Permit Application Status

PRCOM20161058


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20161058
Building Permit - Commercial
Certificate of Occupancy
THE CITY OF LEES SUMMIT
NEW COMMERCIAL
NEW WATER UTILITIES FACILTY
05/06/2016
09/01/2016
01/22/2017
02/06/2020
Locations
Contacts
FOGEL-ANDERSON CONSTRUCTION CO, Address:1212 E 8TH ST, Phone:(816) 842-6914  
ENVIRONMENTAL MECHANICAL CONTRACTORS , Address:14872 W 117TH ST, Phone:(913) 829-0100  
YATES ELECTRIC CO INC, Address:1401 BURLINGTON C, Phone:(816) 421-8343  
SHE DIGS IT LLC, Address:600 SE CENTRAL DR, Phone:(816) 295-1100  
HDR ENGINEERING, INC, Address:P O BOX 80600, Phone:(317) 596-3260  
TERRACON CONSULTANTS INC, Address:10841 S RIDGEVIEW ROAD, Phone:(913) 599-6886  
THE CITY OF LEES SUMMIT, Address:220 SE GREEN ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 01/18/2017
Joe Dir
Misc
Corrective Action Required
01/18/2017

PLANS SHOW THE FIRE DEPARTMENT CONNECTION AS A SIEMESE CONNECTION. FIRE DEPARTMENT CONNECTION SHALL BE A 4 INCH STORTZ FITTING WITH A 30 DEGREE ELBOW. MAKE THE NEEDED CORRECTIONS.
Installation acceptance testing
Corrective Action Required
01/18/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD AND ACCEPTANCE TESTS OF THE SYSTEM ARE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMEN AT 816-969-1300.
Alarm Plan Review Released for Construction 12/31/2016
Joe Dir
Installation acceptance testing
Corrective Action Required
08/29/2017

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: Acceptance testing of the system will be required prior to the final occupancy inspection. To schedule testing contact the fire department. 816-969-1300
Building Plan Review Approved 07/29/2016 08/30/2016
Joe Frogge
Final Development Plan
Resolved
08/24/2016

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Misc
Resolved
08/02/2016

Additional information required to complete review. Action required: Provide a letter describing intended use of kitchen. If used for other than warming puposes, a Type I hood and grease trap would be required as well as approval from Jackson County Health Department. 7/26/16 - not received 8/2/16 - letter provided. kitchen is for warming purposes only.
Misc
Resolved
08/30/2016

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections. 7/26/16 - not received 8/2/16 - Terracon listed but letter not received.
Accessibility - Water closet clearance width 604.3.1
Resolved
07/26/2016

ICC A117.1-2009 604.3.1 – Clearance width. Clearance around a water closet shall be 60 inches minimum in width, measured perpendicular from the sidewall. Action required: Provide required water closet clearance at Restroom 10-178. 7/26/16 - lav counter top shortened to comply
Accessibility - Dining surface height 902.4
Resolved
07/26/2016

ICC A117.1-2009 Section 902.4 Height. The tops of dining surfaces and work surfaces shall be 28 inches minimum and 34 inches maximum in height above the floor. Action required: Modify notes and details to demonstrate compliance at: - Printing 10-109 - Break Room 10-123 - Kitchen 10-125 - Kitchenette 10-157 7/26/16 - elevations updated to comply
Accessibility - Lavatory height 606.3
Resolved
07/26/2016

ICC A117.1-2009 606.3 – Height. The front of lavatories and sinks shall be 34 inches maximum above the floor, measured to the higher of the rim or counter surface. Action required: Modify notes and details to demonstrate compliance at Mothers Room 10-127 7/26/16 - elevations updated to comply
Mech - Equipment and appliances on roofs or elevated structures 306.5
Resolved
07/26/2016

2012 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. (see code section for specific construction requirements) Action required: Provide permanent ladder and access roof mounted equipment. 7/26/16 - ladder added to exterior
Misc
Resolved
08/02/2016

2012 IBC 406.8.2 Ventilation. Repair garages shall be mechanically ventilated in accordance with the International Mechanical Code. The ventilation system shall be controlled at the entrance to the garage. 2012 502.14 Motor vehicle operation. In areas where motor vehicles operate, mechanical ventilation shall be provided in accordance with Section 403. Additionally, areas in which stationary motor vehicles are operated shall be provided with a source capture system that connects directly to the motor vehicle exhaust systems. Exceptions: 1. This section shall not apply where the motor vehicles being operated or repaired are electrically powered. 2. This section shall not apply to one- and two-family dwellings. 3. This section shall not apply to motor vehicle service areas where engines are operated inside the building only for the duration necessary to move the motor vehicles in and out of the building. Action required: Specify controls for exhaust systems that demonstrate compliance. 7/26/16 - not found in submittal 8/2/16 - per architect, the bays are not for service.
Misc
Resolved
08/02/2016

2012 IBC 603.1 Allowable Materials. Combustible materials shall be permitted in buildings of Type I or II construction in the following applications and in accordance with Sections 603.1.1 through 603.1.3: (see code for specific examples and exceptions) Action required: Specify fire-retardant-treated lumber at roofing and parapet blocking. 7/26/16 - not found in submittal 8/2/16 - specifications revised to provide frt lumber
Bldg - Toilet room wall finish 1210.2.2
Resolved
08/02/2016

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: If paint is used in proximity to fixtures listed, it must be epoxy based. Modify finish schedule. 7/26/16 - not found in submittal
Mech - Duct detectors - Return air systems 606.2.1
Resolved
07/26/2016

2012 IMC 606.2.1 Return air systems. Smoke detectors shall be installed in return air systems with a design capacity greater than 2,000 cfm, in the return air duct or plenum upstream of any filters, exhaust air connections, outdoor air connections, or decontamination equipment and appliances. Exception: Smoke detectors are not required in the return air system where all portions of the building served by the air distribution system are protected by area smoke detectors connected to a fire alarm system in accordance with the International Fire Code. The area smoke detection system shall comply with Section 606.4. Action required: Provide duct mounted smoke detectors at required locations.
Misc
Resolved
07/26/2016

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within garage, service bays, kitchen, and covered parking areas will be GFCI protected.
Misc
Resolved
08/02/2016

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide roof mounted receptacle(s) to serve roof mounted equipment. 7/26/16 - not found in submittal 8/2/16 - clarified in letter
Misc
Resolved
08/02/2016

2011 NEC Article 500.1 Scope – Articles 500 Through 504. Articles 500 through 504 cover the requirements for electrical and electronic equipment and wiring for all voltages in Class I, Divisions 1 and 2; Class II, Divisions 1 and 2; and Class III, Divisions 1 and 2 locations where fire or explosion hazards may exist due to flammable gases, flammable liquid-produces vapors, combustible liquid-produced vapors, combustible liquid-produced vapors, combustible dusts, or ignitable fibers/flyings. (see code for additional information and specific requirements) Action required: Provide detailed electrical design at fuel tanks to demonstrate compliance. 7/26/16 - not found in submittal 8/2/16 - clarified in letter
Misc
Resolved
08/02/2016

2012 IMC 1302.1 General. Piping materials shall conform to the standards cited in this section. Action required: Provide pipe material schedule for fuel tank piping. 7/26/16 - not found in submittal 8/2/16 - clarified in letter
Special Inspections Review Approved 08/30/2016
Joe Frogge
Final Development Plan Review Approved 05/20/2016 08/24/2016
Joe Frogge
Licensed Contractors Approved 07/22/2016 08/02/2016
Joe Frogge
LC - General Contractor
Resolved
08/02/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Resolved
08/02/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 07/29/2016 07/26/2016
Joe Dir
07/26/2016

07/26/2016

07/26/2016

07/26/2016

07/26/2016

07/26/2016

Construction documents for fire alarm systems
Corrective Action Required
07/22/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS OF THE FIRE ALARM SYSTEM TO BE INSTALLED.
Knox box required
Corrective Action Required
07/22/2016

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. A KNOX BOX CAN BE OBTAINED ONLINE: knoxbox.com OR CONTACT THE FIRE DEPARTMENT AT 816-969-1300 KNOX BOX TO MOUNTED ON EXTERIOR WALL ABOVE THE FIRE DEPARTMENT CONNECTION WITH THE TOP OF THE KNOX BOX APPROX 6" OFF GROUND.
Locks on gates or barriers
Corrective Action Required
07/22/2016

2012 IFC 506.1.1-Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official. SUGGEST A KNOX KEY SWITCH FOR ANY GATES THAT MAY REQUIRED ACCESS BY THE FIRE DEPARTMENT. A KEY SWITHCH CAN BE OBTAIN ONLINE AT knoxbox.com OR CONTACT THE FIRE DEPARTMENT AT 816-969-1300.
Construction documents - Fire protection systems
Corrective Action Required
07/22/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS FOR THE FIRE SPRINKLER SYSTEM TO BE INSTALLED.
Installation acceptance testing
Corrective Action Required
07/22/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD TESTING AND ACCEPTANCE TESTS WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Misc
Corrective Action Required
07/22/2016

PROVIDE SPECS AND INFORMATION ABOUT THE GENERATOR, FUEL TYPE MAY REQUIRED NFPA 704 PLACARDS. NATURAL GAS POWERED WILL NOT REQUIRE PLACARDING.
Misc
Corrective Action Required
07/22/2016

LOCKS & HARDWARE: NO INFORMATION WAS GIVEN ABOUT LOCKS AND OR DOOR HARWARE TO BE USED. ANY LOCKS SHALL FALL UNDER THE FOLLOWING 2012IFC CONDITIONS. NO KEYED LOCKS ON THE EGRESS SIDE OF ANY MARKED EXIT. [B] 1008.1 Doors.Means of egress doors shall meet the requirements of this section. Doors serving a means of egress system shall meet the requirements of this section and Section 1020.2. Doors provided for egress purposes in numbers greater than required by this code shall meet the requirements of this section.
Building Plan Review Rejected 05/20/2016 05/17/2016
Joe Frogge
Final Development Plan
Corrective Action Required
05/17/2016

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
Misc
Corrective Action Required
05/17/2016

Additional information required to complete review. Action required: Provide a letter describing intended use of kitchen. If used for other than warming puposes, a Type I hood and grease trap would be required as well as approval from Jackson County Health Department.
Misc
Corrective Action Required
05/17/2016

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
Accessibility - Water closet clearance width 604.3.1
Corrective Action Required
05/17/2016

ICC A117.1-2009 604.3.1 – Clearance width. Clearance around a water closet shall be 60 inches minimum in width, measured perpendicular from the sidewall. Action required: Provide required water closet clearance at Restroom 10-178.
Accessibility - Dining surface height 902.4
Corrective Action Required
05/17/2016

ICC A117.1-2009 Section 902.4 Height. The tops of dining surfaces and work surfaces shall be 28 inches minimum and 34 inches maximum in height above the floor. Action required: Modify notes and details to demonstrate compliance at: - Printing 10-109 - Break Room 10-123 - Kitchen 10-125 - Kitchenette 10-157
Accessibility - Lavatory height 606.3
Corrective Action Required
05/17/2016

ICC A117.1-2009 606.3 – Height. The front of lavatories and sinks shall be 34 inches maximum above the floor, measured to the higher of the rim or counter surface. Action required: Modify notes and details to demonstrate compliance at Mothers Room 10-127
Mech - Equipment and appliances on roofs or elevated structures 306.5
Corrective Action Required
05/17/2016

2012 IMC 306.5 Equipment and appliances on roofs or elevated structures. Where equipment requiring access or appliances are located on an elevated structure or the roof of a building such that personnel will have to climb higher than 16 feet above grade to access such equipment or appliances, an interior or exterior means of access shall be provided. Such access shall not require climbing over obstructions greater than 30 inches in height or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Such access shall not require the use of portable ladders. Where access involves climbing over parapet walls, the height shall be measured to the top of the parapet wall. (see code section for specific construction requirements) Action required: Provide permanent ladder and access roof mounted equipment.
Misc
Corrective Action Required
05/17/2016

2012 IMC 406.8.2 Ventilation. Repair garages shall be mechanically ventilated in accordance with the International Mechanical Code. The ventilation system shall be controlled at the entrance to the garage. 2012 502.14 Motor vehicle operation. In areas where motor vehicles operate, mechanical ventilation shall be provided in accordance with Section 403. Additionally, areas in which stationary motor vehicles are operated shall be provided with a source capture system that connects directly to the motor vehicle exhaust systems. Exceptions: 1. This section shall not apply where the motor vehicles being operated or repaired are electrically powered. 2. This section shall not apply to one- and two-family dwellings. 3. This section shall not apply to motor vehicle service areas where engines are operated inside the building only for the duration necessary to move the motor vehicles in and out of the building. Action required: Specify controls for exhaust systems that demonstrate compliance.
Misc
Corrective Action Required
05/17/2016

2012 IBC 603.1 Allowable Materials. Combustible materials shall be permitted in buildings of Type I or II construction in the following applications and in accordance with Sections 603.1.1 through 603.1.3: (see code for specific examples and exceptions) Action required: Specify fire-retardant-treated lumber at roofing and parapet blocking.
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
05/17/2016

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: If paint is used in proximity to fixtures listed, it must be epoxy based. Modify finish schedule.
Mech - Duct detectors - Return air systems 606.2.1
Corrective Action Required
05/17/2016

2012 IMC 606.2.1 Return air systems. Smoke detectors shall be installed in return air systems with a design capacity greater than 2,000 cfm, in the return air duct or plenum upstream of any filters, exhaust air connections, outdoor air connections, or decontamination equipment and appliances. Exception: Smoke detectors are not required in the return air system where all portions of the building served by the air distribution system are protected by area smoke detectors connected to a fire alarm system in accordance with the International Fire Code. The area smoke detection system shall comply with Section 606.4. Action required: Provide duct mounted smoke detectors at required locations.
Misc
Corrective Action Required
05/17/2016

2011 NEC 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (8) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting equipment are to be used. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within garage, service bays, kitchen, and covered parking areas will be GFCI protected.
Misc
Corrective Action Required
05/17/2016

2011 NEC 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide roof mounted receptacle(s) to serve roof mounted equipment.
Misc
Corrective Action Required
05/17/2016

2011 NEC Article 500.1 Scope – Articles 500 Through 504. Articles 500 through 504 cover the requirements for electrical and electronic equipment and wiring for all voltages in Class I, Divisions 1 and 2; Class II, Divisions 1 and 2; and Class III, Divisions 1 and 2 locations where fire or explosion hazards may exist due to flammable gases, flammable liquid-produces vapors, combustible liquid-produced vapors, combustible liquid-produced vapors, combustible dusts, or ignitable fibers/flyings. (see code for additional information and specific requirements) Action required: Provide detailed electrical design at fuel tanks to demonstrate compliance.
Misc
Corrective Action Required
05/17/2016

2012 IMC 1302.1 General. Piping materials shall conform to the standards cited in this section. Action required: Provide pipe material schedule for fuel tank piping.
Licensed Contractors Rejected 05/20/2016 05/12/2016
Joe Frogge
LC - General Contractor
Corrective Action Required
05/12/2016

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
05/12/2016

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Excerpt from Sec. 7-130, Lees Summit Code of Ordinances. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 05/20/2016 05/12/2016
Joe Dir
Misc
Corrective Action Required
05/12/2016

FUEL TANKS/DISPENSERS: PROVIDE SPECS FOR THE FUEL TANKS, FUEL LINES, DISPENCERS, SAFETY FASCTORS. 2306.2.3 Above-ground tanks located outside, above grade. Above-ground tanks shall not be used for the storage of Class I, II or III liquid motor fuels, except as provided by this section. 1. Above-ground tanks used for outside, above-grade storage of Class I liquids shall be listed and labeled as protected above-ground tanks in accordance with UL 2085 and shall be in accordance with Chapter 57. Such tanks shall be located in accordance with Table 2306.2.3. 2. Above-ground tanks used for outside, above-grade storage of Class II or IIIA liquids shall be listed and labeled as protected above-ground tanks in accordance with UL 2085 and shall be installed in accordance with Chapter 57. Tank locations shall be in accordance with Table 2306.2.3. Exception: Other above-ground tanks that comply with Chapter 57 where approved by the fire code official. 3. Tanks containing fuels shall not exceed 12,000 gallons (45 420 L) in individual capacity or 48,000 gallons (181 680 L) in aggregate capacity. Installations with the maximum allowable aggregate capacity shall be separated from other such installations by not less than 100 feet (30 480 mm). 4. Tanks located at farms, construction projects, or rural areas shall comply with Section 5706.2. 5. Above-ground tanks used for outside above-grade storage of Class IIIB liquid motor fuel shall be listed and labeled in accordance with UL 142 or listed and labeled as protected above-ground tanks in accordance with UL 2085 and shall be installed in accordance with Chapter 57. Tank locations shall be in accordance with Table 2306.2.3. 2305.5 Fire extinguishers. Approved portable fire extinguishers complying with Section 906 with a minimum rating of 2-A:20-B:C shall be provided and located such that an extinguisher is not more than 75 feet (23 860 mm) from pumps, dispensers or storage tank fill-pipe openings. 2305.6 Warning signs. Warning signs shall be conspicuously posted within sight of each dispenser in the fuel-dispensing area and shall state the following: 1. No smoking. 2. Shut off motor. 3. Discharge your static electricity before fueling by touching a metal surface away from the nozzle. 4. To prevent static charge, do not reenter your vehicle while gasoline is pumping. 5. If a fire starts, do not remove nozzle—back away immediately. 6. It is unlawful and dangerous to dispense gasoline into unapproved containers. 7. No filling of portable containers in or on a motor vehicle. Place container on ground before filling. 2303.2 Emergency disconnect switches. An approved, clearly identified and readily accessible emergency disconnect switch shall be provided at an approved location to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. An emergency disconnect switch for exterior fuel dispensers shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations, the emergency disconnect switch shall be installed at an approved location. Such devices shall be distinctly labeled as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations.
Construction documents for fire alarm systems
Corrective Action Required
05/12/2016

2012 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS OF THE FIRE ALARM SYSTEM TO BE INSTALLED.
Knox box required
Corrective Action Required
05/12/2016

2012 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. A KNOX BOX CAN BE OBTAINED ONLINE: knoxbox.com OR CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Locks on gates or barriers
Corrective Action Required
05/12/2016

2012 IFC 506.1.1-Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official. SUGGEST A KNOX KEY SWITCH FOR ANY GATES THAT MAY REQUIRED ACCESS BY THE FIRE DEPARTMENT. A KEY SWITHCH CAN BE OBTAIN ONLINE AT knoxbox.com OR CONTACT THE FIRE DEPARTMENT AT 816-969-1300.
Type I hood - Where required
Corrective Action Required
05/12/2016

2012 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. IF THE RANGE WILL BE USED FOR WARMING OF FOOD ONLY, A LETTER WILL BE REQUIRED STATING THAT THE RANGE WILL BE USED FOR WARMING PURPOSES ONLY.
Construction documents - Fire protection systems
Corrective Action Required
05/12/2016

2012 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. HAVE THE SELECTED CONTRACTOR PROVIDE SHOP DRAWINGS FOR THE FIRE SPRINKLER SYSTEM TO BE INSTALLED.
Installation acceptance testing
Corrective Action Required
05/12/2016

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. FIELD TESTING AND ACCEPTANCE TESTS WILL BE REQUIRED PRIOR TO THE FINAL OCCUPANCY INSPECTION. TO SCHEDULE A TEST CONTACT THE FIRE DEPARTMENT AT 816-969-1300
Portable fire extinguishers - general
Corrective Action Required
05/12/2016

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROVIDE FIRE EXTINGUISHERS RATED (5POUND) 2A-10BC FOR EVERY 3000 SQ FT. OF FLOOR SPACE.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
05/12/2016

2012 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. MOUNT THE FIRE EXTINGUISHER WITH THE TOP OF EXTINGUISHER NO HIGHER THAN 60" OFF OF FINISH FLOOR, WITH A MAXIMUM TRAVEL DISTANCE OF 75' FROM ANYWHERE WITHIN THE BUILDING.
Misc
Corrective Action Required
05/12/2016

PROVIDE SPECS AND INFORMATION ABOUT THE GENERATOR, FUEL TYPE MAY REQUIRED NFPA 704 PLACARDS.
Misc
Corrective Action Required
05/12/2016

PROVIDE INFORMATION ABOUT CO MONITORING IN THE VEHICLE AREAS.
Misc
Corrective Action Required
05/12/2016

FIRE DEPARTMENT CONNECTIONS: 903.3.7 THE LOCATION OF THE FIRE DEPARTMENT CONNECTIONS SHALL BE APPROVED BY THE FIRE CODE OFFICIAL. CONNECTIONS SHALL BE A 4" STORZ TYPE FITTING AND LOCATED WITHIN 100' OF A FIRE HYDRANT, OR AS APPROVED BY THE CODE OFFICIAL.
Misc
Corrective Action Required
05/12/2016

LOCKS & HARDWARE: NO INFORMATION WAS GIVEN ABOUT LOCKS AND OR DOOR HARWARE TO BE USED. ANY LOCKS SHALL FALL UNDER THE FOLLOWING 2012IFC CONDITIONS. NO KEYED LOCKS ON THE EGRESS SIDE OF ANY MARKED EXIT. [B] 1008.1 Doors.Means of egress doors shall meet the requirements of this section. Doors serving a means of egress system shall meet the requirements of this section and Section 1020.2. Doors provided for egress purposes in numbers greater than required by this code shall meet the requirements of this section.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $37,905.00 $37,905.00 Paid 08/22/2016
8331507-Sewer Connection Fee $1,410.00 $1,410.00 Paid 08/22/2016
8331401-Water Tap Fee $68,565.00 $68,565.00 Paid 08/22/2016
8350015-Water Meter Fee $1,515.00 $1,515.00 Paid 08/22/2016
9110073-Right of Way Permit Fee $75.00 $75.00 Paid 08/22/2016
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 10/19/2016 (10:00) 10/19/2016 10/19/2016
Misc
Partial Correction
10/19/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH
Footing Inspection - Commercial Partial 10/21/2016 10/21/2016 10/21/2016
Misc
Partial Correction
10/19/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ
Footing Inspection - Commercial Partial 10/25/2016 (11:00) 10/25/2016 10/25/2016
Misc
Partial Correction
10/21/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ
Footing Inspection - Commercial Partial 10/27/2016 10/27/2016 10/27/2016
Misc
Partial Correction
10/25/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ HARDENED ROOM APPROVED.
Footing Inspection - Commercial Partial 10/28/2016 10/28/2016 10/28/2016
Misc
Partial Correction
10/27/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED.
Footing Inspection - Commercial Partial 10/31/2016 (11:30) 10/31/2016 10/31/2016
Misc
Partial Correction
10/28/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Footing Inspection - Commercial Partial 11/1/2016 11/1/2016 11/01/2016
Misc
Partial Correction
10/31/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
11/01/2016
***AREA B**** ISOLATED PADS: B.5/13; B.5/11 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Footing Inspection - Commercial Partial 11/2/2016 11/2/2016 11/02/2016
Misc
Partial Correction
11/01/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
11/01/2016
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Underslab Plumbing Inspection - Commercial Partial 11/7/2016 11/7/2016 11/07/2016
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
11/07/2016
AREA A, BATHROOMS AND FLOOR DRAIN
Footing Inspection - Commercial Partial 11/7/2016 (1:00) 11/7/2016 11/07/2016
Misc
Partial Correction
11/02/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
11/02/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
11/02/2016
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
11/02/2016
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
11/07/2016
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED
Footing Inspection - Commercial Partial 11/8/2016 (11:30) 11/8/2016 at 11:40 AM 11/08/2016
Misc
Partial Correction
11/07/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
11/07/2016
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
11/07/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
11/07/2016
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
11/07/2016
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED
Underground Electrical Inspection - Commercial Partial 11/8/2016 at 12:06 PM 11/08/2016
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
11/08/2016
PRIMARY CONDUITS FROM TRANSFORMER PAD TO BUILDING APPROVED
Footing Inspection - Commercial Partial 11/9/2016 at 12:05 PM 11/09/2016
Misc
Partial Correction
11/08/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
11/08/2016
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
11/08/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
11/08/2016
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
11/08/2016
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED
Underslab Plumbing Inspection - Commercial Partial 11/9/2016 at 12:16 PM 11/09/2016
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
11/07/2016
AREA A: BATHROOMS AND FLOOR DRAIN, MOP SINK, STORM DRAIN APPOVED. HARDENED ROOM YET TO BE SET. AREA B: MECHANICAL CLOSET, STORM NEXT TO MECH ROOM AND FLOOR DRAINS APPROVED.
Underslab Plumbing Inspection - Commercial Partial 11/10/2016 11/10/2016
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
11/09/2016
AREA A: BATHROOMS AND FLOOR DRAIN, MOP SINK, STORM DRAIN APPOVED. HARDENED ROOM YET TO BE SET. AREA B: MECHANICAL CLOSET, STORM NEXT TO MECH ROOM AND FLOOR DRAINS APPROVED. AREA C: NORTH HALF OF LOCKER ROOM APPROVED
Electrical Service Inspection Failed 12/15/2016 12/15/2016 11/10/2016
Partial Correction
11/10/2016
***NOT AN INSPECTION*** UFFER LOCATED AT SOUTH END OF HARDENED ROOM APPROVED
Underslab Plumbing Inspection - Commercial Partial 11/11/2016 11/11/2016
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
11/10/2016
AREA A: BATHROOMS AND FLOOR DRAIN, MOP SINK, STORM DRAIN APPOVED. HARDENED ROOM YET TO BE SET. AREA B: MECHANICAL CLOSET, STORM NEXT TO MECH ROOM AND FLOOR DRAINS APPROVED. AREA C: LOCKER ROOM PLUMBING APPROVED
Underslab Electrical Inspection - Commercial Partial 11/11/2016 11/11/2016
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
11/11/2016
-COUNDUITS NORTH SIDE OF THE HARDENED ROOM, TO UTILITY ROOM AND THROUGH NORTH SIDE OF AREA B THROUGH FOOTING.
Underslab Electrical Inspection - Commercial Partial 11/21/2016 11/21/2016 11/21/2016
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
11/21/2016
-COUNDUITS NORTH SIDE OF THE HARDENED ROOM, TO UTILITY ROOM AND THROUGH NORTH SIDE OF AREA B THROUGH FOOTING. -AREA A AND B, CONDUITS FOR FLOOR BOXES AND HOMERUNS APPROVED
Footing Inspection - Commercial Partial 11/21/2016 (11:30) 11/21/2016 11/21/2016
Misc
Partial Correction
11/09/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
11/09/2016
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
11/09/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
11/09/2016
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
11/09/2016
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Footing Inspection - Commercial Partial 11/22/2016 (10:00) 11/22/2016 11/22/2016
Misc
Partial Correction
11/21/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
11/21/2016
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
11/21/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
11/21/2016
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
11/21/2016
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Footing Inspection - Commercial Partial 11/23/2016 (8:30) 11/23/2016 11/23/2016
Misc
Partial Correction
11/22/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
11/22/2016
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
11/22/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
11/22/2016
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
11/22/2016
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Suspended Slab Inspection Partial 12/2/2016 (4:00) 12/2/2016 12/02/2016
Misc
Partial Correction
12/02/2016
AREA A APPROVED
Electrical Service Inspection Passed 12/16/2016 12/16/2016 12/16/2016
Footing Inspection - Commercial Partial 12/16/2016 (8:00) 12/16/2016 12/16/2016
Misc
Partial Correction
11/23/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
11/23/2016
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
11/23/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
11/23/2016
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
11/23/2016
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
12/16/2016
***COVERED PARKING**** APPROVED SOUTH TO NORTH TO HALF WAY BETWEEN D LINE AND FAR NORTH ELEVATION.
Footing Inspection - Commercial Partial 12/21/2016 (8:00) 12/21/2016 12/21/2016
Misc
Partial Correction
12/16/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
12/16/2016
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
12/16/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
12/16/2016
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
12/16/2016
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
12/16/2016
***COVERED PARKINg STRUCTURE APPROVED
Underground Plumbing Inspection - Commercial Partial 11/11/2016 12/29/2016 12/29/2016
Misc
Partial Correction
12/29/2016
CONDUITS FOR PARKING LIGHTS: SOUTH AND NORTH BORDER LIGHTS APPROVED
Underground Electrical Inspection - Commercial Partial 1/4/2017 1/4/2017 01/04/2017
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
11/08/2016
PRIMARY CONDUITS FROM TRANSFORMER PAD TO BUILDING APPROVED
Underground Electrical Inspection - Commercial Not Ready 1/5/2017 1/5/2017 01/05/2017
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
01/04/2017
PRIMARY CONDUITS FROM TRANSFORMER PAD TO BUILDING APPROVED
Underground Electrical Inspection - Commercial Partial 1/10/2017 1/10/2017 01/10/2017
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
01/05/2017
-PRIMARY CONDUITS FROM TRANSFORMER PAD TO BUILDING APPROVED -NORTH PARKING LIGHTING APPROVED -SOUTH PARKING LIGHTING APPROVED -WEST PARKING LIGHTING APPROVED -DUCT BANK FROM HARDENED ROOM TO WEST LOCATION APPROVED
Footing Inspection - Commercial Not Ready 1/20/2017 (11:00) 1/20/2017 01/20/2017
Misc
Partial Correction
12/21/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
12/21/2016
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
12/21/2016
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
12/21/2016
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
12/21/2016
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
12/21/2016
***COVERED PARKINg STRUCTURE APPROVED
Footing Inspection - Commercial Partial 1/20/2017 (1:00) 1/20/2017 01/20/2017
Misc
Partial Correction
01/20/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
01/20/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
01/20/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
01/20/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
01/20/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
01/20/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
01/20/2017
ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED
Footing Inspection - Commercial Partial 1/25/2017 (11:00) 1/25/2017 01/25/2017
Misc
Partial Correction
01/20/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
01/20/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
01/20/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
01/20/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
01/20/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
01/20/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
01/20/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED BEAMS AND PADS APPROVED TO 1 LINE
Footing Inspection - Commercial Partial 1/27/2017 01/27/2017
Misc
Partial Correction
01/25/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
01/25/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
01/25/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
01/25/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
01/25/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
01/25/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
01/25/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Underslab Electrical Inspection - Commercial Partial 1/27/2017 1/27/2017 01/27/2017
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
11/21/2016
-COUNDUITS NORTH SIDE OF THE HARDENED ROOM, TO UTILITY ROOM AND THROUGH NORTH SIDE OF AREA B THROUGH FOOTING. -AREA A AND B, CONDUITS FOR FLOOR BOXES AND HOMERUNS APPROVED -AREA B GROUNDING ELETRODE CONUCTORS GOING TO NORTH AND SOUTH GROUD RINGS APROVED AND CONDUITS IN AREA BE AND HARDENED ROOM APPROVED.
Footing Inspection - Commercial Partial 1/27/2017 (1:00) 1/30/2017 01/30/2017
Misc
Partial Correction
01/27/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
01/27/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
01/27/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
01/27/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
01/27/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
01/27/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
01/27/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
01/30/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES.
Underground Electrical Inspection - Commercial Partial 1/31/2017 1/31/2017 01/31/2017
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
01/10/2017
-PRIMARY CONDUITS FROM TRANSFORMER PAD TO BUILDING APPROVED -NORTH PARKING LIGHTING APPROVED -SOUTH PARKING LIGHTING APPROVED -WEST PARKING LIGHTING APPROVED -DUCT BANK FROM HARDENED ROOM TO WEST LOCATION APPROVED
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
01/31/2017
NO ISSUES FOUND ON TRENCHED PVC ELECTRICAL CONDUIT: FROM GENERATOR LOCATION: ONE 1" N/NE TO L.P. AT N EDGE OF DETENTION POND; ONE 2" + THREE 1' NE TO J.B. @ GATE CONTROLLER; FIVE 1" NW TO FUEL PUMP LOCATION
Footing Inspection - Commercial Partial 1/31/2017 01/31/2017
Misc
Partial Correction
01/30/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
01/30/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
01/30/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
01/30/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
01/30/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
01/30/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
01/30/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
01/30/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES.
Misc
Partial Correction
01/31/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Footing Inspection - Commercial Not Ready 2/1/2017 2/1/2017 02/01/2017
Misc
Partial Correction
01/31/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
01/31/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
01/31/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
01/31/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
01/31/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
01/31/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
01/31/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
01/31/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES.
Misc
Partial Correction
01/31/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Corrective Action Required
02/01/2017
OFFICE TRAILER LOCKED. NO ACCESS TO PERMIT PRINTS. NOT READY FOR INSPECTION.
Miscellaneous Inspection Partial 2/1/2017 02/01/2017
Miscellaneous Inspection Partial 2/1/2017 02/01/2017
Misc
Partial Correction
02/01/2017
OBSERVED PREP FOR S.O.G. FLOOR POUR AT AREA "B". SPECIAL INSPECTOR ON SITE TO CHECK RE-BAR LAPS. OK TO POUR WHEN APPROVED BY SPECIAL INSPECTOR.
Footing Inspection - Commercial Partial 2/3/2017 (11:00) 2/3/2017 02/03/2017
Misc
Partial Correction
02/01/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
02/01/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
02/01/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
02/01/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
02/01/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
02/01/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
02/01/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
02/01/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
02/01/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
02/01/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
02/01/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
02/01/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
02/01/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
02/01/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
02/01/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES.
Misc
Partial Correction
02/01/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES.
Misc
Partial Correction
02/01/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
02/01/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
02/03/2017
ISOLATED PADS; H.6 3.8; G.4 3.8; F.3 3.8; H.6 6.8; G.4 6.8 GRADE BEAM 1 LINE TO N LINE APPROVED PADS UNDER N LINE APPROVED.
Misc
Resolved
02/01/2017
OFFICE TRAILER LOCKED. NO ACCESS TO PERMIT PRINTS. NOT READY FOR INSPECTION.
Footing Inspection - Commercial Partial 2/7/2017 (9:00) 2/7/2017 02/07/2017
Misc
Partial Correction
02/03/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
02/03/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
02/03/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
02/03/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
02/03/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
02/03/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
02/03/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES. AREA E APPROVED.
Misc
Partial Correction
02/03/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
02/03/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
02/03/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
02/03/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
02/03/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
02/03/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
02/03/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
02/03/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
02/03/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES.
Misc
Partial Correction
02/03/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
02/03/2017
ISOLATED PADS; H.6 3.8; G.4 3.8; F.3 3.8; H.6 6.8; G.4 6.8 GRADE BEAM 1 LINE TO N LINE APPROVED PADS UNDER N LINE APPROVED.
Misc
Partial Correction
02/03/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Footing Inspection - Commercial Partial 2/8/2017 (11:00) 2/8/2017 02/08/2017
Misc
Partial Correction
02/07/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
02/07/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
02/07/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
02/07/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
02/07/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
02/07/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
02/07/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES. AREA E APPROVED.
Misc
Partial Correction
02/07/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
02/07/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
02/07/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
02/07/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
02/07/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
02/07/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
02/07/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
02/07/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
02/07/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES.
Misc
Partial Correction
02/07/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
02/07/2017
ISOLATED PADS; H.6 3.8; G.4 3.8; F.3 3.8; H.6 6.8; G.4 6.8 GRADE BEAM 1 LINE TO N LINE APPROVED PADS UNDER N LINE APPROVED.
Misc
Partial Correction
02/07/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Underground Electrical Inspection - Commercial Failed 2/10/2017 2/10/2017 02/10/2017
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
01/31/2017
-PRIMARY CONDUITS FROM TRANSFORMER PAD TO BUILDING APPROVED -NORTH PARKING LIGHTING APPROVED -SOUTH PARKING LIGHTING APPROVED -WEST PARKING LIGHTING APPROVED -DUCT BANK FROM HARDENED ROOM TO WEST LOCATION APPROVED
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
01/31/2017
NO ISSUES FOUND ON TRENCHED PVC ELECTRICAL CONDUIT: FROM GENERATOR LOCATION: ONE 1" N/NE TO L.P. AT N EDGE OF DETENTION POND; ONE 2" + THREE 1' NE TO J.B. @ GATE CONTROLLER; FIVE 1" NW TO FUEL PUMP LOCATION
Misc
Corrective Action Required
02/10/2017
LIGHT POLE BASE RE-BAR CAGES MUST BE SUSPENDED TO PROVIDE MINIMUM 3" CLEARANCE AT BOTTOM OF HOLE
Underground Plumbing Inspection - Commercial Partial 2/10/2017 02/10/2017
Misc
Partial Correction
12/29/2016
CONDUITS FOR PARKING LIGHTS: SOUTH AND NORTH BORDER LIGHTS APPROVED
Misc
Partial Correction
02/10/2017
EXCEPT FOR VENT PIPING YET TO BE INSTALLED OK TO COVER BOTH OIL/WATER SEPARATORS SET IN PLACE AND PIPED
Underground Electrical Inspection - Commercial Partial 2/10/2017 2/10/2017 02/10/2017
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
02/10/2017
-PRIMARY CONDUITS FROM TRANSFORMER PAD TO BUILDING APPROVED -NORTH PARKING LIGHTING APPROVED -SOUTH PARKING LIGHTING APPROVED -WEST PARKING LIGHTING APPROVED -DUCT BANK FROM HARDENED ROOM TO WEST LOCATION APPROVED
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
02/10/2017
NO ISSUES FOUND ON TRENCHED PVC ELECTRICAL CONDUIT: FROM GENERATOR LOCATION: ONE 1" N/NE TO L.P. AT N EDGE OF DETENTION POND; ONE 2" + THREE 1' NE TO J.B. @ GATE CONTROLLER; FIVE 1" NW TO FUEL PUMP LOCATION
Misc
Partial Correction
02/10/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #5;
Underground Plumbing Inspection - Commercial Partial 2/10/2017 02/10/2017
Misc
Partial Correction
02/10/2017
CONDUITS FOR PARKING LIGHTS: SOUTH AND NORTH BORDER LIGHTS APPROVED
Misc
Partial Correction
02/10/2017
OK TO COVER BOTH OIL/WATER SEPARATORS SET IN PLACE AND PIPED. VENT PIPE TO BUILDING AT EAST UNIT; 19' OF 4" PIPE AT WEST UNIT;
Underground Electrical Inspection - Commercial Partial 2/14/2017 2/14/2017 02/14/2017
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
02/10/2017
-PRIMARY CONDUITS FROM TRANSFORMER PAD TO BUILDING APPROVED -NORTH PARKING LIGHTING APPROVED -SOUTH PARKING LIGHTING APPROVED -WEST PARKING LIGHTING APPROVED -DUCT BANK FROM HARDENED ROOM TO WEST LOCATION APPROVED
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
02/10/2017
NO ISSUES FOUND ON TRENCHED PVC ELECTRICAL CONDUIT: FROM GENERATOR LOCATION: ONE 1" N/NE TO L.P. AT N EDGE OF DETENTION POND; ONE 2" + THREE 1' NE TO J.B. @ GATE CONTROLLER; FIVE 1" NW TO FUEL PUMP LOCATION
Misc
Partial Correction
02/10/2017
OK TO POUR WHEN READY LIGHT POLE BASES AT FOLLOWING LOCATIONS NUMBERED ON SITE PLAN IN PERMIT PRINT SET: #5;
Underground Electrical Inspection - Commercial Partial 2/15/2017 2/15/2017 02/15/2017
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
02/14/2017
-PRIMARY CONDUITS FROM TRANSFORMER PAD TO BUILDING APPROVED -NORTH PARKING LIGHTING APPROVED -SOUTH PARKING LIGHTING APPROVED -WEST PARKING LIGHTING APPROVED -DUCT BANK FROM HARDENED ROOM TO WEST LOCATION APPROVED
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
02/14/2017
NO ISSUES FOUND ON TRENCHED PVC ELECTRICAL CONDUIT: FROM GENERATOR LOCATION: ONE 1" N/NE TO L.P. AT N EDGE OF DETENTION POND; ONE 2" + THREE 1' NE TO J.B. @ GATE CONTROLLER; FIVE 1" NW TO FUEL PUMP LOCATION
Misc
Partial Correction
02/14/2017
LIGHT POLE BASES APPROVED DUCT BANK TO GENERATOR PAD 60 FEET APPROVED
Underslab Plumbing Inspection - Commercial Partial 2/15/2017 2/15/2017 02/15/2017
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
11/11/2016
AREA A: BATHROOMS AND FLOOR DRAIN, MOP SINK, STORM DRAIN APPOVED. HARDENED ROOM YET TO BE SET. AREA B: MECHANICAL CLOSET, STORM NEXT TO MECH ROOM AND FLOOR DRAINS APPROVED. AREA C: LOCKER ROOM PLUMBING APPROVED
Misc
Partial Correction
02/15/2017
4" GREASE LINE FROM G LINE TO N LINE APPROVED
Underslab Plumbing Inspection - Commercial Partial 2/17/2017 2/17/2017 02/17/2017
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
02/15/2017
AREA A: BATHROOMS AND FLOOR DRAIN, MOP SINK, STORM DRAIN APPOVED. HARDENED ROOM YET TO BE SET. AREA B: MECHANICAL CLOSET, STORM NEXT TO MECH ROOM AND FLOOR DRAINS APPROVED. AREA C: LOCKER ROOM PLUMBING APPROVED
Misc
Partial Correction
02/15/2017
4" GREASE LINE FROM G LINE TO N LINE APPROVED AREA D SANITARY APPROVED
Underground Electrical Inspection - Commercial Partial 2/21/2017 2/21/2017 02/21/2017
Misc
Partial Correction
02/15/2017
LIGHT POLE BASES APPROVED DUCT BANK TO GENERATOR PAD 60 FEET APPROVED
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
02/15/2017
NO ISSUES FOUND ON TRENCHED PVC ELECTRICAL CONDUIT: FROM GENERATOR LOCATION: ONE 1" N/NE TO L.P. AT N EDGE OF DETENTION POND; ONE 2" + THREE 1' NE TO J.B. @ GATE CONTROLLER; FIVE 1" NW TO FUEL PUMP LOCATION
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
02/15/2017
-PRIMARY CONDUITS FROM TRANSFORMER PAD TO BUILDING APPROVED -NORTH PARKING LIGHTING APPROVED -SOUTH PARKING LIGHTING APPROVED -WEST PARKING LIGHTING APPROVED -DUCT BANK FROM HARDENED ROOM TO WEST LOCATION APPROVED
Footing Inspection - Commercial Partial 2/22/2017 (1:00) 2/22/2017 02/22/2017
Misc
Partial Correction
02/08/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5 ISO PADS SOUTH CANOPY 14, 15, 16 B.3 LINES
Misc
Partial Correction
02/08/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
02/08/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
02/08/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
02/08/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
02/08/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
02/08/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES. AREA E APPROVED.
Misc
Partial Correction
02/08/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
02/08/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
02/08/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
02/08/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
02/08/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
02/08/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
02/08/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
02/08/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
02/08/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES.
Misc
Partial Correction
02/08/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
02/08/2017
ISOLATED PADS; H.6 3.8; G.4 3.8; F.3 3.8; H.6 6.8; G.4 6.8 GRADE BEAM 1 LINE TO N LINE APPROVED PADS UNDER N LINE APPROVED.
Misc
Partial Correction
02/08/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Underground Electrical Inspection - Commercial Partial 2/28/2017 2/28/2017 02/28/2017
Misc
Partial Correction
02/21/2017
LIGHT POLE BASES APPROVED DUCT BANK TO GENERATOR PAD 60 FEET APPROVED
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
02/21/2017
NO ISSUES FOUND ON TRENCHED PVC ELECTRICAL CONDUIT: FROM GENERATOR LOCATION: ONE 1" N/NE TO L.P. AT N EDGE OF DETENTION POND; ONE 2" + THREE 1' NE TO J.B. @ GATE CONTROLLER; FIVE 1" NW TO FUEL PUMP LOCATION
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
02/21/2017
-PRIMARY CONDUITS FROM TRANSFORMER PAD TO BUILDING APPROVED -NORTH PARKING LIGHTING APPROVED -SOUTH PARKING LIGHTING APPROVED -WEST PARKING LIGHTING APPROVED -DUCT BANK FROM HARDENED ROOM TO WEST LOCATION APPROVED
Misc
Partial Correction
02/28/2017
CONDUITS FOR EXTERIOR RECEPTACLES AT SOUTH COLUMNS APPROVED.
Underslab Electrical Inspection - Commercial Partial 02/28/2017
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
01/27/2017
-COUNDUITS NORTH SIDE OF THE HARDENED ROOM, TO UTILITY ROOM AND THROUGH NORTH SIDE OF AREA B THROUGH FOOTING. -AREA A AND B, CONDUITS FOR FLOOR BOXES AND HOMERUNS APPROVED -AREA B GROUNDING ELETRODE CONUCTORS GOING TO NORTH AND SOUTH GROUD RINGS APROVED AND CONDUITS IN AREA BE AND HARDENED ROOM APPROVED. -AREA C AND AREA D APPROVED
Underslab Electrical Inspection - Commercial Passed 3/2/2017 3/2/2017 03/02/2017
THE FOLLOWING AREAS ARE APPROVED
Resolved
03/02/2017
-COUNDUITS NORTH SIDE OF THE HARDENED ROOM, TO UTILITY ROOM AND THROUGH NORTH SIDE OF AREA B THROUGH FOOTING. -AREA A AND B, CONDUITS FOR FLOOR BOXES AND HOMERUNS APPROVED -AREA B GROUNDING ELETRODE CONUCTORS GOING TO NORTH AND SOUTH GROUD RINGS APROVED AND CONDUITS IN AREA BE AND HARDENED ROOM APPROVED. -AREA C AND AREA D APPROVED
Footing Inspection - Commercial Not Ready 3/7/2017 (1:00) 3/7/2017 03/07/2017
Misc
Partial Correction
02/22/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5 ISO PADS SOUTH CANOPY 14, 15, 16 B.3 LINES
Misc
Partial Correction
02/22/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
02/22/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
02/22/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
02/22/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
02/22/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
02/22/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES. AREA E APPROVED.
Misc
Partial Correction
02/22/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
02/22/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
02/22/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
02/22/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
02/22/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
02/22/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
02/22/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
02/22/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
02/22/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES.
Misc
Partial Correction
02/22/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
02/22/2017
ISOLATED PADS; H.6 3.8; G.4 3.8; F.3 3.8; H.6 6.8; G.4 6.8 GRADE BEAM 1 LINE TO N LINE APPROVED PADS UNDER N LINE APPROVED.
Misc
Partial Correction
02/22/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Underground Electrical Inspection - Commercial Passed 3/8/2017 3/8/2017 03/08/2017
Misc
Partial Correction
02/28/2017
LIGHT POLE BASES APPROVED DUCT BANK TO GENERATOR PAD 60 FEET APPROVED
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
02/28/2017
NO ISSUES FOUND ON TRENCHED PVC ELECTRICAL CONDUIT: FROM GENERATOR LOCATION: ONE 1" N/NE TO L.P. AT N EDGE OF DETENTION POND; ONE 2" + THREE 1' NE TO J.B. @ GATE CONTROLLER; FIVE 1" NW TO FUEL PUMP LOCATION
THE FOLLOWING AREAS ARE APPROVED
Partial Correction
02/28/2017
-PRIMARY CONDUITS FROM TRANSFORMER PAD TO BUILDING APPROVED -NORTH PARKING LIGHTING APPROVED -SOUTH PARKING LIGHTING APPROVED -WEST PARKING LIGHTING APPROVED -DUCT BANK FROM HARDENED ROOM TO WEST LOCATION APPROVED
Misc
Partial Correction
02/28/2017
CONDUITS FOR EXTERIOR RECEPTACLES AT SOUTH COLUMNS APPROVED.
Footing Inspection - Commercial Partial 3/8/2017 (11:30) 3/8/2017 03/08/2017
Misc
Partial Correction
03/07/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5 ISO PADS SOUTH CANOPY 14, 15, 16 B.3 LINES
Misc
Partial Correction
03/07/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
03/07/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
03/07/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
03/07/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
03/07/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/07/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES. AREA E APPROVED.
Misc
Partial Correction
03/07/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
03/07/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
03/07/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/07/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
03/07/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
03/07/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
03/07/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
03/07/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/07/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES.
Misc
Partial Correction
03/07/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
03/07/2017
ISOLATED PADS; H.6 3.8; G.4 3.8; F.3 3.8; H.6 6.8; G.4 6.8 GRADE BEAM 1 LINE TO N LINE APPROVED PADS UNDER N LINE APPROVED.
Misc
Partial Correction
03/07/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Footing Inspection - Commercial Partial 3/9/2017 (11:30) 3/9/2017 03/09/2017
Misc
Partial Correction
03/08/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5 ISO PADS SOUTH CANOPY 14, 15, 16 B.3 LINES
Misc
Partial Correction
03/08/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
03/08/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
03/08/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
03/08/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
03/08/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/08/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES. AREA E APPROVED.
Misc
Partial Correction
03/08/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
03/08/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
03/08/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/08/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
03/08/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
03/08/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
03/08/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
03/08/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/08/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES.
Misc
Partial Correction
03/08/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
03/08/2017
ISOLATED PADS; H.6 3.8; G.4 3.8; F.3 3.8; H.6 6.8; G.4 6.8 GRADE BEAM 1 LINE TO N LINE APPROVED PADS UNDER N LINE APPROVED.
Misc
Partial Correction
03/08/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
03/09/2017
COVERED PARKING PADS AND BEAMS, 4 NORTH APPROVED
Footing Inspection - Commercial Partial 3/9/2017 (2:30) 3/9/2017 03/09/2017
Misc
Partial Correction
03/09/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
03/09/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
03/09/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/09/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES. AREA E APPROVED.
Misc
Partial Correction
03/09/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
03/09/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
03/09/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/09/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
03/09/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
03/09/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
03/09/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
03/09/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/09/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES.
Misc
Partial Correction
03/09/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
03/09/2017
ISOLATED PADS; H.6 3.8; G.4 3.8; F.3 3.8; H.6 6.8; G.4 6.8 GRADE BEAM 1 LINE TO N LINE APPROVED PADS UNDER N LINE APPROVED.
Misc
Partial Correction
03/09/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
03/09/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5 ISO PADS SOUTH CANOPY 14, 15, 16 B.3 LINES
Misc
Partial Correction
03/09/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
03/09/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
03/09/2017
COVERED PARKING PADS AND BEAMS, 4 NORTH APPROVED
Underground Electrical Inspection - Commercial Partial 3/10/2017 3/10/2017 03/10/2017
Misc
Partial Correction
03/10/2017
GROUND RING: WEST HALF OF THE GROUND RING AND RODS ASSOCIATED WITH THE GROUND RINGS AT THE PERIMETER OF THE BUILIDING APPROVED.
Footing Inspection - Commercial Partial 3/10/2017 (11:30) 3/10/2017 03/10/2017
Misc
Partial Correction
03/09/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
03/09/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
03/09/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/09/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES. AREA E APPROVED.
Misc
Partial Correction
03/09/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
03/09/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
03/09/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/09/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
03/09/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
03/09/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
03/09/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
03/09/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/09/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES.
Misc
Partial Correction
03/09/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
03/09/2017
ISOLATED PADS; H.6 3.8; G.4 3.8; F.3 3.8; H.6 6.8; G.4 6.8 GRADE BEAM 1 LINE TO N LINE APPROVED PADS UNDER N LINE APPROVED.
Misc
Partial Correction
03/09/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
03/09/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5 ISO PADS SOUTH CANOPY 14, 15, 16 B.3 LINES
Misc
Partial Correction
03/09/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
03/09/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
03/09/2017
COVERED PARKING PADS AND BEAMS, 4 NORTH APPROVED
Footing Inspection - Commercial Partial 3/13/2017 (1:00) 3/13/2017 03/10/2017
Misc
Partial Correction
03/10/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
03/10/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
03/10/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
03/10/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
03/10/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/10/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/10/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES. AREA E APPROVED.
Misc
Partial Correction
03/10/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES. AREA E APPROVED.
Misc
Partial Correction
03/10/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
03/10/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
03/10/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
03/10/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
03/10/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/10/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/10/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
03/10/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
03/10/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
03/10/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
03/10/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
03/10/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
03/10/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
03/10/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
03/10/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/10/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/10/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES.
Misc
Partial Correction
03/10/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES.
Misc
Partial Correction
03/10/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
03/10/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
03/10/2017
ISOLATED PADS; H.6 3.8; G.4 3.8; F.3 3.8; H.6 6.8; G.4 6.8 GRADE BEAM 1 LINE TO N LINE APPROVED PADS UNDER N LINE APPROVED.
Misc
Partial Correction
03/10/2017
ISOLATED PADS; H.6 3.8; G.4 3.8; F.3 3.8; H.6 6.8; G.4 6.8 GRADE BEAM 1 LINE TO N LINE APPROVED PADS UNDER N LINE APPROVED.
Misc
Partial Correction
03/10/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
03/10/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
03/10/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5 ISO PADS SOUTH CANOPY 14, 15, 16 B.3 LINES
Misc
Partial Correction
03/10/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5 ISO PADS SOUTH CANOPY 14, 15, 16 B.3 LINES
Misc
Partial Correction
03/10/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
03/10/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
03/10/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
03/10/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
03/10/2017
COVERED PARKING PADS AND BEAMS, 4 NORTH APPROVED
Misc
Partial Correction
03/10/2017
COVERED PARKING PADS AND BEAMS, 4 NORTH APPROVED
Footing Inspection - Commercial Partial 03/10/2017
Misc
Partial Correction
03/10/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
03/10/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
03/10/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/10/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES. AREA E APPROVED.
Misc
Partial Correction
03/10/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
03/10/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
03/10/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/10/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
03/10/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
03/10/2017
AREA C ISOLATED PADS AT 10, C.7; 8, C.7; 10, B.5; 8, B.5 APPROVED 1 LINE PADS APPROVED TO POUR
Misc
Partial Correction
03/10/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED. EAST SIDE OF HARDENED ROOM LINE A APPROVED
Misc
Partial Correction
03/10/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5
Misc
Partial Correction
03/10/2017
***AREA D*** GRADE BEAMS AND ASSOCIATED PADS APPROVED FROM E.7 TO L LINES.
Misc
Partial Correction
03/10/2017
OK TO POUR WHEN READY ISOLATED FOOTINGS AT FOLLOWING LOCATIONS: M/9; M/1
Misc
Partial Correction
03/10/2017
ISOLATED PADS; H.6 3.8; G.4 3.8; F.3 3.8; H.6 6.8; G.4 6.8 GRADE BEAM 1 LINE TO N LINE APPROVED PADS UNDER N LINE APPROVED.
Misc
Partial Correction
03/10/2017
***AREA A*** -EXTERIOR GRADE BEAM AND COLUMN PADS OK: FROM LINE 5A/AA TO 14A/CC; F27.8 PAD WITHOUT GRADE BEAM ON TOP; KK TO 4A; LL LINE; 1A LINE ;AA-JJ -ISOLATED COLUMN PADS OK: 9A/CC, 9A/HH, CA-HH,JJ; 6A/CC; 6A/JJ; HH/1 HARDENED ROOM APPROVED. ISOLATED PADS: D.3/17; D.3/15.4; D.3/15 WERE NOT INSPECTED BY CITY INSPECTIONS. CHECK SPECIAL INSPECTIONS. GRADE BEAM AND PADS A LINE FROM 10-14 APPROVED.
Misc
Partial Correction
03/10/2017
***AREA B**** ISOLATED PADS: B.5/13; B.5/11; E.3/12; E.3/13; E.3/15; D.3/12; A/11; A/13 NORTH GRADE BEAM AND PADS: E7 LINE B.5 ISO PADS SOUTH CANOPY 14, 15, 16 B.3 LINES
Misc
Partial Correction
03/10/2017
AREA D AND C FOOTINGS BETWEEN 9 AND 11 LINES APPROVED, LOCKER ROOMS APPROVED BOILER ROOM FOOTING APPROVED
Misc
Partial Correction
03/10/2017
***COVERED PARKINg STRUCTURE APPROVED
Misc
Partial Correction
03/10/2017
COVERED PARKING PADS AND BEAMS, 4 NORTH APPROVED
Underground Electrical Inspection - Commercial Partial 3/15/2017 3/15/2017 03/15/2017
Misc
Partial Correction
03/10/2017
GROUND RING: GROUND RING AND RODS ASSOCIATED WITH THE GROUND RINGS AT THE PERIMETER OF THE BUILIDING APPROVED.
Underground Electrical Inspection - Commercial Partial 3/17/2017 3/17/2017 03/17/2017
Misc
Partial Correction
03/15/2017
GROUND RING: GROUND RING AND RODS ASSOCIATED WITH THE GROUND RINGS AT THE PERIMETER OF THE BUILIDING APPROVED.
Underground Electrical Inspection - Commercial Partial 3/21/2017 3/21/2017 03/21/2017
Misc
Partial Correction
03/17/2017
GROUND RING: GROUND RING AND RODS ASSOCIATED WITH THE GROUND RINGS AT THE PERIMETER OF THE BUILIDING APPROVED. LIGHTNING PROTECTION FOR COVERED PARKING APPROVED. CONDUITES FOR FLAG POLE AND MONUMENT SIGN APPROVED.
Underslab Electrical Inspection - Commercial Passed 4/17/2017 4/17/2017 04/17/2017
Rough Framing Inspection - Commercial Partial 05/12/2017
Misc
Partial Correction
05/12/2017
EXTERIOR SHEATHING FASTNER APPROVED FOR AREAS A, B, AND C
In-wall Inspection Partial 6/15/2017 06/15/2017
Misc
Partial Correction
06/15/2017
AREAS A AND B ARE APPROVED TO COVER
Water Service Inspection Partial 6/27/2017 06/27/2017
Corrective Action Required
06/27/2017
Brice Lawson 06/27/2017 3:08 PM The domestic water service including meter has been installed from the tie-in at the 6" water main extension to the building riser. The 1" copper line has been installed to the wash bay. The 1.5" copper irrigation service line has been installed from the 4" C900 over to the water meter for the irrigation line. All bacterial tests for each of these lines have passed and the lines have been put into service. ***The irrigation line was only installed and inspected up to the inlet side of the meter.
In-wall Inspection Partial 8/2/2017 08/02/2017
Misc
Partial Correction
06/15/2017
AREAS A, B, C, AND D ARE APPROVED TO COVER
Gas Piping Inspection - Commercial Passed 8/23/2017 8/23/2017 08/23/2017
Gas Service Inspection - Commercial Passed 08/23/2017
Above Ceiling Inspection Partial 9/14/2017 9/14/2017 at 11:00 AM 09/14/2017
Misc
Partial Correction
09/14/2017
HARD LIDS IN LOCKER ROOMS, BATHROOMS, AND CONFERENCE ROOM APPROVED.
Electrical Service Inspection Failed 9/29/2017 09/29/2017
Misc
Corrective Action Required
09/29/2017
-MAIN BONDING JUMPER NEEDS TO SIZED NO SMALLER THAN THE LARGEST UNGROUNDED CONDUCTOR -SERVICE EQUIPMENT REQUIRED TO HAVE BONDING BUSHINGS BETWEEN SERVICE EQUIPMENT
Electrical Service Inspection Passed 10/2/2017 at 9:15 AM 10/02/2017
Misc
Resolved
10/02/2017
-MAIN BONDING JUMPER NEEDS TO SIZED NO SMALLER THAN THE LARGEST UNGROUNDED CONDUCTOR -SERVICE EQUIPMENT REQUIRED TO HAVE BONDING BUSHINGS BETWEEN SERVICE EQUIPMENT
Above Ceiling Inspection Partial 10/23/2017 10/23/2017 at 10:15 AM 10/23/2017
Misc
Partial Correction
09/14/2017
HARD LIDS IN LOCKER ROOMS, BATHROOMS, AND CONFERENCE ROOM APPROVED. AREA A: CLOSE J BOXES AND REMOVER TEMP LIGHTING
Above Ceiling Inspection Partial 10/24/2017 at 9:40 AM 10/24/2017
Misc
Partial Correction
10/23/2017
HARD LIDS IN LOCKER ROOMS, BATHROOMS, AND CONFERENCE ROOM APPROVED. AREA A: APPROVED TO DROP TILE
Above Ceiling Inspection Partial 10/26/2017 10/26/2017 at 12:20 PM 10/26/2017
Misc
Partial Correction
10/24/2017
HARD LIDS IN LOCKER ROOMS, BATHROOMS, AND CONFERENCE ROOM APPROVED. AREA A: APPROVED TO DROP TILE AREA B; DROP SPRINKLER HEADS
Sprinkler - Hydrostatic Test Passed 11/6/2017 11/06/2017
Above Ceiling Inspection Partial 11/6/2017 11/6/2017 at 1:30 PM 11/06/2017
Misc
Partial Correction
10/26/2017
ALL APPROVED EXCEPT KITCHEN / BREAK ROOM
Above Ceiling Inspection Partial 11/9/2017 11/9/2017 at 10:00 AM 11/09/2017
Misc
Partial Correction
11/06/2017
ALL APPROVED EXCEPT KITCHEN / BREAK ROOM, REMOVE LOW VOLTAGE WIRING FROM SPRINKLER LINES
Alarm Test Passed 11/15/2017 11/15/2017
Sprinkler - Flow Test Passed 11/15/2017 11/15/2017
Occupancy Inspection - Codes Commercial Not Ready 11/15/2017 11/15/2017 at 12:00 PM 11/15/2017
Misc
Partial Correction
11/15/2017
NOT A COMPLETE FINAL, INSPECTED RECEPTACLES THAT MAY BY COVERED WITH OFFICE FURNITURE. OKAY TO INSALL OFFICE FURNITURE ONLY
Hazardous Materials Inspection Passed 12/12/2017 12/12/2017
Occupancy Inspection - Fire Passed 12/12/2017 12/12/2017
Occupancy Inspection - Codes Commercial Temporary C of O 12/12/2017 12/13/2017 12/13/2017
Misc
Partial Correction
11/15/2017
-NO BUILDING ISSUES OBTAIN APPROVAL FROM ENGINEERING, PLANNING DIVISIONS
Occupancy Inspection - Planning Temporary C of O 12/14/2017
Corrective Action Required
12/14/2017
Complete sodding along Hamblen Rd frontage per the approved landscape plan.
Corrective Action Required
12/14/2017
Complete building exterior (i.e. installation of exterior material panels) per the approved architectural plans.
Occupancy Inspection - Engineering Temporary C of O 12/14/2017 12/14/2017
Informational
12/14/2017
Brice Lawson 12/14/2017 3:51 PM A Cert. of Substantial Completion has been issued with Punch List.
Occupancy Inspection - Water Utilities Passed 12/20/2017
Occupancy Inspection - Engineering Not Ready 3/29/2018 03/29/2018
Informational
03/29/2018
Brice Lawson 03/29/2018 10:55 AM There are items on the revised Punch List that have not been completed. Some of the items have been resolved and marked off on the revised Punch List. I have talked with Casey Williams about the time frame of when he plans to complete the remaining revised Punch List items.
Occupancy Inspection - Planning Passed 03/01/2019
Occupancy Inspection - Engineering Passed 02/06/2020
Occupancy Inspection - Codes Commercial Full C of O 02/06/2020
Misc
Partial Correction
12/13/2017
-NO BUILDING ISSUES OBTAIN APPROVAL FROM ENGINEERING, PLANNING DIVISIONS
Documents & Images
Date Uploaded File Type Document Name
05/12/2016 Letter Fire Building Plan Review
05/17/2016 Letter Codes P/R Corrections Document
07/26/2016 Letter Fire Building Plan Review
07/26/2016 Letter Codes P/R Corrections Document
08/22/2016 Receipt Receipt for transaction: 2016-005547
08/30/2016 SI Letter of Intent
08/30/2016 Letter Codes Plan Review Conditions
08/30/2016 Letter Codes Plan Review Conditions
09/01/2016 Letter Codes Building Permit
10/19/2016 Letter Inspection Summary
10/21/2016 Letter Inspection Summary
10/25/2016 Letter Inspection Summary
10/27/2016 Letter Inspection Summary
10/28/2016 Letter Inspection Summary
10/31/2016 Letter Inspection Summary
11/01/2016 Letter Inspection Summary
11/02/2016 Letter Inspection Summary
11/07/2016 Letter Inspection Summary
11/08/2016 Letter Inspection Summary
11/11/2016 Letter Inspection Summary
11/21/2016 Letter Inspection Summary
11/22/2016 Letter Inspection Summary
11/23/2016 Letter Inspection Summary
12/02/2016 Letter Inspection Summary
12/16/2016 Letter Inspection Summary
12/16/2016 Letter Inspection Summary
12/21/2016 Letter Inspection Summary
01/04/2017 Letter Inspection Summary
01/05/2017 Letter Inspection Summary
01/10/2017 Letter Inspection Summary
01/18/2017 Letter Fire (Sprinkler) Plan Review
01/20/2017 Letter Inspection Summary
01/20/2017 Letter Inspection Summary
01/25/2017 Letter Inspection Summary
01/27/2017 Letter Inspection Summary
01/30/2017 Letter Inspection Summary
01/31/2017 Letter Inspection Summary
02/01/2017 Letter Inspection Summary
02/03/2017 Letter Inspection Summary
02/07/2017 Letter Inspection Summary
02/08/2017 Letter Inspection Summary
02/10/2017 Letter Inspection Summary
02/10/2017 Letter Inspection Summary
02/14/2017 Letter Inspection Summary
02/15/2017 Letter Inspection Summary
02/17/2017 Letter Inspection Summary
02/21/2017 Letter Inspection Summary
02/22/2017 Letter Inspection Summary
02/28/2017 Letter Inspection Summary
03/02/2017 Letter Inspection Summary
03/07/2017 Letter Inspection Summary
03/08/2017 Letter Inspection Summary
03/10/2017 Letter Inspection Summary
03/15/2017 Letter Inspection Summary
03/17/2017 Letter Inspection Summary
03/21/2017 Letter Inspection Summary
04/17/2017 Letter Inspection Summary
05/12/2017 Letter Inspection Summary
06/15/2017 Letter Inspection Summary
06/27/2017 Letter PW-Daily Inspection Summary
08/23/2017 Letter Inspection Summary
08/29/2017 Letter Fire (Alarm) Plan Review Notice
09/14/2017 Letter Inspection Summary
09/29/2017 Letter Inspection Summary
10/02/2017 Letter Inspection Summary
10/23/2017 Letter Inspection Summary
10/24/2017 Letter Inspection Summary
10/26/2017 Letter Inspection Summary
11/06/2017 Letter Inspection Summary
11/09/2017 Letter Inspection Summary
11/15/2017 Letter Inspection Summary
12/13/2017 Letter Codes Temporary Certificate of Occupancy
12/14/2017 Engineer Report/Study DOC121417
12/19/2017 Engineer Report/Study DOC121917
12/27/2017 Letter Fire Building Plan Review
02/07/2018 Letter Water Utilities Operations Building Sidewalk Commitment Letter
03/29/2018 Letter DE-Daily Inspection Summary
05/03/2019 Letter Codes 10 Day Letter
02/06/2020 Letter Codes Final Certificate of Occupancy
02/11/2020 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home