Review Type |
Outcome |
Est. Completion Date |
Completed |
Sprinkler Plan Review
|
Released for Construction
|
08/04/2011
|
08/04/2011
|
|
Jim Eden
|
|
Construction documents - Fire protection systems
Corrective Action Required
2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Revised plans for the patio area received on August 4, 2011.
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Call (816) 969-1300 to schedule system testing.
|
|
|
Fire Plan Review
|
Approved
|
07/20/2011
|
07/18/2011
|
|
Brian Austerman
|
|
Construction documents - Fire protection systems
Corrective Action Required
2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Action required: Provide revised plans for extending sprinkler coverage under the roof of the patio. NOTED IN RESUB, PROVIDE REVISED SPRINKLER PLANS
|
|
|
Building Plan Review
|
Approved
|
07/20/2011
|
07/18/2011
|
|
Mike Weisenborn
|
|
Misc
Corrective Action Required
Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Action required - This comment is for information purposes.
|
|
Engineered truss package
Corrective Action Required
Copies of the engineered truss package were not provided at the time of permit application.
Action required - Provide two (2) copies of the engineered truss package which have been sealed and signed by an engineer licensed in the State of Missouri. This information is not required for permit approval or issuance but shall be provided prior to inspection.
|
|
Misc
Corrective Action Required
Information on the hoods to be installed has not been provided.
Action required - Provide specifications and installation details for the hoods, ducts, exhaust and make-up air systems. This shall include the information clearances to combustibles, how the equipment will be supported and air calculations.
Specifications on the hoods and make-up air systems will be a deferred submittal.
|
|
Misc
Corrective Action Required
2006 IMC 507.2.2 - Type II hoods. Type II hoods shall be installed where cooking or dishwashing appliances produce heat, steam, or products of combustion and do not produce grease or smoke, such as steamers, kettles, pasta cookers and dishwashing machines.
Action required - Show how this requirement will be met.
The hood location is now shown on the floor plans. Specifications will be a deferred submittal.
|
|
Plumb - Indirect waste for food handling fixtures
Corrective Action Required
2006 IPC 802.1.1 - Food handling. Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap.
Action required - Show how this requirement will be met.
This will be verified on inspection.
|
|
Misc
Corrective Action Required
Egress from the patio area shall not be through the building.
Action required - Provide an exterior means of egress from the patio area. If a latching device is provided on the gate, hardware shall meet the standard requirments.
The gate has been added to Sheet A-1. Hardware will be verified on inspection.
|
|
Screening - Rooftop equipment
Corrective Action Required
Planning and Development - Commercial businesses located along existing public streets shall be subject to the following design standards: a. buildings shall be designed with four (4) sided architecture, the same level of finish on all sides (no "back"); b. rooftop or ground-level mechanical equipment shall be totally screened from view by using either parapet walls at the same height of the mechanical units for rooftop mounts or by providing screening for ground mounted units acceptable to the Director; c. Wherever possible, parking areas and pedestrian walks shall connect internally to parking areas and pedestrian walks of existing adjoining businesses. Provisions shall be make for future connections to adjoining property not yet developed or redeveloped.
Action required - Provide details for screening of the rooftop equipment.
Responce letter indicates that the parapet as shown will screen the rooftop kitchen equipment. This will be verified on inspection.
|
|
Mech - Clearance for Type I hood
Corrective Action Required
2003 IMC 507.9 - Clearance for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18 inches (457 mm).
Exception: Clearance shall not be required from gypsum wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed between the hood and the gypsum wallboard over an area extending not less than 18 inches (457 mm) in all directions from the hood.
Action required - A type one hood can not be located within of combustible framing. Make needed corrections.
Note 15 has been added to the plans. The steel stud wall shall extend a minimum of 18" beyond the end of the hood unless the wall terminates in less than that distance. to be verified on inspection.
|
|
Misc
The revised Final Development Plan shows the roof covering to be spanish tile but the re-submittal for the building permit shows standing seam metal roof.
Action required - I am assuming that the structural calculations provided were for a standing seam roof as that is what is shown on the plans. Clearify which material is to be used. If spanish tile is being used, we will need either a letter from the engineer indicating that the structural calculations are for the material or provide revisions.
|
|
Misc
The revised plans show a change in the facade for the building which I understand has been approved by Planning and Development. However these changes have never been provided to the Codes Department.
Action required - Make corrections to Sheet A-5.
|
|
Misc
I am unable to locate any details showing how the new roof is to be tied into the wall for water proofing.
Action required - Provide flashing details.
|
|
Misc
Revised plans for the electrical on for the patio have not been provided.
Action required - If revisions for the electrical system are plan, the plans need to be revised for such work.
|
|
|
Internal Plan Review (Res)
|
Rejected
|
|
07/07/2011
|
|
Mike Weisenborn
|
|
|
Fire Plan Review
|
Rejected
|
07/08/2011
|
07/07/2011
|
|
Jim Eden
|
|
Misc
A fire hydrant has beenprovided within 100' of the FDC. Provide revised sprinkler plans. Some allowance may be given to the location of the hydrant in front of the building.
|
|
Construction documents - Fire protection systems
Corrective Action Required
2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Action required: Provide revised plans for extending sprinkler coverage under the roof of the patio.
|
|
|
Building Plan Review
|
Rejected
|
07/08/2011
|
07/05/2011
|
|
Mike Weisenborn
|
|
Misc
Corrective Action Required
Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Action required - This comment is for information purposes.
|
|
Engineered truss package
Corrective Action Required
Copies of the engineered truss package were not provided at the time of permit application.
Action required - Provide two (2) copies of the engineered truss package which have been sealed and signed by an engineer licensed in the State of Missouri. This information is not required for permit approval or issuance but shall be provided prior to inspection.
|
|
Misc
Corrective Action Required
Information on the hoods to be installed has not been provided.
Action required - Provide specifications and installation details for the hoods, ducts, exhaust and make-up air systems. This shall include the information clearances to combustibles, how the equipment will be supported and air calculations.
Specifications on the hoods and make-up air systems will be a deferred submittal.
|
|
Misc
Corrective Action Required
2006 IMC 507.2.2 - Type II hoods. Type II hoods shall be installed where cooking or dishwashing appliances produce heat, steam, or products of combustion and do not produce grease or smoke, such as steamers, kettles, pasta cookers and dishwashing machines.
Action required - Show how this requirement will be met.
The hood location is now shown on the floor plans. Specifications will be a deferred submittal.
|
|
Plumb - Indirect waste for food handling fixtures
Corrective Action Required
2006 IPC 802.1.1 - Food handling. Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap.
Action required - Show how this requirement will be met.
This will be verified on inspection.
|
|
Misc
Corrective Action Required
Egress from the patio area shall not be through the building.
Action required - Provide an exterior means of egress from the patio area. If a latching device is provided on the gate, hardware shall meet the standard requirments.
The gate has been added to Sheet A-1. Hardware will be verified on inspection.
|
|
Screening - Rooftop equipment
Corrective Action Required
Planning and Development - Commercial businesses located along existing public streets shall be subject to the following design standards: a. buildings shall be designed with four (4) sided architecture, the same level of finish on all sides (no "back"); b. rooftop or ground-level mechanical equipment shall be totally screened from view by using either parapet walls at the same height of the mechanical units for rooftop mounts or by providing screening for ground mounted units acceptable to the Director; c. Wherever possible, parking areas and pedestrian walks shall connect internally to parking areas and pedestrian walks of existing adjoining businesses. Provisions shall be make for future connections to adjoining property not yet developed or redeveloped.
Action required - Provide details for screening of the rooftop equipment.
Responce letter indicates that the parapet as shown will screen the rooftop kitchen equipment. This will be verified on inspection.
|
|
Mech - Clearance for Type I hood
Corrective Action Required
2003 IMC 507.9 - Clearance for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18 inches (457 mm).
Exception: Clearance shall not be required from gypsum wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed between the hood and the gypsum wallboard over an area extending not less than 18 inches (457 mm) in all directions from the hood.
Action required - A type one hood can not be located within of combustible framing. Make needed corrections.
Note 15 has been added to the plans. The steel stud wall shall extend a minimum of 18" beyond the end of the hood unless the wall terminates in less than that distance. to be verified on inspection.
|
|
Misc
Corrective Action Required
The revised Final Development Plan shows the roof covering to be spanish tile but the re-submittal for the building permit shows standing seam metal roof.
Action required - I am assuming that the structural calculations provided were for a standing seam roof as that is what is shown on the plans. Clearify which material is to be used. If spanish tile is being used, we will need either a letter from the engineer indicating that the structural calculations are for the material or provide revisions.
|
|
Misc
Corrective Action Required
The revised plans show a change in the facade for the building which I understand has been approved by Planning and Development. However these changes have never been provided to the Codes Department.
Action required - Make corrections to Sheet A-5.
|
|
Misc
Corrective Action Required
I am unable to locate any details showing how the new roof is to be tied into the wall for water proofing.
Action required - Provide flashing details.
|
|
Misc
Corrective Action Required
Revised plans for the electrical on for the patio have not been provided.
Action required - If revisions for the electrical system are plan, the plans need to be revised for such work.
|
|
|
Alarm Plan Review
|
Released for Construction
|
|
06/30/2011
|
|
Brian Austerman
|
|
Misc
Corrective Action Required
Fire Dept- need to show an exterior horn strobe on the south side by the FDC. This is to activate only for sprinkler water flow
ADDRESSED IN RESUB, RELEASED FOR CONSTRUCTION
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Action Required: Call 969-1300 to schedule alarm and hood test prior to final
|
|
|
Alarm Plan Review
|
Rejected
|
|
06/28/2011
|
|
Brian Austerman
|
|
Misc
Corrective Action Required
Fire Dept- need to show an exterior horn strobe on the south side by the FDC. This is to activate only for sprinkler water flow
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Action Required: Call 969-1300 to schedule alarm and hood test prior to final
|
|
|
Sprinkler Plan Review
|
Released for Construction
|
|
06/08/2011
|
|
Jim Eden
|
|
Construction documents - Fire protection systems
Corrective Action Required
2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Revised plans recieved June 1,2011.
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Call (816)969-1300 to schedule hydrostatic and flow tests.
|
|
Misc
A fire hydrant is required within 100' of the fire department connection. Currently a fire hydrant does not meet this requirement. Contact the General Contractor to coordinate the location of both.
|
|
Misc
The sprinkler system shall be designed to the 2002 NFPA 13, as adopted by the 2006 International Fire Code.
Correct design criteria. Provide a Code Modification Request for items not addressed or changed from the 2002 edition of NFPA 13.
|
|
Misc
The outside bell shall be replaced by a weatherproof horn/strobe.
|
|
Misc
The FDC shall have a 4" Storz type connection.
|
|
|
Fire Plan Review
|
Approved
|
01/19/2011
|
05/26/2011
|
|
Mike Weisenborn
|
|
Misc
Corrective Action Required
A fire hydrant has beenprovided within 100' of the FDC. Provide revised sprinkler plans. Some allowance may be given to the location of the hydrant in front of the building.
|
|
|
Sprinkler Plan Review
|
Rejected
|
|
05/19/2011
|
|
Jim Eden
|
|
Construction documents - Fire protection systems
Corrective Action Required
2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Plans received May 18,2011.
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Call (816)969-1300 to schedule hydrostatic and flow tests.
|
|
Misc
Corrective Action Required
A fire hydrant is required within 100' of the fire department connection. Currently a fire hydrant does not meet this requirement. Contact the General Contractor to coordinate the location of both.
|
|
Misc
Corrective Action Required
The sprinkler system shall be designed to the 2002 NFPA 13, as adopted by the 2006 International Fire Code.
Correct design criteria. Provide a Code Modification Request for items not addressed or changed from the 2002 edition of NFPA 13.
|
|
Misc
Corrective Action Required
The outside bell shall be replaced by a weatherproof horn/strobe.
|
|
Misc
Corrective Action Required
The FDC shall have a 4" Storz type connection.
|
|
|
Building Plan Review
|
Approved
|
01/18/2011
|
01/18/2011
|
|
Mike Weisenborn
|
|
Misc
Corrective Action Required
Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Action required - This comment is for information purposes.
|
|
Engineered truss package
Corrective Action Required
Copies of the engineered truss package were not provided at the time of permit application.
Action required - Provide two (2) copies of the engineered truss package which have been sealed and signed by an engineer licensed in the State of Missouri. This information is not required for permit approval or issuance but shall be provided prior to inspection.
|
|
Misc
Corrective Action Required
Information on the hoods to be installed has not been provided.
Action required - Provide specifications and installation details for the hoods, ducts, exhaust and make-up air systems. This shall include the information clearances to combustibles, how the equipment will be supported and air calculations.
Specifications on the hoods and make-up air systems will be a deferred submittal.
|
|
Mech - Outdoor air required
2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Action required - Provide calculations.
Information for unit F-3 has not been provided. Provide additional informaiton.
|
|
Misc
Corrective Action Required
2006 IMC 507.2.2 - Type II hoods. Type II hoods shall be installed where cooking or dishwashing appliances produce heat, steam, or products of combustion and do not produce grease or smoke, such as steamers, kettles, pasta cookers and dishwashing machines.
Action required - Show how this requirement will be met.
The hood location is now shown on the floor plans. Specifications will be a deferred submittal.
|
|
Misc
A plumbing riser diagram has not been provided.
Action required - Provide a riser diagram for the waste, vent and water systems.
A riser diagram has been provided but not all the pipe sizes are indicated. Make needed corrections.
|
|
Plumb - Indirect waste for food handling fixtures
Corrective Action Required
2006 IPC 802.1.1 - Food handling. Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap.
Action required - Show how this requirement will be met.
This will be verified on inspection.
|
|
Misc
Corrective Action Required
Egress from the patio area shall not be through the building.
Action required - Provide an exterior means of egress from the patio area. If a latching device is provided on the gate, hardware shall meet the standard requirments.
The gate has been added to Sheet A-1. Hardware will be verified on inspection.
|
|
Screening - Rooftop equipment
Corrective Action Required
Planning and Development - Commercial businesses located along existing public streets shall be subject to the following design standards: a. buildings shall be designed with four (4) sided architecture, the same level of finish on all sides (no "back"); b. rooftop or ground-level mechanical equipment shall be totally screened from view by using either parapet walls at the same height of the mechanical units for rooftop mounts or by providing screening for ground mounted units acceptable to the Director; c. Wherever possible, parking areas and pedestrian walks shall connect internally to parking areas and pedestrian walks of existing adjoining businesses. Provisions shall be make for future connections to adjoining property not yet developed or redeveloped.
Action required - Provide details for screening of the rooftop equipment.
Responce letter indicates that the parapet as shown will screen the rooftop kitchen equipment. This will be verified on inspection.
|
|
Mech - Clearance for Type I hood
Corrective Action Required
2003 IMC 507.9 - Clearance for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18 inches (457 mm).
Exception: Clearance shall not be required from gypsum wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed between the hood and the gypsum wallboard over an area extending not less than 18 inches (457 mm) in all directions from the hood.
Action required - A type one hood can not be located within of combustible framing. Make needed corrections.
Note 15 has been added to the plans. The steel stud wall shall extend a minimum of 18" beyond the end of the hood unless the wall terminates in less than that distance. to be verified on inspection.
|
|
|
Internal Plan Review (Res)
|
Approved
|
01/18/2011
|
01/18/2011
|
|
Mike Weisenborn
|
|
|
Fire Plan Review
|
Approved
|
01/18/2011
|
01/13/2011
|
|
Jim Eden
|
|
Misc
Fire Department- IFC 903.3.7 Fire department connections.
The location of fire department connections shall be approved by the fire code official. connections shall be 4 inch Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the fire code official.
Action required: Provide a fire hydrant within 100' of the FDC.
Action required 12/30: The FDC will be on a pedestal located at the street. Provide a detail for the Backflow /FDC assembly.
Action Required 1/13/11: Provide a civil detail for the pedestal FDC.
|
|
Construction documents - Fire protection systems
Corrective Action Required
Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Action required: Provide shop drawings for review and approval.
|
|
Construction documents for fire alarm systems
Corrective Action Required
Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Action required: Provide shop drawings for review and approval. Interior alarm notification appliances and monitoring are required.
|
|
Knox box required
Corrective Action Required
Fire Department- 2006 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official.
Action required 12/30: Obtain a Knox application from the fire department. The Knox box shall be mounted 6' AFF below the exterior horn/strobe for the sprinkler system.
|
|
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
Fire Department- 2006 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
Action required: Provide a K class extinguisher under the hood system manual pull station with instructions in english and the predominate language.
Action required 12/30: The K Class extinguisher shall be located under the manual pull station for the hood suppression system and shall not be any closer than 10 feet, and not farther than 20 feet from the hood. Relocate the extinguisher.
|
|
Posting of occupant load
Corrective Action Required
Fire Department- 2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Action required: Provide occupant load signage.
Action required: An occupant load of 22 shall be posted for the patio.
|
|
Type I hood - Where required
Corrective Action Required
Fire Department- 2006 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors.
Action requred: Provide hood and suppression system specifications.
|
|
Misc
Fire Department- IFC 1003.6 Means of egress continuity.
The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel.
Action required: Provide an appropriate exit door/hardware, sign, emergency light, and landing from the patio to provide a continuous means of egress.
Action required 12/30: The occupant load of the patio is not to exceed 22. It is not required to have an exit sign on the exterior. The occupant load of the patio has been included in the total occupant load of the space.
|
|
|
Internal Plan Review (Res)
|
Rejected
|
01/07/2011
|
01/06/2011
|
|
Mike Weisenborn
|
|
|
Building Plan Review
|
Rejected
|
01/07/2011
|
01/06/2011
|
|
Mike Weisenborn
|
|
Misc
Codes Administration - For the Health Department permit approval contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Plan approval is required by the City of Lee's Summit prior to issuance of any type of permit.
Action Required - Provide documentation of approval.
|
|
Misc
Corrective Action Required
Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Action required - This comment is for information purposes.
|
|
Engineered truss package
Corrective Action Required
Copies of the engineered truss package were not provided at the time of permit application.
Action required - Provide two (2) copies of the engineered truss package which have been sealed and signed by an engineer licensed in the State of Missouri. This information is not required for permit approval or issuance but shall be provided prior to inspection.
|
|
Bldg - Doors - Size of doors
2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches.
Action required - Doors 10, 11, 12 and 13 do not meet this requirement. Make needed corrections.
Corrections have been made.
|
|
Misc
The plans do not indicate what hardware each door will get.
Action required - Provide door hardware information, including closers, for each door.
Addition information has been provided.
|
|
Misc
Corrective Action Required
Information on the hoods to be installed has not been provided.
Action required - Provide specifications and installation details for the hoods, ducts, exhaust and make-up air systems. This shall include the information clearances to combustibles, how the equipment will be supported and air calculations.
Specifications on the hoods and make-up air systems will be a deferred submittal.
|
|
Mech - Outdoor air required
Corrective Action Required
2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Action required - Provide calculations.
Information for unit F-3 has not been provided. Provide additional informaiton.
|
|
Misc
Corrective Action Required
2006 IMC 507.2.2 - Type II hoods. Type II hoods shall be installed where cooking or dishwashing appliances produce heat, steam, or products of combustion and do not produce grease or smoke, such as steamers, kettles, pasta cookers and dishwashing machines.
Action required - Show how this requirement will be met.
The hood location is now shown on the floor plans. Specifications will be a deferred submittal.
|
|
Misc
Corrective Action Required
A plumbing riser diagram has not been provided.
Action required - Provide a riser diagram for the waste, vent and water systems.
A riser diagram has been provided but not all the pipe sizes are indicated. Make needed corrections.
|
|
Misc
Water piping is not shown on the floor plans.
Action required - Show the water piping layout.
|
|
Bldg - Doors - Door operations
2006 IBC 1008.1.8 - Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Action required - Show how the patio doors meet this requirement.
Doors have been removed. Additional comments added on egress from the patio.
|
|
Bldg - Means of egress illumination - Emergency power
2006 IBC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas.
1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress.
2. Corridors, exit enclosures and exit passageways in building required to have two or more exits.
3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits.
4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits.
5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in building required to have two or more exits.
The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702.
Action required - Emergency lighting is not shown for the patio area. Make needed corrections.
Lighting has been added.
|
|
Accessibility - Water closet compartment - Doors
ICC/ANSI A117.1 2003 604.8.3 - Doors. Toilet compartment doors, including door hardware, shall comply with Section 404.1, except if the approach is to the latch side of the compartment door clearance between the door side of the stall any obstruction shall be 42 inches minimum. Doors shall be located in the front partition or in the side wall or partition farthest from the water closet. Where located in the front partition, the door opening shall be 4 inches maximum from the side wall or portion farthest from the water closet. Where located in the side wall or partition, the door opening shall be 4 inches maximum from the front partition. the door shall be self-closing. A door pull complying with Section 404.2.6 shall be placed on both sides of the door near the latch. Toilet compartment doors shall not swing into the required minimum area of the compartment.
Action required - The door to the accessible men's stall is shown swinging into the clear floor space. Make needed corrections.
Corrections have been made.
|
|
Misc
The door identifies is missing on Sheet A-1.
Action required - Add the identifier.
Corrections have been made.
|
|
Misc
Codes Administration - 2006 IPC 310.5 - Urinal partitions. Each urinal utilized by the public or employees shall occupy a separate area with walls or partitions to provide privacy. The construction of such walls or partitions shall incorporate waterproof, smooth, readily cleanable and nonabsorbent finish surfaces. The walls or partitions shall begin at a height not more than 12 inches from and extend not less than 60 inches above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the urinal a minimum of 18 inches or to a point not less than 6 inches beyond the outermost front lip of the urinal measured from the finished back wall surface, whichever is greater.
Action required - I can not tell from the plans if a partion is between the urinal and the lav. Provide additional information.
Corrections have been made.
|
|
Plumb - Backflow general 608.3
2006 IPC 608.3 - Devices, appurtenances, appliances and apparatus. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to the water supply system, shall be provided with protection against backflow and contamination of the water supply system. Water pumps, filters, softeners, tanks and all other appliances and devices that handle or treat potable water shall be protected against contamination.
Action required - Show how this requirement will be met.
Notes have been added to Sheet A-4.
|
|
Plumb - Backflow on beverage dispensers
2006 IPC 608.16.1 - Beverage dispensers. The water supply connection to beverage dispensers shall be protected against backflow by a backflow preventer conforming to ASSE 1022, CSA B64.3.1 or by an airgap. The backflow preventer device and the piping downstream therefrom shall not be affected by carbon dioxide gas.
Action required - Show how this requirement will be met.
Notes have been added to Sheet A-4.
|
|
Plumb - Indirect waste for food handling fixtures
Corrective Action Required
2006 IPC 802.1.1 - Food handling. Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap.
Action required - Show how this requirement will be met.
I am unable to locate this note.
|
|
Misc
Sheet P-1 shows 2 water service entrance diagrams and one appears to be for the fire line. I beleive the backflow for the fire line will be located on the exterior of the building.
Action required - Make needed corrections.
|
|
Misc
An electric panel schedule is not provided.
Action required - Provide a schedule for the electrical panel.
|
|
Bldg - Glazing - Human impact loads
Codes Administration - 2003 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4.
Action required - Indicate locations of required safety glass on the plans.
Notes have been added.
|
|
Misc
2006 IPC 409.2 - Water connection. The water supply to a dishwashing machine shall be protected against backflow by an air gap or backflow preventer in accordance with Section 608.
Action required - Show how this requirement will be met.
Notes have been added.
|
|
Misc
2006 IMC 1003.3.1 - Grease interceptors and automatic grease removal devices required. A grease interceptor or automatic grease removal device shall be required to receive the drainage from fixtures and equipment with grease-laden waste located in food preparation areas, such as in restaurants, hotel kitchens, hospitals, school kitchens, bars, factory cafeterias and clubs. Fixtures and equipment shall include pot sinks, prerinse sinks; soup kettles or similar devices; wok stations; floor drains or sinks into which kettles are drained; automatic hood wash units and dishwashers without prerinse sinks. Grease interceptors and automatic grease removal devices shall receive waste only from fixtures and equipment that allow fats, oils or grease to be discharged.
Action required - Make needed correction.
|
|
Misc
2006 IMC 1003.3.2 - Food waste grinders. Where food waste grinders connect to grease interceptors, a solids interceptor shall separate the discharge before connecting to the grease interceptor. Solids interceptors and grease interceptors shall be sized and rated for the discharge of the food waste grinder. Emulsifiers, chemicals enzymes and bacteria shall not discharge into the food waste grinder.
Action required - Provide additional information.
|
|
Misc
Notes for the interceptor are provided but they are not indicated on the detail.
Action required - Make needed corrections.
|
|
Misc
Corrective Action Required
Egress from the patio area shall not be through the building.
Action required - Provide an exterior means of egress from the patio area. If a latching device is provided on the gate, hardware shall meet the standard requirments.
|
|
Screening - Rooftop equipment
Corrective Action Required
Planning and Development - Commercial businesses located along existing public streets shall be subject to the following design standards: a. buildings shall be designed with four (4) sided architecture, the same level of finish on all sides (no "back"); b. rooftop or ground-level mechanical equipment shall be totally screened from view by using either parapet walls at the same height of the mechanical units for rooftop mounts or by providing screening for ground mounted units acceptable to the Director; c. Wherever possible, parking areas and pedestrian walks shall connect internally to parking areas and pedestrian walks of existing adjoining businesses. Provisions shall be make for future connections to adjoining property not yet developed or redeveloped.
Action required - Provide details for screening of the rooftop equipment.
|
|
Mech - Clearance for Type I hood
Corrective Action Required
2003 IMC 507.9 - Clearance for Type I hood. A Type I hood shall be installed with a clearance to combustibles of not less than 18 inches (457 mm).
Exception: Clearance shall not be required from gypsum wallboard attached to noncombustible structures provided that a smooth, cleanable, nonabsorbent and noncombustible material is installed between the hood and the gypsum wallboard over an area extending not less than 18 inches (457 mm) in all directions from the hood.
Action required - A type one hood can not be located within of combustible framing. Make needed corrections.
|
|
|
Final Development Plan Review
|
Approved
|
01/10/2011
|
01/04/2011
|
|
Mike Weisenborn
|
|
|
Fire Plan Review
|
Rejected
|
01/07/2011
|
12/30/2010
|
|
Jim Eden
|
|
Misc
Fire Department- IFC 903.3.7 Fire department connections.
The location of fire department connections shall be approved by the fire code official. connections shall be 4 inch Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the fire code official.
Action required: Provide a fire hydrant within 100' of the FDC.
Action required 12/30: The FDC will be on a pedestal located at the street. Provide a detail for the Backflow /FDC assembly.
|
|
Construction documents - Fire protection systems
Corrective Action Required
Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Action required: Provide shop drawings for review and approval.
|
|
Construction documents for fire alarm systems
Corrective Action Required
Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Action required: Provide shop drawings for review and approval. Interior alarm notification appliances and monitoring are required.
|
|
Knox box required
Corrective Action Required
Fire Department- 2006 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official.
Action required 12/30: Obtain a Knox application from the fire department. The Knox box shall be mounted 6' AFF below the exterior horn/strobe for the sprinkler system.
|
|
Address numbers required
Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Action required: Post address. verified at inspection.
|
|
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
Fire Department- 2006 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
Action required: Provide a K class extinguisher under the hood system manual pull station with instructions in english and the predominate language.
Action required 12/30: The K Class extinguisher shall be located under the manual pull station for the hood suppression system and shall not be any closer than 10 feet, and not farther than 20 feet from the hood. Relocate the extinguisher.
|
|
Portable fire extinguishers - conspicuous locations
Fire Department- 2006 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.
Action required: Provide a minimum of two 2A:10B:C fire extinguishers.
|
|
Posting of occupant load
Corrective Action Required
Fire Department- 2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Action required: Provide occupant load signage.
Action required: An occupant load of 22 shall be posted for the patio.
|
|
Type I hood - Where required
Corrective Action Required
Fire Department- 2006 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors.
Action requred: Provide hood and suppression system specifications.
|
|
Unlawful to occupancy
Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
For information only.
|
|
Installation acceptance testing
Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Action required: Call (816) 969-1300 to schedule testing.
|
|
Misc
Fire Department- IFC 1003.6 Means of egress continuity.
The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel.
Action required: Provide an appropriate exit door/hardware, sign, emergency light, and landing from the patio to provide a continuous means of egress.
Action required 12/30: The occupant load of the patio is not to exceed 22. It is not required to have an exit sign on the exterior. The occupant load of the patio has been included in the total occupant load of the space.
|
|
Misc
Fire Department-1008.1.9 Panic and fire exit hardware.
Where panic and fire exit hardware is installed, it shall comply with the following:
1.The actuating portion of the releasing device shall extend at least one-half of the door leaf width.
2.The maximum unlatching force shall not exceed 15 pounds (67 N).
Each door in a means of egress from a Group A or E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware.
Exception: A main exit of a Group A occupancy in compliance with Section 1008.1.8.3, Item 2.
Action required : Provide appropriate door hardware.
|
|
|
Internal Plan Review (Res)
|
Rejected
|
|
12/08/2010
|
|
Mike Weisenborn
|
|
|
Building Plan Review
|
Rejected
|
12/08/2010
|
12/08/2010
|
|
Mike Weisenborn
|
|
Misc
Corrective Action Required
Codes Administration - For the Health Department permit approval contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Plan approval is required by the City of Lee's Summit prior to issuance of any type of permit.
Action Required - Provide documentation of approval.
|
|
Misc
Corrective Action Required
Codes Administration - For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division at 816-881-4455. Occupancy approval is required by the City of Lee's Summit prior to issuance of any type of occupancy.
Action required - This comment is for information purposes.
|
|
Engineered truss package
Corrective Action Required
Copies of the engineered truss package were not provided at the time of permit application.
Action required - Provide two (2) copies of the engineered truss package which have been sealed and signed by an engineer licensed in the State of Missouri. This information is not required for permit approval or issuance but shall be provided prior to inspection.
|
|
Bldg - Doors - Size of doors
Corrective Action Required
2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches.
Action required - Doors 10, 11, 12 and 13 do not meet this requirement. Make needed corrections.
|
|
Misc
Corrective Action Required
The plans do not indicate what hardware each door will get.
Action required - Provide door hardware information, including closers, for each door.
|
|
Misc
Corrective Action Required
Information on the hoods to be installed has not been provided.
Action required - Provide specifications and installation details for the hoods, ducts, exhaust and make-up air systems. This shall include the information clearances to combustibles, how the equipment will be supported and air calculations.
|
|
Mech - Outdoor air required
Corrective Action Required
2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Action required - Provide calculations.
|
|
Misc
Corrective Action Required
2006 IMC 507.2.2 - Type II hoods. Type II hoods shall be installed where cooking or dishwashing appliances produce heat, steam, or products of combustion and do not produce grease or smoke, such as steamers, kettles, pasta cookers and dishwashing machines.
Action required - Show how this requirement will be met.
|
|
Misc
Corrective Action Required
A plumbing riser diagram has not been provided.
Action required - Provide a riser diagram for the waste, vent and water systems.
|
|
Misc
Corrective Action Required
Water piping is not shown on the floor plans.
Action required - Show the water piping layout.
|
|
Bldg - Doors - Door operations
Corrective Action Required
2006 IBC 1008.1.8 - Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Action required - Show how the patio doors meet this requirement.
|
|
Bldg - Means of egress illumination - Emergency power
Corrective Action Required
2006 IBC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas.
1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress.
2. Corridors, exit enclosures and exit passageways in building required to have two or more exits.
3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits.
4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits.
5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in building required to have two or more exits.
The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702.
Action required - Emergency lighting is not shown for the patio area. Make needed corrections.
|
|
Accessibility - Water closet compartment - Doors
Corrective Action Required
ICC/ANSI A117.1 2003 604.8.3 - Doors. Toilet compartment doors, including door hardware, shall comply with Section 404.1, except if the approach is to the latch side of the compartment door clearance between the door side of the stall any obstruction shall be 42 inches minimum. Doors shall be located in the front partition or in the side wall or partition farthest from the water closet. Where located in the front partition, the door opening shall be 4 inches maximum from the side wall or portion farthest from the water closet. Where located in the side wall or partition, the door opening shall be 4 inches maximum from the front partition. the door shall be self-closing. A door pull complying with Section 404.2.6 shall be placed on both sides of the door near the latch. Toilet compartment doors shall not swing into the required minimum area of the compartment.
Action required - The door to the accessible men's stall is shown swinging into the clear floor space. Make needed corrections.
|
|
Misc
Corrective Action Required
The door identifies is missing on Sheet A-1.
Action required - Add the identifier.
|
|
Misc
Corrective Action Required
Codes Administration - 2006 IPC 310.5 - Urinal partitions. Each urinal utilized by the public or employees shall occupy a separate area with walls or partitions to provide privacy. The construction of such walls or partitions shall incorporate waterproof, smooth, readily cleanable and nonabsorbent finish surfaces. The walls or partitions shall begin at a height not more than 12 inches from and extend not less than 60 inches above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the urinal a minimum of 18 inches or to a point not less than 6 inches beyond the outermost front lip of the urinal measured from the finished back wall surface, whichever is greater.
Action required - I can not tell from the plans if a partion is between the urinal and the lav. Provide additional information.
|
|
Plumb - Backflow general 608.3
Corrective Action Required
2006 IPC 608.3 - Devices, appurtenances, appliances and apparatus. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to the water supply system, shall be provided with protection against backflow and contamination of the water supply system. Water pumps, filters, softeners, tanks and all other appliances and devices that handle or treat potable water shall be protected against contamination.
Action required - Show how this requirement will be met.
|
|
Plumb - Backflow on beverage dispensers
Corrective Action Required
2006 IPC 608.16.1 - Beverage dispensers. The water supply connection to beverage dispensers shall be protected against backflow by a backflow preventer conforming to ASSE 1022, CSA B64.3.1 or by an airgap. The backflow preventer device and the piping downstream therefrom shall not be affected by carbon dioxide gas.
Action required - Show how this requirement will be met.
|
|
Plumb - Indirect waste for food handling fixtures
Corrective Action Required
2006 IPC 802.1.1 - Food handling. Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap.
Action required - Show how this requirement will be met.
|
|
Misc
Corrective Action Required
Sheet P-1 shows 2 water service entrance diagrams and one appears to be for the fire line. I beleive the backflow for the fire line will be located on the exterior of the building.
Action required - Make needed corrections.
|
|
Misc
Corrective Action Required
An electric panel schedule is not provided.
Action required - Provide a schedule for the electrical panel.
|
|
Bldg - Glazing - Human impact loads
Corrective Action Required
Codes Administration - 2003 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4.
Action required - Indicate locations of required safety glass on the plans.
|
|
Misc
Corrective Action Required
2006 IPC 409.2 - Water connection. The water supply to a dishwashing machine shall be protected against backflow by an air gap or backflow preventer in accordance with Section 608.
Action required - Show how this requirement will be met.
|
|
Misc
Corrective Action Required
2006 IMC 1003.3.1 - Grease interceptors and automatic grease removal devices required. A grease interceptor or automatic grease removal device shall be required to receive the drainage from fixtures and equipment with grease-laden waste located in food preparation areas, such as in restaurants, hotel kitchens, hospitals, school kitchens, bars, factory cafeterias and clubs. Fixtures and equipment shall include pot sinks, prerinse sinks; soup kettles or similar devices; wok stations; floor drains or sinks into which kettles are drained; automatic hood wash units and dishwashers without prerinse sinks. Grease interceptors and automatic grease removal devices shall receive waste only from fixtures and equipment that allow fats, oils or grease to be discharged.
Action required - Make needed correction.
|
|
Misc
Corrective Action Required
2006 IMC 1003.3.2 - Food waste grinders. Where food waste grinders connect to grease interceptors, a solids interceptor shall separate the discharge before connecting to the grease interceptor. Solids interceptors and grease interceptors shall be sized and rated for the discharge of the food waste grinder. Emulsifiers, chemicals enzymes and bacteria shall not discharge into the food waste grinder.
Action required - Provide additional information.
|
|
Misc
Corrective Action Required
Notes for the interceptor are provided but they are not indicated on the detail.
Action required - Make needed corrections.
|
|
|
License Tax Codes
|
Approved
|
12/08/2010
|
12/08/2010
|
|
Mike Weisenborn
|
|
|
Fire Plan Review
|
Rejected
|
12/08/2010
|
11/24/2010
|
|
Jim Eden
|
|
Misc
Corrective Action Required
Fire Department- IFC 903.3.7 Fire department connections.
The location of fire department connections shall be approved by the fire code official. connections shall be 4 inch Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the fire code official.
Action required: Provide a fire hydrant within 100' of the FDC.
|
|
Construction documents - Fire protection systems
Corrective Action Required
Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Action required: Provide shop drawings for review and approval.
|
|
Construction documents for fire alarm systems
Corrective Action Required
Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Action required: Provide shop drawings for review and approval. Interior alarm notification appliances and monitoring are required.
|
|
Knox box required
Corrective Action Required
Fire Department- 2006 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official.
Action required: Obtain a Knox application from the fire department. The Knox box shall be mounted 6' AFF over the FDC.
|
|
Address numbers required
Corrective Action Required
Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Action required: Post address. verified at inspection.
|
|
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
Fire Department- 2006 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
Action required: Provide a K class extinguisher under the hood system manual pull station with instructions in english and the predominate language.
|
|
Portable fire extinguishers - conspicuous locations
Corrective Action Required
Fire Department- 2006 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.
Action required: Provide a minimum of two 2A:10B:C fire extinguishers.
|
|
Posting of occupant load
Corrective Action Required
Fire Department- 2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Action required: Provide occupant load signage.
|
|
Type I hood - Where required
Corrective Action Required
Fire Department- 2006 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors.
Action requred: Provide hood and suppression system specifications.
|
|
Unlawful to occupancy
Corrective Action Required
Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved.
For information only.
|
|
Installation acceptance testing
Corrective Action Required
Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Action required: Call (816) 969-1300 to schedule testing.
|
|
Misc
Corrective Action Required
Fire Department- IFC 1003.6 Means of egress continuity.
The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel.
Action required: Provide an appropriate exit door/hardware, sign, emergency light, and landing from the patio to provide a continuous means of egress.
|
|
Misc
Corrective Action Required
Fire Department-1008.1.9 Panic and fire exit hardware.
Where panic and fire exit hardware is installed, it shall comply with the following:
1.The actuating portion of the releasing device shall extend at least one-half of the door leaf width.
2.The maximum unlatching force shall not exceed 15 pounds (67 N).
Each door in a means of egress from a Group A or E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware.
Exception: A main exit of a Group A occupancy in compliance with Section 1008.1.8.3, Item 2.
Action required: Provide appropriate door hardware.
|
|
|
Historical Preservation Review
|
Approved
|
07/08/2011
|
11/22/2010
|
|
Mike Weisenborn
|
|
|