIPE FROM DISTRIBUTION LINE AT OBRIEN RD TO S WALL OF BLDG HELD STEADY AT 95 PSI FOR >20 MINUTES. PIPE DEPTH IN TRENCH OK TO COVER WHEN READY. GAS LINE FROM NW CORNER OF POOL TO FIREPLACE AND GRILLE LOCATIONS: DEPTH APPROVED; PRESSURE TEST HELD STEADY AT 31 PSI FOR >20 MINUTES. OK TO COVER & USE.
Misc
Partial Correction
09/15/2017
PRESSURE TEST ON INTERIOR & ROOFTOP GAS PIPING HELD STEADY AT 30 PSI FOR >30 MINUTES. OK FOR USE CONTINGENT ON INSPECTION/APPROVAL OF ROOFTOP PIPING.
Underground Electrical Inspection - Commercial Partial 9/20/2017 at 3:10 PM 09/25/2017
Misc
Partial Correction
09/14/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #15; 16; 17; 18; 19; 20; 21; 22; 23; 24; 25; 26; 27;
Misc
Partial Correction
09/14/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER;
Underground Electrical Inspection - Commercial Partial 9/25/2017 at 9:55 AM 09/25/2017
Misc
Partial Correction
09/25/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #15; 16; 17; 18; 19; 20; 21; 22; 23; 24; 25; 26; 27;
Misc
Partial Correction
09/25/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B";
Miscellaneous Inspection Passed 9/26/2017 9/26/2017 at 10:10 AM 09/26/2017
Underground Electrical Inspection - Commercial Partial 9/27/2017 at 8:30 AM 09/27/2017
Misc
Partial Correction
09/25/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #15; 16; 17; 18; 19; 20; 21; 22; 23; 24; 25; 26; 27; D1; D3;
Misc
Partial Correction
09/25/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B";
Above Ceiling Inspection Passed 9/27/2017 9/27/2017 at 1:20 PM 09/27/2017
Misc
Resolved
09/27/2017
OK TO COVER WHEN READY GWB CEILING / SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: C102; 104; 106; 107; C104 - C108; 111; 112; C115; 116; C118; C119; C121 - C129; 123; C131 - C134; C137 - C138; C140; C142 - C144; C146 - C149; C154 - C159; FOUR CLOUD CEILINGS AT AEROBICS 157; C163; SOFFITS AT 113 INCLUDING EAST 12' (RD PENETRATION OF RATED WALL AT SOUTH YET TO BE RESOLVED); SOFFITS AT 118; SOFFITS AT 126 EXCEPT S 10'; CEILING @ 129; 141; 147; 148; CORR 108; 109; REVISIONS @ 124; CORR 144; AV 110; WOMEN'S 143; CORR 116; MEN'S LOCKER 145 INCLUDING SOUTH SHOWER UNIT; PORTE COCHERE; 101 CEILING ONLY; SOFFITS AT N & S ENDS OF 102; SOUTH PATIO; 101;
Misc
Resolved
09/27/2017
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 104; 105; 118; 119; 121; 122; 136; 137; 138; 141; 143; 145; 146; 148; 157 EXCEPT 4' AT N WALL; 163; [113; 125 EXCEPT E 4'; 126;
Underground Electrical Inspection - Commercial Partial 9/28/2017 9/28/2017 at 10:15 AM 09/28/2017
Misc
Partial Correction
09/27/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #15; 16; 17; 18; 19; 20; 21; 22; 23; 24; 25; 26; 27; D1; D3; D4
Misc
Partial Correction
09/27/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B"; ONE 1" PVC FROM INSIDE-CORNER OF PATIO TO WEST OF POOL BLDG, EAST ALONG NORTH SIDE OF PATIO; ONE 1" PVC FROM NORTH SIDE OF COMMONS PATIO TO EAST SIDE OF FIREPIT; FROM NORTH SIDE OF PATIO TO NORTH, AROUND CORNER OF FIREPIT, THEN WEST TO L.P. #D5;
Alarm Test Passed 9/28/2017 09/28/2017
Alternate Protection Systems Inspection Passed 9/28/2017 09/28/2017
Sprinkler - Flow Test Passed 9/28/2017 09/28/2017
Occupancy Inspection - Codes Commercial Not Ready 9/29/2017 9/29/2017 at 10:00 AM 09/29/2017
Misc
Partial Correction
08/30/2017
NOT READY FOR INSPECTION. TOO MANY INCOMPLETE ITEMS. MENTIONED TO THE CONTRACTOR, THE SIDES NEXT TO URINALS NEED TO BE A NON-ABSORBANT SURFACE. TIGHTEN RECEPTACLES, UNCOVER SPRINKLER HEADS, COMPLETE BONDING OF ALL METAL PARTS AND PUMPS AT POOL, EXIT SIGNS NEED TO BE FUNCTIONAL.
Occupancy Inspection - Fire Not Ready 9/29/2017 09/29/2017
Occupancy Inspection - Codes Commercial Not Ready 10/2/2017 10/2/2017 at 10:05 AM 10/02/2017
Misc
Partial Correction
09/29/2017
NOT READY FOR INSPECTION. TOO MANY INCOMPLETE ITEMS. MENTIONED TO THE CONTRACTOR, THE SIDES NEXT TO URINALS NEED TO BE A NON-ABSORBANT SURFACE. TIGHTEN RECEPTACLES, UNCOVER SPRINKLER HEADS, COMPLETE BONDING OF ALL METAL PARTS AND PUMPS AT POOL, ALL CIRCUITS AVAILABLE FOR TESTS, EXIT HARDWARE IN KITCHEN, TERMINATING ELEC IN J BOX,
Occupancy Inspection - Fire Not Ready 10/2/2017 10/02/2017
Occupancy Inspection - Fire Temporary C of O 10/3/2017 10/03/2017
Underground Electrical Inspection - Commercial Partial 10/4/2017 10/4/2017 at 8:10 AM 10/04/2017
Misc
Partial Correction
09/28/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #15; 16; 17; 18; 19; 20; 21; 22; 23; 24; 25; 26; 27; D1; D3; D4; D5; D6
Misc
Partial Correction
09/28/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B"; ONE 1" PVC FROM INSIDE-CORNER OF PATIO TO WEST OF POOL BLDG, EAST ALONG NORTH SIDE OF PATIO; ONE 1" PVC FROM NORTH SIDE OF COMMONS PATIO TO EAST SIDE OF FIREPIT; FROM NORTH SIDE OF PATIO TO NORTH, AROUND CORNER OF FIREPIT, THEN WEST TO L.P. #D5;
Underground Electrical Inspection - Commercial Partial 10/16/2017 10/16/2017 at 4:15 PM 10/16/2017
Misc
Partial Correction
10/16/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #27; D1; D3; D4; D5; D6;
Misc
Partial Correction
10/16/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B"; ONE 1" PVC FROM INSIDE-CORNER OF PATIO TO WEST OF POOL BLDG, EAST ALONG NORTH SIDE OF PATIO; ONE 1" PVC FROM NORTH SIDE OF COMMONS PATIO TO EAST SIDE OF FIREPIT; FROM NORTH SIDE OF PATIO TO NORTH, AROUND CORNER OF FIREPIT, THEN WEST TO L.P. #D5;
Electrical Service Inspection Partial 10/16/2017 at 4:40 PM 10/16/2017
Occupancy Inspection - Water Utilities Passed 10/17/2017
Underground Electrical Inspection - Commercial Partial 10/17/2017 at 3:40 PM 10/17/2017
Misc
Partial Correction
10/16/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #35;
Misc
Partial Correction
10/16/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B"; ONE 1" PVC FROM INSIDE-CORNER OF PATIO TO WEST OF POOL BLDG, EAST ALONG NORTH SIDE OF PATIO; ONE 1" PVC FROM NORTH SIDE OF COMMONS PATIO TO EAST SIDE OF FIREPIT; FROM NORTH SIDE OF PATIO TO NORTH, AROUND CORNER OF FIREPIT, THEN WEST TO L.P. #D5;
Underground Electrical Inspection - Commercial Partial 10/19/2017 10/19/2017 at 7:05 AM 10/19/2017
Misc
Partial Correction
10/17/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #35; [36-39:
Misc
Partial Correction
10/17/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B"; ONE 1" PVC FROM INSIDE-CORNER OF PATIO TO WEST OF POOL BLDG, EAST ALONG NORTH SIDE OF PATIO; ONE 1" PVC FROM NORTH SIDE OF COMMONS PATIO TO EAST SIDE OF FIREPIT; FROM NORTH SIDE OF PATIO TO NORTH, AROUND CORNER OF FIREPIT, THEN WEST TO L.P. #D5;
Electrical Service Inspection Partial 10/19/2017 at 2:35 PM 10/19/2017
Misc
Partial Correction
10/19/2017
PEDESTAL ELECTRICAL SERVICES FOR PARKING LOT LIGHTING CONTROL PANELS: - RELEASE 1800-LC1 - RELEASE 1800-LC2
Underground Electrical Inspection - Commercial Partial 10/25/2017 10/24/2017 at 1:20 PM 10/24/2017
Misc
Partial Correction
10/19/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #41;
Misc
Partial Correction
10/19/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B"; ONE 1" PVC FROM INSIDE-CORNER OF PATIO TO WEST OF POOL BLDG, EAST ALONG NORTH SIDE OF PATIO; ONE 1" PVC FROM NORTH SIDE OF COMMONS PATIO TO EAST SIDE OF FIREPIT; FROM NORTH SIDE OF PATIO TO NORTH, AROUND CORNER OF FIREPIT, THEN WEST TO L.P. #D5; FROM #36 TO 37 TO 38 TO BOLLARD #42;
Occupancy Inspection - Fire Passed 10/24/2017 10/24/2017
Underground Electrical Inspection - Commercial Partial 10/25/2017 at 1:00 PM 10/25/2017
Misc
Partial Correction
10/24/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #41;
Misc
Partial Correction
10/24/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B"; ONE 1" PVC FROM INSIDE-CORNER OF PATIO TO WEST OF POOL BLDG, EAST ALONG NORTH SIDE OF PATIO; ONE 1" PVC FROM NORTH SIDE OF COMMONS PATIO TO EAST SIDE OF FIREPIT; FROM NORTH SIDE OF PATIO TO NORTH, AROUND CORNER OF FIREPIT, THEN WEST TO L.P. #D5; FROM #36 TO 37 TO 38 TO BOLLARD #43; 28 to 36; BOLL 44 TO LP 34; 42 TO 30' SE;
Underground Electrical Inspection - Commercial Partial 10/26/2017 at 3:15 PM 10/26/2017
Misc
Partial Correction
10/25/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #41;
Misc
Partial Correction
10/25/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B"; ONE 1" PVC FROM INSIDE-CORNER OF PATIO TO WEST OF POOL BLDG, EAST ALONG NORTH SIDE OF PATIO; ONE 1" PVC FROM NORTH SIDE OF COMMONS PATIO TO EAST SIDE OF FIREPIT; FROM NORTH SIDE OF PATIO TO NORTH, AROUND CORNER OF FIREPIT, THEN WEST TO L.P. #D5; FROM #36 TO 37 TO 38 TO BOLLARD #43; 28 to 36; BOLL 44 TO LP 34; 42 TO 30' SE; L.P. 34 TO 35 TO 41 TO 40 TO 29;
Underground Electrical Inspection - Commercial Partial 10/27/2017 10/27/2017 at 10:25 AM 10/27/2017
Misc
Partial Correction
10/26/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #41;
Misc
Partial Correction
10/26/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B"; ONE 1" PVC FROM INSIDE-CORNER OF PATIO TO WEST OF POOL BLDG, EAST ALONG NORTH SIDE OF PATIO; ONE 1" PVC FROM NORTH SIDE OF COMMONS PATIO TO EAST SIDE OF FIREPIT; FROM NORTH SIDE OF PATIO TO NORTH, AROUND CORNER OF FIREPIT, THEN WEST TO L.P. #D5; FROM #36 TO 37 TO 38 TO BOLLARD #43; 28 to 36; BOLL 44 TO LP 34; 42 TO 30' SE; L.P. 34 TO 35 TO 41 TO 40 TO 29; 28 TO TO 29;
Underground Electrical Inspection - Commercial Partial 11/7/2017 at 1:10 PM 11/07/2017
Misc
Partial Correction
10/27/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #49;
Misc
Partial Correction
10/27/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B"; ONE 1" PVC FROM INSIDE-CORNER OF PATIO TO WEST OF POOL BLDG, EAST ALONG NORTH SIDE OF PATIO; ONE 1" PVC FROM NORTH SIDE OF COMMONS PATIO TO EAST SIDE OF FIREPIT; FROM NORTH SIDE OF PATIO TO NORTH, AROUND CORNER OF FIREPIT, THEN WEST TO L.P. #D5; FROM #36 TO 37 TO 38 TO BOLLARD #43; 28 to 36; BOLL 44 TO LP 34; 42 TO 30' SE; L.P. 34 TO 35 TO 41 TO 40 TO 29; 28 TO 29;
Underground Electrical Inspection - Commercial Partial 11/8/2017 at 10:00 AM 11/08/2017
Misc
Partial Correction
11/07/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #49;
Misc
Partial Correction
11/07/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B"; ONE 1" PVC FROM INSIDE-CORNER OF PATIO TO WEST OF POOL BLDG, EAST ALONG NORTH SIDE OF PATIO; ONE 1" PVC FROM NORTH SIDE OF COMMONS PATIO TO EAST SIDE OF FIREPIT; FROM NORTH SIDE OF PATIO TO NORTH, AROUND CORNER OF FIREPIT, THEN WEST TO L.P. #D5; FROM #36 TO 37 TO 38 TO BOLLARD #43; 28 to 36; BOLL 44 TO LP 34; 42 TO 30' SE; L.P. 34 TO 35 TO 41 TO 40 TO 29; 28 TO 29; [FROM 45 TO 20' NW;
Underground Electrical Inspection - Commercial Partial 11/8/2017 11/8/2017 at 1:00 PM 11/08/2017
Misc
Partial Correction
11/08/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #49;
Misc
Partial Correction
11/08/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B"; ONE 1" PVC FROM INSIDE-CORNER OF PATIO TO WEST OF POOL BLDG, EAST ALONG NORTH SIDE OF PATIO; ONE 1" PVC FROM NORTH SIDE OF COMMONS PATIO TO EAST SIDE OF FIREPIT; FROM NORTH SIDE OF PATIO TO NORTH, AROUND CORNER OF FIREPIT, THEN WEST TO L.P. #D5; FROM #36 TO 37 TO 38 TO BOLLARD #43; 28 to 36; BOLL 44 TO LP 34; 42 TO 30' SE; L.P. 34 TO 35 TO 41 TO 40 TO 29; 28 TO 29; FROM 45 TO 20' NW; [FROM 50 TO 51 AND TO 52;
Underground Electrical Inspection - Commercial Not Ready 11/14/2017 11/14/2017 at 1:55 PM 11/14/2017
Misc
Partial Correction
11/08/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #49;
Misc
Partial Correction
11/08/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B"; ONE 1" PVC FROM INSIDE-CORNER OF PATIO TO WEST OF POOL BLDG, EAST ALONG NORTH SIDE OF PATIO; ONE 1" PVC FROM NORTH SIDE OF COMMONS PATIO TO EAST SIDE OF FIREPIT; FROM NORTH SIDE OF PATIO TO NORTH, AROUND CORNER OF FIREPIT, THEN WEST TO L.P. #D5; FROM #36 TO 37 TO 38 TO BOLLARD #43; 28 to 36; BOLL 44 TO LP 34; 42 TO 30' SE; L.P. 34 TO 35 TO 41 TO 40 TO 29; 28 TO 29; FROM 45 TO 20' NW; [FROM 50 TO 51 AND TO 52;
Underground Electrical Inspection - Commercial Partial 11/16/2017 11/16/2017 at 8:15 AM 11/16/2017
Misc
Partial Correction
11/14/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #49;
Misc
Partial Correction
11/14/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B"; ONE 1" PVC FROM INSIDE-CORNER OF PATIO TO WEST OF POOL BLDG, EAST ALONG NORTH SIDE OF PATIO; ONE 1" PVC FROM NORTH SIDE OF COMMONS PATIO TO EAST SIDE OF FIREPIT; FROM NORTH SIDE OF PATIO TO NORTH, AROUND CORNER OF FIREPIT, THEN WEST TO L.P. #D5; FROM #36 TO 37 TO 38 TO BOLLARD #43; 28 to 36; BOLL 44 TO LP 34; 42 TO 30' SE; L.P. 34 TO 35 TO 41 TO 40 TO 29; 28 TO 29; FROM 45 TO 20' NW; FROM 50 TO 51 AND TO 52; FROM 45 TO 46 TO 47 TO 48 TO 49;
Underground Electrical Inspection - Commercial Partial 11/16/2017 11/16/2017 at 10:55 AM 11/16/2017
Misc
Partial Correction
11/16/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #49;
Misc
Partial Correction
11/16/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B"; ONE 1" PVC FROM INSIDE-CORNER OF PATIO TO WEST OF POOL BLDG, EAST ALONG NORTH SIDE OF PATIO; ONE 1" PVC FROM NORTH SIDE OF COMMONS PATIO TO EAST SIDE OF FIREPIT; FROM NORTH SIDE OF PATIO TO NORTH, AROUND CORNER OF FIREPIT, THEN WEST TO L.P. #D5; FROM #36 TO 37 TO 38 TO BOLLARD #43; 28 to 36; BOLL 44 TO LP 34; 42 TO 30' SE; L.P. 34 TO 35 TO 41 TO 40 TO 29; 28 TO 29; FROM 45 TO 20' NW; FROM 50 TO 51 AND TO 52; FROM 45 TO 46 TO 47 TO 48 TO 49; [FROM 52 TO A TO B TO C TO 53; FROM D TO E;
Underground Electrical Inspection - Commercial Partial 11/20/2017 at 1:25 PM 11/20/2017
Misc
Partial Correction
11/16/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #49;
Misc
Partial Correction
11/16/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B"; ONE 1" PVC FROM INSIDE-CORNER OF PATIO TO WEST OF POOL BLDG, EAST ALONG NORTH SIDE OF PATIO; ONE 1" PVC FROM NORTH SIDE OF COMMONS PATIO TO EAST SIDE OF FIREPIT; FROM NORTH SIDE OF PATIO TO NORTH, AROUND CORNER OF FIREPIT, THEN WEST TO L.P. #D5; FROM #36 TO 37 TO 38 TO BOLLARD #43; 28 to 36; BOLL 44 TO LP 34; 42 TO 30' SE; L.P. 34 TO 35 TO 41 TO 40 TO 29; 28 TO 29; FROM 45 TO 20' NW; FROM 50 TO 51 AND TO 52; FROM 45 TO 46 TO 47 TO 48 TO 49; [FROM 52 TO A TO B TO C TO 53; FROM D TO E; [FROM E TO 40' EAST;
Underground Electrical Inspection - Commercial Partial 11/21/2017 at 10:40 AM 11/21/2017
Misc
Partial Correction
11/20/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #53; [54;
Misc
Partial Correction
11/20/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B"; ONE 1" PVC FROM INSIDE-CORNER OF PATIO TO WEST OF POOL BLDG, EAST ALONG NORTH SIDE OF PATIO; ONE 1" PVC FROM NORTH SIDE OF COMMONS PATIO TO EAST SIDE OF FIREPIT; FROM NORTH SIDE OF PATIO TO NORTH, AROUND CORNER OF FIREPIT, THEN WEST TO L.P. #D5; FROM #36 TO 37 TO 38 TO BOLLARD #43; 28 to 36; BOLL 44 TO LP 34; 42 TO 30' SE; L.P. 34 TO 35 TO 41 TO 40 TO 29; 28 TO 29; FROM 45 TO 20' NW; FROM 50 TO 51 AND TO 52; FROM 45 TO 46 TO 47 TO 48 TO 49; [FROM 52 TO A TO B TO C TO 53; FROM D TO E; FROM E TO 40' EAST; [FROM 27 E TO TWO BL1s; FROM 49 TO 54 W TO BL1;
Underground Electrical Inspection - Commercial Partial 11/22/2017 11/22/2017 at 8:25 AM 11/22/2017
Misc
Partial Correction
11/21/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #53; 54;
Misc
Partial Correction
11/21/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B"; ONE 1" PVC FROM INSIDE-CORNER OF PATIO TO WEST OF POOL BLDG, EAST ALONG NORTH SIDE OF PATIO; ONE 1" PVC FROM NORTH SIDE OF COMMONS PATIO TO EAST SIDE OF FIREPIT; FROM NORTH SIDE OF PATIO TO NORTH, AROUND CORNER OF FIREPIT, THEN WEST TO L.P. #D5; FROM #36 TO 37 TO 38 TO BOLLARD #43; 28 to 36; BOLL 44 TO LP 34; 42 TO 30' SE; L.P. 34 TO 35 TO 41 TO 40 TO 29; 28 TO 29; FROM 45 TO 20' NW; FROM 50 TO 51 AND TO 52; FROM 45 TO 46 TO 47 TO 48 TO 49; [FROM 52 TO A TO B TO C TO 53; FROM D TO E; FROM E TO 40' EAST; [FROM 27 E TO TWO BL1s; FROM 49 TO 54 W TO BL1; [FROM TWO BOLLARD LIGHTS AT 55 EAST TO BLDG;
Underground Electrical Inspection - Commercial Partial 11/30/2017 at 3:30 PM 11/30/2017
Misc
Resolved
11/30/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #1 THRU #53; 54;
Misc
Partial Correction
11/22/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B"; ONE 1" PVC FROM INSIDE-CORNER OF PATIO TO WEST OF POOL BLDG, EAST ALONG NORTH SIDE OF PATIO; ONE 1" PVC FROM NORTH SIDE OF COMMONS PATIO TO EAST SIDE OF FIREPIT; FROM NORTH SIDE OF PATIO TO NORTH, AROUND CORNER OF FIREPIT, THEN WEST TO L.P. #D5; FROM #36 TO 37 TO 38 TO BOLLARD #43; 28 to 36; BOLL 44 TO LP 34; 42 TO 30' SE; L.P. 34 TO 35 TO 41 TO 40 TO 29; 28 TO 29; FROM 45 TO 20' NW; FROM 50 TO 51 AND TO 52; FROM 45 TO 46 TO 47 TO 48 TO 49; [FROM 52 TO A TO B TO C TO 53; FROM D TO E; FROM E TO 40' EAST; [FROM 27 E TO TWO BL1s; FROM 49 TO 54 W TO BL1; FROM TWO BOLLARD LIGHTS AT 55 EAST TO BLDG; CONDUIT BORED FROM LC3 LOCATION AT (56) TO QUAZITE BOX AT (57);
Occupancy Inspection - Codes Commercial Temporary C of O 12/14/2017 12/14/2017 at 3:30 PM 12/14/2017
Misc
Corrective Action Required
12/14/2017
POOL BONDING FOR LADDER NEEDS TO BE INSPECTED
Misc
Corrective Action Required
12/14/2017
LADDER EXTENSIONS REQUIRED TO PROJECT >=30" ABOVE HATCH.
Misc
Corrective Action Required
12/14/2017
PAINT ALL ROOFTOP BLACK IRON GAS PIPE 100% INCLUDING AT SUPPORT BLOCK CLAMPS AND AT ENTRY TO UNITS.
Misc
Corrective Action Required
12/14/2017
ENSURE AT LEAST ONE GFCI ELECTRICAL RECEPTACLE WITH IN-USE COVER WITHIN 25' OF EVERY ROOFTOP MECHANICAL UNIT.
Misc
Corrective Action Required
12/14/2017
AFFIX PERMANENT NUMBERS TO ALL ROOFTOP MECHANICAL UNITS AND CORRECTLY REFLECT UNIT NUMBERS IN ELECTRICAL PANELS.
Misc
Corrective Action Required
12/14/2017
IFGC 408 GAS PIPING DRIP/DIRT LEG: MUST BE AT ELEVATION TO HAVE CAP REMOVED FOR CLEANING AND REPLACED. BOTTOM OF CAP TO BE NO CLOSER TO ROOF THAN DEPTH OF CAP + 1/4".
Misc
Corrective Action Required
12/14/2017
ENSURE ALL EXPOSED ROOFTOP REFRIGERANT PIPING IS COMPLETELY INSULATED, AND THAT ALL INSULATION IS COMPLETELY SECURED TO PIPE/TUBE.
Misc
Corrective Action Required
12/14/2017
PROPERLY SEAL DUCT PENETRATIONS OF STRUCTURE (WALLS) AGAINST WEATHER, RODENTS, INSECTS, ETC.
All Rough Inspection - Commercial Passed 9/12/2017 12/19/2017
Misc
Resolved
12/19/2017
OK TO COVER WHEN READY WALLS AND CEILINGS WITH 5/8" GWB AT SPACES: PUMP ROOMS 152 & 153;
Foundation Inspection - Commercial Passed 8/1/2017 12/19/2017
Misc
Resolved
12/19/2017
OK TO POUR WHEN READY: RADIUS FOUNDATION WALL AT POOL AREA NORTH; PLANTER CURB WALL; BASES FOR FIREPLACE & GRILL; TRELLIS PIERS;
Gas Piping Inspection - Commercial Passed 9/25/2017 12/19/2017
Misc
Resolved
12/19/2017
GAS FEEDER PIPE FROM DISTRIBUTION LINE AT OBRIEN RD TO S WALL OF BLDG HELD STEADY AT 95 PSI FOR >20 MINUTES. PIPE DEPTH IN TRENCH OK TO COVER WHEN READY. GAS LINE FROM NW CORNER OF POOL TO FIREPLACE AND GRILLE LOCATIONS: DEPTH APPROVED; PRESSURE TEST HELD STEADY AT 31 PSI FOR >20 MINUTES. OK TO COVER & USE.
Misc
Resolved
12/19/2017
PRESSURE TEST ON INTERIOR & ROOFTOP GAS PIPING HELD STEADY AT 30 PSI FOR >30 MINUTES. OK FOR USE CONTINGENT ON INSPECTION/APPROVAL OF ROOFTOP PIPING.
In-wall Inspection Passed 9/7/2017 8/31/2017 12/19/2017
Misc
Resolved
12/19/2017
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT: C104; 105; 106; 107; 108; 109; 110; 111; 112; 113; 115 PERIMETER + KNEE WALL AT BAR; 116; 117; 118; 119; 121; 123; 125; 127; 128; 129; 131; 132; 133; 134; 135; 136; 137; 138; 141; 142; 143; 144; 145; 146; 147; 148; 149; 154; 155; 156; 157; 158; 159; 161; 162; 163; [GREAT HALL 108 EAST AND WEST WALLS ONLY; FURRED WALLS AT PERIMETER OF POOL 151;
Pool Steel/Bonding - Commercial Passed 6/6/2017 12/19/2017
Misc
Resolved
12/19/2017
POOL SHELL RE-BAR BONDED TO PERIMETER BONDING RING WITH LEADS TO BEYOND SHELL POUR
Misc
Resolved
12/19/2017
POOL DECK REINFORCING MESH BONDED; READY FOR DECK POUR
Rated Assembly Inspection Passed 7/11/2017 12/19/2017
Misc
Resolved
12/19/2017
OK TO COVER WHEN READY COMPONENTS OF RATED WALL ASSEMBLIES: 104; 105; 106; 107; 108; 109; 110; 113; 117; 118; 119; 122; 127; 128; 135-138; 142; 143; 145; 147; 148; 157; 158; [154;
Misc
Resolved
12/19/2017
OK TO TAPE, MUD, & FIRE-STOP WHEN UL P522 RATED CEILING ASSEMBLIES AT SPACES: 104-108; 110; 113; 115; 117; 118; 121-123; 125-129; 132; 135; 136-138; 141- 144; 147; 148; 154-158; 159; 161; 162;
Misc
Resolved
12/19/2017
PP1 WALLS: SHAFT LINER LAYER APPROVED; OK TO APPLY 5/8" TYPE X AT OPPOSITE FACE AT C113 WEST & C157 EAST;
Rough Framing Inspection - Commercial Passed 5/10/2017 12/19/2017
Misc
Resolved
12/19/2017
EXTERIOR WALL SHEATHING: NAIL PATTERN SUBSTANTIALLY COMPLETED CORRECTLY; SOME AREAS POINTED OUT TO BE CHECKED AND CORRECTED AS NECESSARY
Misc
Resolved
12/19/2017
FRAMER TO INSTALL TRUSS WEB BRACING WHERE MISSING IN ADVANCE OF ABOVE-CEILING INSULATION INSTALLATION; ALSO AT DOUBLE TRUSSES BOTTOM CHORDS ARE TO BE FULLY NAILED TIGHT. THEN OK TO INSULATE AND INSTALL CEILING GWB.
Underground Electrical Inspection - Commercial Passed 11/30/2017 12/19/2017
Misc
Resolved
12/19/2017
OK TO COVER WHEN READY TRENCHED PVC CONDUIT: FROM L.P.#2 ONE 1" TO 80' WEST + ONE 3/4" TO 28' WEST CONN TO EXSTG; ONE 1" FROM PL#2 TO 45' NE FOR BL; ONE 1" ~80' ACROSS FRONT ENTRANCE FROM BL TO BL; ONE 3/4" FROM LP#7 ~110' NW FOR BL; ONE 1" FROM PL#7 NORTH 20' TO Q-BOX LOCATION; ONE 1" FROM Q-BOX LOCATION NW TO BL LOCATION EAST OF ENTRANCE CANOPY; GROUND ROD FOR LP#7 LAID IN CONDUIT TRENCH DUE TO ROCK CONDITIONS; FROM L.P.#10 TO #11 TO #12; #13 TO #9 TO #10; FROM #12 TO #14 TO #15; FROM #6 TO 15' WEST; 1" PVC FROM #17 TO 26 TO 25 TO 24 TO 23 TO 22 TO 21; TWO 1" FROM 29 WEST/NW TO PEDESTAL METER; ONE 1" PVC FROM NW CORNER OF POOL BLDG TO 100' WEST - FROM THIS POINT TO STUB-UP AT BUILDING A; FROM STUB-UP AT BUILDING A EAST TO BOLLARD LIGHT #D2; FROM BOLLARD LIGHT #D2 TO A POINT 20' TO THE NORTH; CONDUIT COMPLETE AND CONNECTED IN AREA OF SITE LIGHTING METER PEDESTAL, L.P. BASE AND QUAZITE BOX N OF BLDG "B"; ONE 1" PVC FROM INSIDE-CORNER OF PATIO TO WEST OF POOL BLDG, EAST ALONG NORTH SIDE OF PATIO; ONE 1" PVC FROM NORTH SIDE OF COMMONS PATIO TO EAST SIDE OF FIREPIT; FROM NORTH SIDE OF PATIO TO NORTH, AROUND CORNER OF FIREPIT, THEN WEST TO L.P. #D5; FROM #36 TO 37 TO 38 TO BOLLARD #43; 28 to 36; BOLL 44 TO LP 34; 42 TO 30' SE; L.P. 34 TO 35 TO 41 TO 40 TO 29; 28 TO 29; FROM 45 TO 20' NW; FROM 50 TO 51 AND TO 52; FROM 45 TO 46 TO 47 TO 48 TO 49; [FROM 52 TO A TO B TO C TO 53; FROM D TO E; FROM E TO 40' EAST; [FROM 27 E TO TWO BL1s; FROM 49 TO 54 W TO BL1; FROM TWO BOLLARD LIGHTS AT 55 EAST TO BLDG; CONDUIT BORED FROM LC3 LOCATION AT (56) TO QUAZITE BOX AT (57);
Underground Plumbing Inspection - Commercial Passed 3/21/2017 2/21/2017 12/19/2017
Misc
Resolved
12/19/2017
GREASE INTERCEPTOR SET AND PARTIALLY BACKFILLED WITH CRUSHER-RUN FINES. ANTI-BOUYANCY SLAB SAID NOT TO HAVE BEEN PLACED PER APPROVED DRAWING.
Hood/Duct Inspection Passed 12/28/2017 at 1:10 PM 12/28/2017
Misc
Resolved
12/28/2017
DUCT WRAP WAS COMPLETED WITHOUT INSPECTION OF FIRST LAYER. OUTER LAYER HAS BEEN PARTIALLY OPENED AT BOTTOM OF HORIZONTAL RUN TO EXPOSE FIRST LAYER.
Occupancy Inspection - Codes Commercial Not Ready 1/9/2018 at 1:15 PM 01/09/2018
Misc
Corrective Action Required
12/14/2017
POOL BONDING FOR LADDER NEEDS TO BE INSPECTED
Misc
Corrective Action Required
12/14/2017
LADDER EXTENSIONS REQUIRED TO PROJECT >=30" ABOVE HATCH.
Misc
Corrective Action Required
12/14/2017
PAINT ALL ROOFTOP BLACK IRON GAS PIPE 100% INCLUDING AT SUPPORT BLOCK CLAMPS AND AT ENTRY TO UNITS.
Misc
Corrective Action Required
12/14/2017
ENSURE AT LEAST ONE GFCI ELECTRICAL RECEPTACLE WITH IN-USE COVER WITHIN 25' OF EVERY ROOFTOP MECHANICAL UNIT.
Misc
Corrective Action Required
12/14/2017
AFFIX PERMANENT NUMBERS TO ALL ROOFTOP MECHANICAL UNITS AND CORRECTLY REFLECT UNIT NUMBERS IN ELECTRICAL PANELS.
Misc
Corrective Action Required
12/14/2017
IFGC 408 GAS PIPING DRIP/DIRT LEG: MUST BE AT ELEVATION TO HAVE CAP REMOVED FOR CLEANING AND REPLACED. BOTTOM OF CAP TO BE NO CLOSER TO ROOF THAN DEPTH OF CAP + 1/4".
Misc
Corrective Action Required
12/14/2017
ENSURE ALL EXPOSED ROOFTOP REFRIGERANT PIPING IS COMPLETELY INSULATED, AND THAT ALL INSULATION IS COMPLETELY SECURED TO PIPE/TUBE.
Misc
Corrective Action Required
12/14/2017
PROPERLY SEAL DUCT PENETRATIONS OF STRUCTURE (WALLS) AGAINST WEATHER, RODENTS, INSECTS, ETC.
Electrical Service Inspection Not Ready 1/22/2018 at 2:55 PM 01/22/2018
Misc
Partial Correction
01/22/2018
PEDESTAL ELECTRICAL SERVICES FOR PARKING LOT LIGHTING CONTROL PANELS: - RELEASE 1800-LC1 - RELEASE 1800-LC2
Misc
Corrective Action Required
01/22/2018
PEDESTAL FOR LC3 NOT LABELED
Electrical Service Inspection Not Ready 1/23/2018 01/23/2018
Misc
Partial Correction
01/22/2018
PEDESTAL ELECTRICAL SERVICES FOR PARKING LOT LIGHTING CONTROL PANELS: - RELEASE 1800-LC1 - RELEASE 1800-LC2
Misc
Corrective Action Required
01/22/2018
PEDESTAL FOR LC3 NOT LABELED
Electrical Service Inspection Passed 1/25/2018 at 11:45 AM 01/25/2018
Misc
Resolved
01/25/2018
PEDESTAL ELECTRICAL SERVICES FOR PARKING LOT LIGHTING CONTROL PANELS: - RELEASE 1800-LC1 - RELEASE 1800-LC2 - RELEASE 1800-LC3
Misc
Resolved
01/25/2018
PEDESTAL FOR LC3 NOT LABELED
Occupancy Inspection - Codes Commercial Temporary C of O 1/16/2018 1/26/2018 at 8:50 AM 01/26/2018
Misc
Corrective Action Required
01/09/2018
SECURE POOL EQUIPMENT BONDING CONDUCTOR TO WALLS OR OTHERWISE PROTECT FROM DAMAGE.
Misc
Corrective Action Required
01/09/2018
LADDER EXTENSIONS REQUIRED TO PROJECT >=30" ABOVE HATCH. LADDER TO BE INSTALLED AT ROOF ELEVATION TRANSITION PER DRAWING.
Misc
Corrective Action Required
01/09/2018
PAINT ALL ROOFTOP BLACK IRON GAS PIPE 100% INCLUDING AT SUPPORT BLOCK CLAMPS AND AT ENTRY TO UNITS.
Misc
Corrective Action Required
01/09/2018
ENSURE AT LEAST ONE GFCI ELECTRICAL RECEPTACLE WITH IN-USE COVER WITHIN 25' OF EVERY ROOFTOP MECHANICAL UNIT.
Misc
Corrective Action Required
01/09/2018
AFFIX PERMANENT NUMBERS TO ALL ROOFTOP MECHANICAL UNITS AND CORRECTLY REFLECT UNIT NUMBERS IN ELECTRICAL PANELS.
Misc
Corrective Action Required
01/09/2018
IFGC 408 GAS PIPING DRIP/DIRT LEG: MUST BE AT ELEVATION TO HAVE CAP REMOVED FOR CLEANING AND REPLACED. BOTTOM OF CAP TO BE NO CLOSER TO ROOF THAN DEPTH OF CAP + 1/4".
Misc
Corrective Action Required
01/09/2018
ENSURE ALL EXPOSED ROOFTOP REFRIGERANT PIPING IS COMPLETELY INSULATED, AND THAT ALL INSULATION IS COMPLETELY SECURED TO PIPE/TUBE.
Misc
Corrective Action Required
01/09/2018
PROPERLY SEAL DUCT PENETRATIONS OF STRUCTURE (WALLS) AGAINST WEATHER, RODENTS, INSECTS, ETC.
Occupancy Inspection - Codes Commercial Full C of O 2/12/2018 2/12/2018 at 9:50 AM 02/12/2018
Misc
Resolved
02/12/2018
SECURE POOL EQUIPMENT BONDING CONDUCTOR TO WALLS OR OTHERWISE PROTECT FROM DAMAGE.
Misc
Resolved
02/12/2018
LADDER EXTENSIONS REQUIRED TO PROJECT >=30" ABOVE HATCH. LADDER TO BE INSTALLED AT ROOF ELEVATION TRANSITION PER DRAWING.
Misc
Resolved
02/12/2018
PAINT ALL ROOFTOP BLACK IRON GAS PIPE 100% INCLUDING AT SUPPORT BLOCK CLAMPS AND AT ENTRY TO UNITS.
Misc
Resolved
02/12/2018
ENSURE AT LEAST ONE GFCI ELECTRICAL RECEPTACLE WITH IN-USE COVER WITHIN 25' OF EVERY ROOFTOP MECHANICAL UNIT.
Misc
Resolved
02/12/2018
AFFIX PERMANENT NUMBERS TO ALL ROOFTOP MECHANICAL UNITS AND CORRECTLY REFLECT UNIT NUMBERS IN ELECTRICAL PANELS.
Misc
Resolved
02/12/2018
IFGC 408 GAS PIPING DRIP/DIRT LEG: MUST BE AT ELEVATION TO HAVE CAP REMOVED FOR CLEANING AND REPLACED. BOTTOM OF CAP TO BE NO CLOSER TO ROOF THAN DEPTH OF CAP + 1/4".
Misc
Resolved
02/12/2018
ENSURE ALL EXPOSED ROOFTOP REFRIGERANT PIPING IS COMPLETELY INSULATED, AND THAT ALL INSULATION IS COMPLETELY SECURED TO PIPE/TUBE.
Misc
Resolved
02/12/2018
PROPERLY SEAL DUCT PENETRATIONS OF STRUCTURE (WALLS) AGAINST WEATHER, RODENTS, INSECTS, ETC.
Documents & Images
Date Uploaded File Type Document Name
06/02/2016 Letter Fire Building Plan Review
06/03/2016 Letter Codes P/R Corrections Document
06/21/2016 Letter Fire Building Plan Review
11/02/2016 CMU Product
11/22/2016 Receipt Receipt for transaction: 2016-006926
11/22/2016 Letter Codes Building Permit
11/22/2016 Letter Codes Plan Review Conditions
11/22/2016 Receipt Receipt for transaction: 2016-006927
11/29/2016 KTI - Meadows Agreement
12/02/2016 Letter Inspection Summary
12/08/2016 Letter Inspection Summary
12/12/2016 Letter Inspection Summary
12/16/2016 Letter Inspection Summary
01/03/2017 Letter Inspection Summary
01/17/2017 Letter Fire (Sprinkler) Plan Review
02/01/2017 Letter Inspection Summary
02/02/2017 Letter Inspection Summary
02/07/2017 Letter Inspection Summary
02/21/2017 Letter Inspection Summary
02/23/2017 Letter Inspection Summary
02/24/2017 Letter Inspection Summary
03/01/2017 Letter Inspection Summary
03/07/2017 Letter Fire (Alarm) Plan Review Notice
03/09/2017 Letter email
03/17/2017 Letter Inspection Summary
03/21/2017 Letter Inspection Summary
03/24/2017 Letter Inspection Summary
03/27/2017 Letter Fire (Alarm) Plan Review Notice
04/18/2017 Letter Inspection Summary
04/21/2017 Letter Inspection Summary
04/25/2017 Letter Inspection Summary
04/26/2017 Letter Inspection Summary
04/28/2017 Letter Inspection Summary
05/05/2017 Letter Inspection Summary
05/10/2017 Letter Inspection Summary
05/10/2017 Letter Inspection Summary
05/10/2017 Letter Inspection Summary
05/11/2017 Letter Inspection Summary
05/15/2017 Letter Inspection Summary
05/15/2017 Letter Inspection Summary
05/16/2017 Letter Inspection Summary
05/17/2017 Letter Inspection Summary
05/18/2017 Letter Inspection Summary
05/19/2017 Letter Inspection Summary
05/23/2017 Letter Inspection Summary
05/23/2017 Letter Inspection Summary
05/24/2017 Letter Inspection Summary
05/25/2017 Letter Inspection Summary
05/26/2017 Letter Inspection Summary
05/31/2017 Letter Inspection Summary
05/31/2017 Letter Inspection Summary
06/01/2017 Letter Inspection Summary
06/01/2017 Letter Inspection Summary
06/02/2017 Letter Inspection Summary
06/05/2017 Letter Inspection Summary
06/06/2017 Letter Inspection Summary
06/07/2017 Letter Inspection Summary
06/08/2017 Letter Inspection Summary
06/09/2017 Letter Inspection Summary
06/13/2017 Letter Inspection Summary
06/15/2017 Letter Inspection Summary
06/30/2017 13129.00 CCD 50 2017.06.27
06/30/2017 Letter Inspection Summary
07/11/2017 Letter Inspection Summary
07/14/2017 Letter Inspection Summary
07/20/2017 Letter Inspection Summary
07/24/2017 Letter Inspection Summary
07/24/2017 Letter Inspection Summary
07/26/2017 Letter Inspection Summary
07/27/2017 Letter Inspection Summary
07/28/2017 Letter Inspection Summary
08/01/2017 Letter Inspection Summary
08/03/2017 Letter Inspection Summary
08/04/2017 Letter Inspection Summary
08/08/2017 Letter Inspection Summary
08/18/2017 Letter Inspection Summary
08/22/2017 Letter Inspection Summary
08/24/2017 Letter Inspection Summary
08/31/2017 Letter Inspection Summary
09/07/2017 Letter Inspection Summary
09/12/2017 Letter Inspection Summary
09/13/2017 Letter Inspection Summary
09/14/2017 Letter Inspection Summary
09/15/2017 Letter Inspection Summary
09/19/2017 Letter Inspection Summary
09/20/2017 Letter Inspection Summary
09/22/2017 Letter Inspection Summary
09/25/2017 Letter Inspection Summary
09/27/2017 Letter Inspection Summary
09/27/2017 Letter Inspection Summary
09/28/2017 Letter Inspection Summary
09/29/2017 Letter Inspection Summary
10/03/2017 Letter Codes Temporary Certificate of Occupancy
10/19/2017 Letter Inspection Summary
10/24/2017 Letter Inspection Summary
10/25/2017 Letter Inspection Summary
10/26/2017 Letter Inspection Summary
10/27/2017 Letter Inspection Summary
11/07/2017 Letter Inspection Summary
11/08/2017 Letter Inspection Summary
11/08/2017 Letter Inspection Summary
11/16/2017 Letter Inspection Summary
11/16/2017 Letter Inspection Summary
11/20/2017 Letter Inspection Summary
11/21/2017 Letter Inspection Summary
11/22/2017 Letter Inspection Summary
11/30/2017 Letter Inspection Summary
12/14/2017 Letter Codes Temporary Certificate of Occupancy
12/28/2017 Letter Inspection Summary
01/02/2018 Engineer Report/Study Greenfield - John Knox Meadows Bldg
01/25/2018 Letter Inspection Summary
01/26/2018 Letter Codes Temporary Certificate of Occupancy
02/12/2018 Letter Field Certificate of Occupancy
02/13/2018 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home