Summary
PRRES20242915
Building Permit - Residential
Certificate of Occupancy
DJ23 INVESTMENTS LLC
NEW SINGLE FAMILY
NEW HOUSE. UNFINISHED BASEMENT. ROOF TRUSSES - DEFERRED.
06/06/2024
06/19/2024
12/09/2024
03/04/2025
Locations
Contacts
Avital Homes, LLC, Address:7500 W 151st Street, #23100, Phone:(816) 914-7128  
DJ23 INVESTMENTS LLC, Address:7200 W 132ND ST  
Doug Jenson, Address:11010 Nora Dodge Dr, Phone:(816) 266-0685  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
CARUTHERS ELECTRICAL LLC, Address:30905 E TRUMAN RD, Phone:(816) 508-9050  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
DOUG@APGKC.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331401-Water Tap Fee $3,760.00 $3,760.00 Paid 06/19/2024
8350015-Water Meter Fee $680.46 $680.46 Paid 06/19/2024
8331507-Sanitary Sewer Development Fee $2,159.00 $2,159.00 Paid 06/19/2024
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 06/19/2024
7232302-Residential License Tax Fee $1,022.72 $1,022.72 Paid 06/19/2024
9110078-Valuation Fee New Single Family $1,421.93 $1,421.93 Paid 06/19/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 09/26/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 10/18/2024
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 02/10/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Erosion Control Inspection Residential Partial 06/10/2024
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
06/10/2024
6-10-24 Dustin A, EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. Street needs to be cleaned
Erosion Control Inspection Residential Passed 6/13/2024 6/13/2024 06/12/2024
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
06/10/2024
6-10-24 Dustin A, EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. Street needs to be cleaned 6-12-24 Dustin A, Street was cleaned up and erosion control will be installed on friday pending locates
Erosion Control Inspection Residential Partial 7/12/2024 07/12/2024
Miscellaneous Correction
Informational
07/12/2024
Erosion control is in place at the time of footing inspection. Full erosion control must be maintained until CofO
Footing Inspection - Residential Passed 7/12/2024 7/12/2024 07/12/2024
Miscellaneous Correction
Informational
07/12/2024
Engineer letter on site altered the steel pattern, width and depth of the footing
Underslab Plumbing Inspection - Residential Not Ready 7/26/2024 7/26/2024 07/26/2024
Underslab Plumbing Inspection - Residential Passed 7/30/2024 7/30/2024 07/30/2024
Erosion Control Inspection Residential Failed 7/30/2024 07/30/2024
Miscellaneous Correction
Informational
07/12/2024
Erosion control is in place at the time of footing inspection. Full erosion control must be maintained until CofO
Misc
Corrective Action Required
07/30/2024
-Erosion control must be in compliance until Full C ofO -Front and east side need to be repaired
Sewer Service Inspection - R Passed 8/9/2024 08/09/2024
Misc
Informational
08/09/2024
-Erosion control must be maintained until full. C of O
Water Service Inspection - R Passed 8/9/2024 08/09/2024
Misc
Informational
08/09/2024
-Erosion control must be maintained until full C of O
Erosion Control Inspection Residential Partial 8/16/2024 08/16/2024
Miscellaneous Correction
Resolved
08/16/2024
Erosion control is in place at the time of footing inspection. Full erosion control must be maintained until CofO
Misc
Resolved
08/16/2024
-Erosion control must be in compliance until Full C ofO -Front and east side need to be repaired
Miscellaneous Correction
Informational
08/16/2024
Full erosion control measures are in place and must be maintained until CofO
All Rough Inspection - Residential Not Ready 8/22/2024 8/22/2024 08/22/2024
Miscellaneous Correction
Corrective Action Required
08/22/2024
Portal garage sheeting inspection failed. The sheeting must go vertical enough to be attached to both top plates. I noticed this same problem last week and told the builder about it in person, but this inspection was still scheduled. Not ready fee will be added. K.Beard. 08/22/2024
All Rough Inspection - Residential Failed 8/29/2024 8/29/2024 08/29/2024
Miscellaneous Correction
Resolved
08/29/2024
Portal garage sheeting inspection failed. The sheeting must go vertical enough to be attached to both top plates. I noticed this same problem last week and told the builder about it in person, but this inspection was still scheduled. Not ready fee will be added. K.Beard. 08/22/2024
Miscellaneous Correction
Informational
08/29/2024
Garage exterior sheeting for portal passed and is okay to cover This is a partial pass only
Erosion Control Inspection Residential Partial 9/6/2024 09/06/2024
Miscellaneous Correction
Informational
08/16/2024
Full erosion control measures are in place and must be maintained until CofO
Piers/Caissons Inspection - Residential Passed 9/30/2024 9/30/2024 09/30/2024
All Rough Inspection - Residential Not Ready 10/1/2024 10/1/2024 10/01/2024
Miscellaneous Correction
Resolved
10/01/2024
Garage exterior sheeting for portal passed and is okay to cover This is a partial pass only
Miscellaneous Correction
Corrective Action Required
10/01/2024
- Gas line was not completed - Plans are not on site for inspection Not ready for inspection 10/01/24 KBEARD time 10:04am
Gas Service Inspection - Residential Passed 10/2/2024 10/2/2024 10/02/2024
All Rough Inspection - Residential Passed 10/2/2024 10/2/2024 10/02/2024
Miscellaneous Correction
Resolved
10/02/2024
- Gas line was not completed - Plans are not on site for inspection Not ready for inspection 10/01/24 KBEARD time 10:04am
Electrical Service Inspection Passed 10/2/2024 10/2/2024 10/02/2024
Suspended Slab Inspection Passed 10/11/2024 10/11/2024
Miscellaneous Correction
Informational
10/11/2024
Third party for front porch
Erosion Control Inspection Residential Partial 11/6/2024 11/06/2024
Miscellaneous Correction
Informational
09/06/2024
Full erosion control measures are in place and must be maintained until CofO
Driveway Inspection Partial 11/8/2024 11/8/2024 11/08/2024
Misc
Informational
11/08/2024
11-8-24 DP. DW was formed, aggregate compacted, approved to pour.
Sidewalk Inspection Partial 11/8/2024 11/8/2024 11/08/2024
Misc
Informational
11/08/2024
11-8-24 DP. SW was formed, aggregate compacted, cross slopes were in compliance but conditions can change. Approved to pour.
Driveway Inspection Passed 11/15/2024 11/15/2024 11/15/2024
Misc
Informational
11/08/2024
11-8-24 DP. DW was formed, aggregate compacted, approved to pour. 11-1524 Dustin A, dw is pored to city specs and slopes are in compliance. Pass
Sidewalk Inspection Partial 11/15/2024 11/15/2024 11/15/2024
Misc
Informational
11/08/2024
11-8-24 DP. SW was formed, aggregate compacted, cross slopes were in compliance but conditions can change. Approved to pour. 11-15-24 Dustin A, Cannot do final inspection due to debris on sw and forms still on
Occupancy Inspection - Codes Residential Failed 12/11/2024 12/11/2024 12/11/2024
Misc
Corrective Action Required
12/11/2024
-provide as graded plot plan -provide issued lawn irrigation permit -final grade and sod -splash blocks and sump pump discharge to extend 36” from foundation -will check water meter at time of final grade and sod, ensure 14”-18” from top of meter to well lid ring -shear off set screw at water anti siphon device in basement -laundry circuits to be AFCI and GFCI protected -
Sidewalk Inspection Passed 12/11/2024 12/11/2024 12/11/2024
Misc
Informational
11/15/2024
11-8-24 DP. SW was formed, aggregate compacted, cross slopes were in compliance but conditions can change. Approved to pour. 11-1524 Dustin A, Cannot do final inspection due to debris on sw and forms still on 12-11-24 Jamie S, SW is poured to city specs, slopes are compliance. Passed
Occupancy Inspection - Codes Residential Failed 12/18/2024 12/18/2024 12/18/2024
Misc
Resolved
12/18/2024
-provide as graded plot plan -provide issued lawn irrigation permit -final grade and sod -splash blocks and sump pump discharge to extend 36” from foundation -will check water meter at time of final grade and sod, ensure 14”-18” from top of meter to well lid ring -shear off set screw at water anti siphon device in basement -laundry circuits to be AFCI and GFCI protected -
Miscellaneous Correction
Corrective Action Required
12/18/2024
provide as graded plot plan -final grade and sod -splash blocks and sump pump discharge to extend 36” from foundation -will check water meter at time of final grade and sod, ensure 14”-18” from top of meter to well lid ring -shear off set screw at water anti siphon device in basement -water heater needs to have a lockout installed at the electrical panel
Plot Plan Inspection Failed 12/18/2024 12/18/2024
Miscellaneous Correction
Corrective Action Required
12/18/2024
As graded plot plan is required before sodding
Erosion Control Inspection Residential Partial 12/18/2024 12/18/2024
Miscellaneous Correction
Informational
11/06/2024
Full erosion control measures are in place and must be maintained until CofO
Occupancy Inspection - Codes Residential Failed 12/19/2024 12/19/2024 12/19/2024
Miscellaneous Correction
Corrective Action Required
12/18/2024
provide as graded plot plan -final grade and sod -splash blocks and sump pump discharge to extend 36” from foundation -will check water meter at time of final grade and sod, ensure 14”-18” from top of meter to well lid ring -water heater needs to have a lockout installed at the electrical panel
Occupancy Inspection - Codes Residential Ready for Temp CO 12/19/2024 12/19/2024
Miscellaneous Correction
Resolved
12/19/2024
provide as graded plot plan -final grade and sod -splash blocks and sump pump discharge to extend 36” from foundation -will check water meter at time of final grade and sod, ensure 14”-18” from top of meter to well lid ring -water heater needs to have a lockout installed at the electrical panel
Miscellaneous Correction
Corrective Action Required
12/19/2024
provide as graded plot plan -final grade and sod -splash blocks and sump pump discharge to extend 36” from foundation -will check water meter at time of final grade and sod, ensure 14”-18” from top of meter to well lid ring Passed for TCO only
Occupancy Inspection - Codes Residential Failed 12/27/2024 12/27/2024 12/27/2024
Miscellaneous Correction
Resolved
12/27/2024
provide as graded plot plan -final grade and sod -splash blocks and sump pump discharge to extend 36” from foundation -will check water meter at time of final grade and sod, ensure 14”-18” from top of meter to well lid ring Passed for TCO only
Miscellaneous Correction
Corrective Action Required
12/27/2024
-provide as graded plot plan (as graded plot plan still not uploaded) -will check water meter at time of final grade and sod, ensure 14”-18” from top of meter to well lid ring (water meter lid is blocked by sod netting) - pay $50 fee associated with this permit
Plot Plan Inspection Failed 12/27/2024 12/27/2024
Miscellaneous Correction
Corrective Action Required
12/18/2024
As graded plot plan is required before sodding (still not uploaded to the portal for inspection)
Erosion Control Inspection Residential Passed 12/27/2024 12/27/2024
Miscellaneous Correction
Resolved
12/27/2024
Full erosion control measures are in place and must be maintained until CofO
Plot Plan Inspection Failed 1/10/2025 01/10/2025
Miscellaneous Correction
Resolved
01/10/2025
As graded plot plan is required before sodding (still not uploaded to the portal for inspection)
Miscellaneous Correction
Corrective Action Required
01/10/2025
Plot plan could not be verified because snow on the lot
Occupancy Inspection - Codes Residential Failed 1/10/2025 1/10/2025 01/10/2025
Miscellaneous Correction
Resolved
01/10/2025
-provide as graded plot plan (as graded plot plan still not uploaded) -will check water meter at time of final grade and sod, ensure 14”-18” from top of meter to well lid ring (water meter lid is blocked by sod netting) - pay $50 fee associated with this permit
Miscellaneous Correction
Resolved
02/10/2025
1)Plot plan could not be verified due to snow on the lot 2)will check water meter at time of final grade and sod, ensure 14”-18” from top of meter to well lid ring (water meter lid is blocked by sod netting) (Water meter could not be located due to snow on the lot) - pay $50 fee associated with this permit (Still has a fee associated with this permit)
Miscellaneous Correction
Corrective Action Required
02/10/2025
- pay $50 fee associated with this permit
Plot Plan Inspection Passed 2/10/2025 02/10/2025
Miscellaneous Correction
Resolved
02/10/2025
Plot plan could not be verified because snow on the lot
Occupancy Inspection - Codes Residential Failed 2/10/2025 2/10/2025 02/10/2025
Miscellaneous Correction
Corrective Action Required
01/10/2025
1)Plot plan could not be verified due to snow on the lot 2)will check water meter at time of final grade and sod, ensure 14”-18” from top of meter to well lid ring (water meter lid is blocked by sod netting) (Water meter could not be located due to snow on the lot) - pay $50 fee associated with this permit (Still has a fee associated with this permit)
Occupancy Inspection - Codes Residential Full C of O 3/4/2025 3/4/2025 03/04/2025
Miscellaneous Correction
Resolved
03/04/2025
1)Plot plan could not be verified due to snow on the lot 2)will check water meter at time of final grade and sod, ensure 14”-18” from top of meter to well lid ring (water meter lid is blocked by sod netting) (Water meter could not be located due to snow on the lot) - pay $50 fee associated with this permit (Still has a fee associated with this permit)
Documents & Images
Date Uploaded File Type Document Name
06/10/2024 Letter INSPECTION SUMMARY
06/10/2024 Letter INSPECTION SUMMARY
06/12/2024 Permit Codes Residential Plan Review
06/12/2024 Letter INSPECTION SUMMARY
06/19/2024 RS 97 Permit Application Signed 6_4_24
06/19/2024 Application Form APPROVED PLANS
06/19/2024 Plot Plan APPROVED PLOT PLAN
06/19/2024 Approved Plans APPROVED TRUSS LAYOUT
06/19/2024 Permit Codes Residential Plan Review
06/19/2024 Permit DS Building Permit
06/19/2024 Receipt Receipt for transaction:2024-004949
06/27/2024 Approved Plans 6-27-24 APPROVED PLANS
07/12/2024 Letter INSPECTION SUMMARY
07/12/2024 Letter INSPECTION SUMMARY
07/15/2024 3RD Party Insp Report THIRD PARTY SUBGRADE INSPECTION REPORT
07/26/2024 Letter INSPECTION SUMMARY
07/30/2024 Letter INSPECTION SUMMARY
07/30/2024 Letter INSPECTION SUMMARY
08/09/2024 Letter INSPECTION SUMMARY
08/09/2024 Letter INSPECTION SUMMARY
08/16/2024 Letter INSPECTION SUMMARY
08/22/2024 Letter INSPECTION SUMMARY
08/29/2024 Letter INSPECTION SUMMARY
09/06/2024 Letter INSPECTION SUMMARY
09/26/2024 Receipt Receipt for transaction:2024-007960
09/30/2024 Letter INSPECTION SUMMARY
10/01/2024 Letter INSPECTION SUMMARY
10/02/2024 Letter INSPECTION SUMMARY
10/02/2024 Letter INSPECTION SUMMARY
10/02/2024 Letter INSPECTION SUMMARY
10/09/2024 2024_10_07_1800 SW Hightown Dr_LSMO_Stoop_Sealed
10/11/2024 Letter INSPECTION SUMMARY
10/18/2024 Receipt Receipt for transaction:2024-008437
11/06/2024 Letter INSPECTION SUMMARY
11/08/2024 Letter INSPECTION SUMMARY
11/08/2024 Letter INSPECTION SUMMARY
11/15/2024 Letter INSPECTION SUMMARY
11/15/2024 Letter INSPECTION SUMMARY
11/15/2024 Letter INSPECTION SUMMARY
12/11/2024 Letter INSPECTION SUMMARY
12/11/2024 Letter INSPECTION SUMMARY
12/18/2024 Letter INSPECTION SUMMARY
12/18/2024 Letter INSPECTION SUMMARY
12/18/2024 Letter INSPECTION SUMMARY
12/19/2024 Letter INSPECTION SUMMARY
12/19/2024 Letter INSPECTION SUMMARY
12/27/2024 Letter INSPECTION SUMMARY
12/27/2024 Letter INSPECTION SUMMARY
12/27/2024 Letter INSPECTION SUMMARY
01/09/2025 Plot Plan APPROVED AS BUILT PLOT PLAN
01/10/2025 Letter INSPECTION SUMMARY
01/10/2025 Letter INSPECTION SUMMARY
02/10/2025 Letter INSPECTION SUMMARY
02/10/2025 Letter INSPECTION SUMMARY
02/10/2025 Certificate/License Codes Temporary Certificate of Occupancy
02/10/2025 Receipt Receipt for transaction:2025-000865
03/04/2025 Letter Codes Final Certificate of Occupancy
03/04/2025 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home