Review Type |
Outcome |
Est. Completion Date |
Completed |
Engineering Review
|
Approved with Conditions
|
09/14/2022
|
09/07/2022
|
|
Nikia Chapman-Freiberger
|
|
DE C&O #11 Pavement Thickness
Corrective Action Required
Private parking lots shall follow Article 8 of the Unified Development Ordinance for pavement thickness and base requirements.
|
|
DE Contact Field Eng. Inspector
Corrective Action Required
Prior to the commencement of any construction activities, the Contractor shall contact Field Engineering Inspections at (816) 969-1200 to coordinate a preconstruction meeting / conference with the assigned Field Engineering Inspector.
|
|
DE Contact ROW Inspector
Corrective Action Required
Prior to any activities within the right-of-way that are not directly associated with a specific infrastructure or building permit, a separate right-of-way permit may be required. Contact a Right-of-Way Inspector at (816) 969-1800 to obtain the required permit.
|
|
DE Engineers Estimate
Corrective Action Required
The Engineer’s Estimate of Probable Construction Costs has been accepted for this project, and the Engineering Plan Review and Inspection Fee (which is calculated as 3% of the total infrastructure cost plus a water test inspection fee(s)), and the water tap and meter setup fee have been included. These must be paid prior to the issuance of an infrastructure permit and/or the final processing of a building permit. $74,667.42
|
|
DE Future Repair Work
Corrective Action Required
Please be aware that any future repair work to public infrastructure (e.g., water main repair, sanitary sewer repair, storm sewer repair, etc.) within public easements will not necessarily include the repair of pavement, curbing, landscaping, or other private improvements which are located within the easement.
|
|
|
Building Codes Review
|
Approved with Conditions
|
09/14/2022
|
09/07/2022
|
|
Mike Weisenborn
|
|
Miscellaneous Correction
Corrective Action Required
Information:
- Review did not include architectural plans
- 4 sided screening required for hvac equipment. If roof mounted screening must be by parapets. If ground mounted screening can be either masonry or evergreen landscaping.
7/29/22 - acknowledged in letter
|
|
|
Traffic Review
|
No Comments
|
09/14/2022
|
09/07/2022
|
|
Mike Weisenborn
|
|
|
Fire Review
|
Approved with Conditions
|
09/14/2022
|
09/07/2022
|
|
Mike Weisenborn
|
|
Code Statement
Corrective Action Required
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
|
|
|
Planning Review
|
No Comments
|
09/14/2022
|
09/07/2022
|
|
Mike Weisenborn
|
|
|
Engineering Review
|
Corrections
|
09/06/2022
|
09/06/2022
|
|
Nikia Chapman-Freiberger
|
|
Corrective Action Required
Provide an updated Engineer's opinion of probable construction costs based on the updated plans.
|
|
|
Building Codes Review
|
Approved with Conditions
|
09/06/2022
|
08/29/2022
|
|
Mike Weisenborn
|
|
Miscellaneous Correction
Corrective Action Required
Information:
- Review did not include architectural plans
- 4 sided screening required for hvac equipment. If roof mounted screening must be by parapets. If ground mounted screening can be either masonry or evergreen landscaping.
7/29/22 - acknowledged in letter
|
|
|
Traffic Review
|
No Comments
|
09/06/2022
|
08/29/2022
|
|
Mike Weisenborn
|
|
|
Fire Review
|
Approved with Conditions
|
09/06/2022
|
08/29/2022
|
|
Mike Weisenborn
|
|
Code Statement
Corrective Action Required
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
|
|
|
Planning Review
|
No Comments
|
09/06/2022
|
08/29/2022
|
|
Mike Weisenborn
|
|
|
Planning Review
|
No Comments
|
08/23/2022
|
08/24/2022
|
|
Shannon McGuire
|
|
|
Building Codes Review
|
Approved with Conditions
|
08/23/2022
|
08/23/2022
|
|
Joe Frogge
|
|
Miscellaneous Correction
Corrective Action Required
Information:
- Review did not include architectural plans
- 4 sided screening required for hvac equipment. If roof mounted screening must be by parapets. If ground mounted screening can be either masonry or evergreen landscaping.
7/29/22 - acknowledged in letter
|
|
|
Traffic Review
|
No Comments
|
08/23/2022
|
08/23/2022
|
|
Brad Cooley, P.E., RSPI
|
|
|
Fire Review
|
Approved with Conditions
|
08/23/2022
|
08/22/2022
|
|
Jim Eden
|
|
Code Statement
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
|
|
Water Supply
IFC 507.1 - An approved water supply capable of supplying the required fire flow for fire protection shall be provided to premises upon which facilities, buildings or portions of buildings are hereafter constructed or moved into or within the jurisdiction.
Action required- Per Table B105.1(2) a IIB building (47,740 sq. ft.) with a 50% reduction for an automatic sprinkler system requires 2,375 gpm fire flow for 4 hours. The information you provided on hydrant 014-183 FH provide only 1,750 gpm on a dead-end line. Indicate how fire flow will be met.
Resolved by accessing a second water supply.
|
|
|
Engineering Review
|
Corrections
|
08/23/2022
|
08/22/2022
|
|
Nikia Chapman-Freiberger
|
|
Corrective Action Required
C5.0 UTILITY PLAN:
The backflow prevention vault should be located outside of traffic areas and where surface water will not drain into it. Please review and relocate.
|
|
Corrective Action Required
C3.4 DETAILED GRADING (ADA):
Correct north arrow direction.
|
|
Corrective Action Required
C6.4 STORM LINE 100:
Staff made an oversight on the first round of comments and should have made the comment: “Review APWA 5604.5 Inverts and Pipes and revise the inverts for storm line 100 that do not meet offset requirements (manholes 102 and 103).” While the City does not regulate private storm systems, it is staff’s recommendation that APWA design criteria are met. Staff aims for consistency and to reflect similar comments previously made for manholes in storm line 300.
|
|
|
Engineering Review
|
Corrections
|
08/02/2022
|
08/02/2022
|
|
Mike Weisenborn
|
|
Corrective Action Required
General:
The grading sheets seem to have been plotted incorrectly. Please review and correct.
|
|
Corrective Action Required
C2.0 SITE PLAN:
Why do sections of curb have different hatching? If it represents something, that should be specified in the legend. Please review and revise.
|
|
Corrective Action Required
C3.0 GRADING PLAN:
What is the purpose of the berm to the north of storm structure 302 and why is it outlined? Please specify what it is on the plan set.
|
|
Corrective Action Required
C5.0 UTILITY PLAN:
Include leader callout for (SS|03) in drawing.
|
|
Corrective Action Required
C6.0 EXISTING DRAINAGE MAP:
Include existing inlet labels in legend.
|
|
Corrective Action Required
C6.7 STORM LINE 300:
Review APWA 5604.5 Inverts and Pipes. The inverts and crowns entering/existing structure 302 do not meet offset requirements.
|
|
Corrective Action Required
ENGINEER’S OPINION OF PROBABLE CONSTRUCTION COSTS:
A) Item 2 should be 2” service line to match plans. Please review and revise.
B) The following item numbers are “no fee” items and can be removed from the estimate: 3, 7, 8, 9, 23, and 24.
|
|
|
Planning Review
|
Corrections
|
08/02/2022
|
08/01/2022
|
|
Shannon McGuire
|
|
Corrective Action Required
All light fixtures on properties that do not adjoin residential uses and/or districts shall not exceed 28 feet. The proposed light poles in combination with the proposed bases exceed this standard. Please reduce the proposed fixture height.
|
|
Corrective Action Required
All vehicle parking lot areas and access drives in all zoning districts shall have a boundary constructed of straight-back Portland cement concrete curbing (CG-1) or an integral Portland cement concrete sidewalk and curb with a vertical face. Additionally, the use of curb blocks in parking areas shall be prohibited, except at the head of accessible parking spaces when they are adjacent to a pedestrian walkway with no raised curb. Please remove the curb blocks and add a CG-1 type curb to the 6-parking stall adjacent to the building, north of the ADA stalls.
|
|
Corrective Action Required
Sheet C2.0 - Staff understand that the 2010 ADA standards allow for an 11’ van accusable stall with a 5’ aisle. However, by providing 8’ stall and 8’ aisle in this location allows for 2 van accessible stalls as opposed to the 1 proposed. The 8’ aisle is staff’s preferred option.
|
|
|
Fire Review
|
Corrections
|
08/02/2022
|
08/01/2022
|
|
Jim Eden
|
|
Code Statement
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
|
|
Water Supply
Corrective Action Required
IFC 507.1 - An approved water supply capable of supplying the required fire flow for fire protection shall be provided to premises upon which facilities, buildings or portions of buildings are hereafter constructed or moved into or within the jurisdiction.
Action required- Per Table B105.1(2) a IIB building (47,740 sq. ft.) with a 50% reduction for an automatic sprinkler system requires 2,375 gpm fire flow for 4 hours. The information you provided on hydrant 014-183 FH provide only 1,750 gpm on a dead-end line. Indicate how fire flow will be met.
|
|
Fire Lanes - Marking
IFC 503.3 - Where required by the fire code official, approved signs or other approved notices or markings that include the words NO PARKING—FIRE LANE shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. The means by which fire lanes are designated shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility.
Indicate how the fire lanes will be posted.
|
|
Imposed Loads
IFC 503.2.3 - Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
Action required- The side walk portion of the fire lane shall carry the weight of a fire apparatus (75,000-pounds).
|
|
|
Building Codes Review
|
Approved with Conditions
|
08/02/2022
|
07/29/2022
|
|
Joe Frogge
|
|
Miscellaneous Correction
Specify water meter size and location. 2-1/2" taps nor 2-1/2" meters are an option. Coordinate with water department.
|
|
Miscellaneous Correction
Provide pipe material schedule.
|
|
Miscellaneous Correction
Provide engineered light pole base detail.
|
|
Miscellaneous Correction
Corrective Action Required
Information:
- Review did not include architectural plans
- 4 sided screening required for hvac equipment. If roof mounted screening must be by parapets. If ground mounted screening can be either masonry or evergreen landscaping.
7/29/22 - acknowledged in letter
|
|
|
Traffic Review
|
No Comments
|
08/02/2022
|
07/26/2022
|
|
Mike Weisenborn
|
|
|
Engineering Review
|
Corrections
|
07/12/2022
|
07/13/2022
|
|
Loic Nguinguiri, E.I.
|
|
Corrective Action Required
The planning and development department has the same contact information as codes administration (i.e. extensions Tel-1200 & Fax-1201)
|
|
Corrective Action Required
Revise general note 14, located on sheet C0.1, to state that “All construction shall follow the City of Lee’s Summit’s Design and Construction Manual”.
|
|
Corrective Action Required
On the site plan sheet, the leaders for details number 019 and construction notes 06 and 07 appear to be missing in plan view. Add/revise as necessary. A temporary (asphalt) curb will also be needed across where the pavement discontinues, by the proposed area inlet.
|
|
Corrective Action Required
Inlet protection(s) would not be needed on the north side of the northern drive. Intermediate silt fence barrier running north-south will be needed as well across the site, on sheet C4.0.
|
|
Corrective Action Required
Show on sheet C4.2 where ESC blanket/mat, or steep slope protection, will be used.
|
|
Corrective Action Required
A Backflow prevention device (BFPD) will be required along the fire line(s), between the W13 existing valve and the W15 proposed 6” tee.
|
|
Corrective Action Required
The domestic water service line must tie directly into the existing public 6” water main, not the fire hydrant leg. The size of the water tap and domestic service line will depend on the size of the proposed water meter. The size of the water meter to be used is determined by the estimated water demand for the building.
|
|
Corrective Action Required
SS03 and SS04 are out of place on sheet C5.0. SS04 is also not part of the legend. Revise, as necessary.
|
|
Corrective Action Required
Sanitary connection at SS02 must be via a 12” x 6” cut-in wye. Make sure to also label construction note SS01 in plan view of sheet C5.1.
|
|
Corrective Action Required
Show the hydraulic grade line within the storm profile views.
|
|
Corrective Action Required
While adding the sheet number within the title block of sheet C6.4, make sure to also indicate the (W) outflow elevation of storm structure 101 in profile view. Inflow elevation of structure 201 comes from the east, not the south.
|
|
Corrective Action Required
While revising the direction of the north arrow in plan view of sheet C6.5, make sure to also indicate the (N) inflow elevation of storm structure 108 in profile view.
|
|
Corrective Action Required
While revising the direction of the north arrow in plan view of sheet C6.6, correct the information for in/outflow(s) shown for both storm structures 101 and 201 in profile view. Storm structure 101 has 2 inflows and 1 outflow, while storm structure 201 has 1 outflow only.
|
|
Corrective Action Required
Inflow elevations are lower than outflow elevations on sheet C6.7. How is this system supposed to drain? Please revise. Make sure to also provide adequate drop within the storm structures.
|
|
Corrective Action Required
Provide/show profile views for any roof drain line larger than 6” in diameter.
|
|
Corrective Action Required
Connection to existing storm structures X-2 and X-3 needs to be via core drilling. Show on each applicable sheet.
|
|
Corrective Action Required
Aggregate base + subgrade of both asphalt and concrete pavements must extend 1’ beyond back of curb. On sheet C7.1, revise the applicable pavement details accordingly or add a general note.
|
|
Corrective Action Required
Include the City’s construction standard details. Construction standard details are accessible through the Design & Construction manual tab located on the City’s website. Include all the ESC, water, sanitary, storm and pavement construction details that apply to the current project.
|
|
Corrective Action Required
Only ornamental tree varieties are allowed within public easements. Review and verify that the landscape plan meets this requirement.
|
|
Corrective Action Required
Please provide a SWPPP report and a Missouri DNR permit.
|
|
Corrective Action Required
Please provide an Engineer’s Opinion of Probable Construction Cost (EOOPCC) sheet.
|
|
|
Fire Review
|
Corrections
|
07/12/2022
|
07/13/2022
|
|
Jim Eden
|
|
Code Statement
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
|
|
Water Supply
Corrective Action Required
IFC 507.1 - An approved water supply capable of supplying the required fire flow for fire protection shall be provided to premises upon which facilities, buildings or portions of buildings are hereafter constructed or moved into or within the jurisdiction.
|
|
Fire Lanes - Marking
Corrective Action Required
IFC 503.3 - Where required by the fire code official, approved signs or other approved notices or markings that include the words NO PARKING—FIRE LANE shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. The means by which fire lanes are designated shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility.
Indicate how the fire lanes will be posted.
|
|
Imposed Loads
Corrective Action Required
IFC 503.2.3 - Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
Action required- The side walk portion of the fire lane shall carry the weight of a fire apparatus (75,000-pounds).
|
|
|
Planning Review
|
Corrections
|
07/12/2022
|
07/13/2022
|
|
Shannon McGuire
|
|
Corrective Action Required
Please provide details on the proposed parking lot light poles including pole and base height.
|
|
Corrective Action Required
Will there be any ground mounted mechanical equipment? If so please provide the location, size, and type of material to be used in all screening of ground mounted mechanical equipment. Please also provide the manufacturer’s specification sheets for proposed mechanical equipment to be used.
|
|
Corrective Action Required
Please show the location, size and materials to be used in all screening of rooftop mechanical equipment. On the elevations show a dashed line indicating the roof line and rooftop mechanical equipment.
|
|
Corrective Action Required
CG-1 concrete curbing required around all parking areas and access drives in office, commercial and industrial districts. Temporary asphalt curbs may be used in areas to be expanded only as shown and approved on the development plan. Please indicate the proposed curb type on the driveway stub at the north west corner of the parking lot leading to lot 1.
|
|
Corrective Action Required
Accessible parking spaces shall have an adjacent aisle 5 feet wide, and one in every 8 accessible spaces (but no less than one) shall be adjacent to an aisle 8 feet wide and the space shall be clearly marked with a sign indicating that the space is “van accessible.” Accessible parking space aisles shall be clearly demarcated by lines painted on or otherwise applied to the parking lot surface. The ADA parking stall detail on sheet C2.0 does not meet the van accessible requirements. The adjacent van accessible aisle shall be a minimum of 8 feet wide. The ADA striping detail on sheet C7.2 shows the correct dimensions. Please update the plan sheets to meet ADA requirements.
|
|
Corrective Action Required
For any property within two miles of the airport, a Form 7460 shall be completed and submitted to the FAA, and comments received back prior to any construction.
|
|
|
Traffic Review
|
No Comments
|
07/12/2022
|
07/12/2022
|
|
Brad Cooley, P.E., RSPI
|
|
|
Building Codes Review
|
Corrections
|
07/12/2022
|
07/07/2022
|
|
Joe Frogge
|
|
Miscellaneous Correction
Corrective Action Required
Specify water meter size and location. 2-1/2" taps nor 2-1/2" meters are an option. Coordinate with water department.
|
|
Miscellaneous Correction
Corrective Action Required
Provide pipe material schedule.
|
|
Miscellaneous Correction
Corrective Action Required
Provide engineered light pole base detail.
|
|
Miscellaneous Correction
Corrective Action Required
Information:
- Review did not include architectural plans
- 4 sided screening required for hvac equipment. If roof mounted screening must be by parapets. If ground mounted screening can be either masonry or evergreen landscaping.
|
|
|