PL2022094
COBEY CREEK 2ND PLAT - Sanitary Sewer
Engineering Plan Review
Engineering Plan Review
Withdrawn
03/14/2022
JCM DEVELOPMENT LLC
Locations
Contacts
JCM DEVELOPMENT LLC, Address:1314 SW MARKET ST  
ANDERSON ENGINEERING INC, Address:941 W 141ST TERRACE SUITE A, Phone:(816) 777-0400  
Reviews
Review Type Outcome Est. Completion Date Completed
Engineering Review No Comments 07/06/2023 07/06/2023
Gene Williams, P.E.
Engineering Review Corrections 11/04/2022 11/04/2022
Gene Williams, P.E.
Engineering Review No Comments 09/15/2022 09/15/2022
Gene Williams, P.E.
Engineering Review No Comments 07/29/2022 07/29/2022
Gene Williams, P.E.
Engineering Review No Comments 05/25/2022 05/26/2022
Gene Williams, P.E.
Engineering Review Corrections 03/30/2022 03/30/2022
Gene Williams, P.E.
Corrective Action Required
03/30/2022

An exclusive sanitary sewer easement shall be established between Lot 69 and 68. Please show on the plat (comments to be provided under the Final Plat with specific language for the exclusive sanitary sewer easement). The reason behind this requirement is that Water Utiliities does not want any other utilities within this sideyard easement as it makes maintenance impossible or extremely difficult.
Corrective Action Required
03/30/2022

The same comment (above) applies to the easement between Lots 229 and 230. An exclusive sanitary sewer easement shall be required for this sideyard easement. Please see final plat comments for specific language to place on the dedication language of the plat.
Corrective Action Required
03/30/2022

A trenching and backfill detail was missing. Please ensure it shows the newer standard of 12 inches of aggegate over the top of pipe. This standard was adopted in July 2020.
Corrective Action Required
03/30/2022

A separate detail is being provided to address the issue of placing sanitary manholes within the street. Please use this as a guide for your own design, and ensure they are placed longitudinally within the drive lane to create a "diamond shape" as viewed along the driving lane. This is done purely for asthetics.
Corrective Action Required
03/30/2022

A separate MDNR construction permit shall be required. An MDNR concurrence letter shall be provided to you after the plans are deemed approvable, and is needed by the MDNR to process the permit. Little Blue Valley Sewer District (LBVSD) shall also be required to provide a concurrence letter, but they generally wait until they see the City's concurrence letter.
Hearings

There are no hearings for this planning application.

Documents & Images
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home