Summary
PRRES20242598
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - UNFINISHED BASEMENT - ROOF TRUSSES STOP WORK ORDER generated on 11/22/2024 12:00 AM by username 'Dustin Agcopra'. STOP WORK ORDER removed on 12/05/2024 12:00 AM by username 'Kyle Beard'.
05/21/2024
05/22/2024
04/17/2025
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
BRUCER@SUMMITHOMESKC.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
Sanitary Sewer Development Fee $2,159.00 $2,159.00 Paid 05/22/2024
Right of Way Permit Fee $85.00 $85.00 Paid 05/22/2024
Residential Excise Tax Fee $1,022.72 $1,022.72 Paid 05/22/2024
Water Tap Fee $3,760.00 $3,760.00 Paid 05/22/2024
Water Meter Fee $680.46 $680.46 Paid 05/22/2024
Valuation Fee New Single Family $1,743.63 $1,743.63 Paid 05/22/2024
Not Ready Inspection Fee $75.00 $75.00 Paid 12/04/2024
Not Ready Inspection Fee $75.00 $75.00 Paid 12/04/2024
3rd and Subsequent Inspection Fee (Per Hour) $50.00 $50.00 Paid 12/04/2024
Temporary Occupancy Fee $50.00 $50.00 Paid 12/10/2024
Temporary Occupancy Fee $50.00 $50.00 Paid 01/13/2025
Temporary Occupancy Fee $50.00 $50.00 Paid 02/06/2025
Temporary Occupancy Fee $50.00 $50.00 Paid 02/27/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Erosion Control Inspection Residential Partial 6/28/2024 06/28/2024
Miscellaneous Correction
Informational
06/28/2024
Full erosion control measures are in place and must be maintained until CofO
Footing Inspection - Residential Passed 6/28/2024 06/28/2024
Miscellaneous Correction
Informational
06/28/2024
Footing passed by a third party
Sewer Service Inspection - R Passed 7/9/2024 7/9/2024 07/09/2024
Water Service Inspection - R Failed 7/11/2024 07/11/2024
Miscellaneous Correction
Informational
07/11/2024
PEX ran out 20 feet from the foundation Okay to cover This is a partial pass only
Water Service Inspection - R Passed 7/12/2024 07/12/2024
Miscellaneous Correction
Resolved
07/12/2024
PEX ran out 20 feet from the foundation Okay to cover This is a partial pass only
Underslab Plumbing Inspection - Residential Failed 7/22/2024 7/22/2024 07/22/2024
Miscellaneous Correction
Corrective Action Required
07/22/2024
Remove decaying wood forms from foundation
Erosion Control Inspection Residential Partial 7/22/2024 07/22/2024
Miscellaneous Correction
Resolved
07/22/2024
Full erosion control measures are in place and must be maintained until CofO
Miscellaneous Correction
Informational
07/22/2024
Full erosion control measures are in place and must be maintained until CofO
Underslab Plumbing Inspection - Residential Passed 7/23/2024 7/23/2024 07/23/2024
Miscellaneous Correction
Resolved
07/23/2024
Erosion Control Inspection Residential Failed 7/23/2024 07/23/2024
Miscellaneous Correction
Resolved
07/23/2024
Full erosion control measures are in place and must be maintained until CofO
DCM6 ESC INSP DENIED STREET CLEAN UP
Corrective Action Required
07/23/2024
- STREET CLEAN UP REQUIRED IMMEDIATELY, AND SHALL BE COMPLETED PRIOR TO REQUESTED INSPECTION(S) BEING PERFORMED. - REMOVE GRAVEL OUT OF CURB.
Erosion Control Inspection Residential Partial 8/13/2024 08/13/2024
DCM6 ESC INSP DENIED STREET CLEAN UP
Resolved
08/13/2024
- STREET CLEAN UP REQUIRED IMMEDIATELY, AND SHALL BE COMPLETED PRIOR TO REQUESTED INSPECTION(S) BEING PERFORMED. - REMOVE GRAVEL OUT OF CURB.
Miscellaneous Correction
Informational
08/13/2024
Full erosion control measures are in place and must be maintained until CofO
Erosion Control Inspection Residential Partial 8/28/2024 08/28/2024
Miscellaneous Correction
Informational
08/13/2024
Full erosion control measures are in place and must be maintained until CofO
All Rough Inspection - Residential Failed 8/28/2024 8/28/2024 08/28/2024
Miscellaneous Correction
Corrective Action Required
08/28/2024
Exterior garage portal sheeting in not nailed at blocking between studs (pages S530 in your plans) This was scheduled for a exterior garage portal inspection only
All Rough Inspection - Residential Failed 9/4/2024 9/4/2024 09/04/2024
Miscellaneous Correction
Resolved
09/04/2024
Exterior garage portal sheeting in not nailed at blocking between studs (pages S530 in your plans) This was scheduled for a exterior garage portal inspection only
Miscellaneous Correction
Informational
09/04/2024
Exterior garage portal fame inspection passed and is okay to cover. This is a partial pass only
Erosion Control Inspection Residential Partial 9/11/2024 09/11/2024
Miscellaneous Correction
Informational
08/28/2024
Full erosion control measures are in place and must be maintained until CofO
Erosion Control Inspection Residential Partial 9/27/2024 09/27/2024
Miscellaneous Correction
Informational
09/11/2024
Full erosion control measures are in place and must be maintained until CofO
All Rough Inspection - Residential Not Ready 9/27/2024 9/27/2024 09/27/2024
Miscellaneous Correction
Informational
09/04/2024
Exterior garage portal fame inspection passed and is okay to cover. This is a partial pass only
Miscellaneous Correction
Corrective Action Required
09/27/2024
House and truss plans are not on property at the time of inspection Not ready for inspection
All Rough Inspection - Residential Not Ready 10/1/2024 10/1/2024 10/01/2024
Miscellaneous Correction
Informational
09/27/2024
Exterior garage portal fame inspection passed and is okay to cover. This is a partial pass only
Miscellaneous Correction
Resolved
10/01/2024
House and truss plans are not on property at the time of inspection Not ready for inspection
Miscellaneous Correction
Corrective Action Required
10/01/2024
House and truss plans are not on property at the time of inspection. Second time Not ready for inspection 10/01/24 KBEARD time 8:51am
Gas Service Inspection - Residential Passed 10/2/2024 10/02/2024
Electrical Service Inspection Failed 10/2/2024 10/02/2024
Miscellaneous Correction
Corrective Action Required
10/02/2024
-Neutral in electrical panel is not connected -UFER is not utilized -14/2 wire in basement by HVAC in in a loop and not connected
All Rough Inspection - Residential Failed 10/2/2024 10/2/2024 10/02/2024
Miscellaneous Correction
Informational
10/01/2024
Exterior garage portal fame inspection passed and is okay to cover. This is a partial pass only
Miscellaneous Correction
Corrective Action Required
10/01/2024
House and truss plans are not on property at the time of inspection. Second time Not ready for inspection 10/01/24 KBEARD time 8:51am
Miscellaneous Correction
Corrective Action Required
10/02/2024
•Plans call for 3 inch steel columns in garage at steel Ibeam •(3) 2x4’s are not installed in garage along south and north walls •Nail garage corners to code •Fire block to of chase in garage •Truss hangers are not installed in garage above overhead garage door •Cantilever blocking is missing in one cavity above garage overhead door •Neutral is not connected in electrical panel •Fire block hole in floor above powder bathroom •Fire block 1 1/2 DWV in powder bathroom at ceiling height •Fire block top of chase in pantry •Nail pantry corner to code •One ceiling joist hangers is cut above kitchen/greatroom •Nails missing in joist hanger above basement stairwell entry •Install office LIB per plan •Nail king studs to jack studs at great room window •Truss tie downs screws are missing in stairwell •Top of stairs to upper rooms, the stair stringer beams do not rest on 1 1/2 inches of support against double 2x10’s •Nail stairwell corner to code •LGT2’s are not installed upstairs •Lateral support is not installed for trusses in attic •Nail all corners to code •Vent fans in upstairs bathrooms are not wired •Fire block top of chase in in primary bathroom •Floor joist above basement window needs joist hangers installed •Electrical panel is not bonded to the UFER •14/2 wire is looped and hanging from floor joist in the basement
All Rough Inspection - Residential Failed 10/2/2024 10/02/2024
Miscellaneous Correction
Informational
10/02/2024
Exterior garage portal fame inspection passed and is okay to cover. This is a partial pass only
Miscellaneous Correction
Corrective Action Required
10/02/2024
House and truss plans are not on property at the time of inspection. Second time Not ready for inspection 10/01/24 KBEARD time 8:51am
Miscellaneous Correction
Corrective Action Required
10/02/2024
•Plans call for 3 inch steel columns in garage at steel Ibeam •(3) 2x4’s are not installed in garage along south and north walls •Nail garage corners to code •Fire block to of chase in garage •Truss hangers are not installed in garage above overhead garage door •Cantilever blocking is missing in one cavity above garage overhead door •Neutral is not connected in electrical panel •Fire block hole in floor above powder bathroom •Fire block 1 1/2 DWV in powder bathroom at ceiling height •Fire block top of chase in pantry •Nail pantry corner to code •One ceiling joist hangers is cut above kitchen/greatroom •Nails missing in joist hanger above basement stairwell entry •Install office LIB per plan •Nail king studs to jack studs at great room window •Truss tie downs screws are missing in stairwell •Top of stairs to upper rooms, the stair stringer beams do not rest on 1 1/2 inches of support against double 2x10’s •Nail stairwell corner to code •LGT2’s are not installed upstairs •Lateral support is not installed for trusses in attic •Nail all corners to code •Vent fans in upstairs bathrooms are not wired •Fire block top of chase in in primary bathroom •Floor joist above basement window needs joist hangers installed •Electrical panel is not bonded to the UFER •14/2 wire is looped and hanging from floor joist in the basement
Miscellaneous Correction
Corrective Action Required
10/02/2024
3808 SW Ravengate. All rough •Plans call for 3 inch steel columns in garage at steel Ibeam •(3) 2x4’s are not installed in garage along south and north walls •Nail garage corners to code •Fire block to of chase in garage •Truss hangers are not installed in garage above overhead garage door •Cantilever blocking is missing in one cavity above garage overhead door •Neutral is not connected in electrical panel •Fire block hole in floor above powder bathroom •Fire block 1 1/2 DWV in powder bathroom at ceiling height •Fire block top of chase in pantry •Nail pantry corner to code •One ceiling joist hangers is cut above kitchen/greatroom •Nails missing in joist hanger above basement stairwell entry •Install office LIB per plan •Nail king studs to jack studs at great room window •Truss tie downs screws are missing in stairwell •Top of stairs to upper rooms, the stair stringer beams do not rest on 1 1/2 inches of support against double 2x10’s •Nail stairwell corner to code •LGT2’s are not installed upstairs •Lateral support is not installed for trusses in attic •Nail all corners to code •Vent fans in upstairs bathrooms are not wired •Fire block top of chase in in primary bathroom •Floor joist above basement window needs joist hangers installed •Electrical panel is not bonded to the UFER •14/2 wire is looped and hanging from floor joist in the basement Added requirements for original list •2 inches washers with a 5/8 inch bolt are required at the garage sole plate •Fasten double truss together above the primary bedroom •12/2 wire above the electrical panel is below the ceiling joist •Snow block step flashing at gable over second floor
Erosion Control Inspection Residential Partial 10/9/2024 10/09/2024
Miscellaneous Correction
Informational
09/27/2024
Full erosion control measures are in place and must be maintained until CofO
All Rough Inspection - Residential Failed 10/9/2024 10/9/2024 10/09/2024
Miscellaneous Correction
Informational
10/02/2024
Exterior garage portal fame inspection passed and is okay to cover. This is a partial pass only
Miscellaneous Correction
Corrective Action Required
10/02/2024
House and truss plans are not on property at the time of inspection. Second time Not ready for inspection 10/01/24 KBEARD time 8:51am
Miscellaneous Correction
Corrective Action Required
10/02/2024
•Plans call for 3 inch steel columns in garage at steel Ibeam •(3) 2x4’s are not installed in garage along south and north walls •Nail garage corners to code •Fire block to of chase in garage •Truss hangers are not installed in garage above overhead garage door •Cantilever blocking is missing in one cavity above garage overhead door •Neutral is not connected in electrical panel •Fire block hole in floor above powder bathroom •Fire block 1 1/2 DWV in powder bathroom at ceiling height •Fire block top of chase in pantry •Nail pantry corner to code •One ceiling joist hangers is cut above kitchen/greatroom •Nails missing in joist hanger above basement stairwell entry •Install office LIB per plan •Nail king studs to jack studs at great room window •Truss tie downs screws are missing in stairwell •Top of stairs to upper rooms, the stair stringer beams do not rest on 1 1/2 inches of support against double 2x10’s •Nail stairwell corner to code •LGT2’s are not installed upstairs •Lateral support is not installed for trusses in attic •Nail all corners to code •Vent fans in upstairs bathrooms are not wired •Fire block top of chase in in primary bathroom •Floor joist above basement window needs joist hangers installed •Electrical panel is not bonded to the UFER •14/2 wire is looped and hanging from floor joist in the basement
Miscellaneous Correction
Corrective Action Required
10/02/2024
3808 SW Ravengate. All rough •Plans call for 3 inch steel columns in garage at steel Ibeam •(3) 2x4’s are not installed in garage along south and north walls •Nail garage corners to code •Fire block to of chase in garage •Truss hangers are not installed in garage above overhead garage door •Cantilever blocking is missing in one cavity above garage overhead door •Neutral is not connected in electrical panel •Fire block hole in floor above powder bathroom •Fire block 1 1/2 DWV in powder bathroom at ceiling height •Fire block top of chase in pantry •Nail pantry corner to code •One ceiling joist hangers is cut above kitchen/greatroom •Nails missing in joist hanger above basement stairwell entry •Install office LIB per plan •Nail king studs to jack studs at great room window •Truss tie downs screws are missing in stairwell •Top of stairs to upper rooms, the stair stringer beams do not rest on 1 1/2 inches of support against double 2x10’s •Nail stairwell corner to code •LGT2’s are not installed upstairs •Lateral support is not installed for trusses in attic •Nail all corners to code •Vent fans in upstairs bathrooms are not wired •Fire block top of chase in in primary bathroom •Floor joist above basement window needs joist hangers installed •Electrical panel is not bonded to the UFER •14/2 wire is looped and hanging from floor joist in the basement Added requirements for original list •2 inches washers with a 5/8 inch bolt are required at the garage sole plate •Fasten double truss together above the primary bedroom •12/2 wire above the electrical panel is below the ceiling joist •Snow block step flashing at gable over second floor
Miscellaneous Correction
Corrective Action Required
10/09/2024
3808 SW Ravengate. All rough (2) • •LGT2’s are not installed upstairs •Floor joist above basement window needs joist hangers installed (missing nails) •Fire block at electrical bonding wire from panel to UFER at bottom plate in garage Added requirements for original list •2 inches washers with a 5/8 inch bolt are required at the garage sole plate •Fasten double truss together above the primary bedroom •12/2 wire above the electrical panel is below the ceiling joist •Snow block step flashing at gable over second floor
Electrical Service Inspection Passed 10/11/2024 10/11/2024
Miscellaneous Correction
Resolved
10/11/2024
-Neutral in electrical panel is not connected -UFER is not utilized -14/2 wire in basement by HVAC in in a loop and not connected
All Rough Inspection - Residential Failed 10/11/2024 10/11/2024 10/11/2024
Miscellaneous Correction
Informational
10/09/2024
Exterior garage portal fame inspection passed and is okay to cover. This is a partial pass only
Miscellaneous Correction
Corrective Action Required
10/09/2024
House and truss plans are not on property at the time of inspection. Second time Not ready for inspection 10/01/24 KBEARD time 8:51am
Miscellaneous Correction
Corrective Action Required
10/09/2024
•Plans call for 3 inch steel columns in garage at steel Ibeam •(3) 2x4’s are not installed in garage along south and north walls •Nail garage corners to code •Fire block to of chase in garage •Truss hangers are not installed in garage above overhead garage door •Cantilever blocking is missing in one cavity above garage overhead door •Neutral is not connected in electrical panel •Fire block hole in floor above powder bathroom •Fire block 1 1/2 DWV in powder bathroom at ceiling height •Fire block top of chase in pantry •Nail pantry corner to code •One ceiling joist hangers is cut above kitchen/greatroom •Nails missing in joist hanger above basement stairwell entry •Install office LIB per plan •Nail king studs to jack studs at great room window •Truss tie downs screws are missing in stairwell •Top of stairs to upper rooms, the stair stringer beams do not rest on 1 1/2 inches of support against double 2x10’s •Nail stairwell corner to code •LGT2’s are not installed upstairs •Lateral support is not installed for trusses in attic •Nail all corners to code •Vent fans in upstairs bathrooms are not wired •Fire block top of chase in in primary bathroom •Floor joist above basement window needs joist hangers installed •Electrical panel is not bonded to the UFER •14/2 wire is looped and hanging from floor joist in the basement
Miscellaneous Correction
Corrective Action Required
10/09/2024
3808 SW Ravengate. All rough •Plans call for 3 inch steel columns in garage at steel Ibeam •(3) 2x4’s are not installed in garage along south and north walls •Nail garage corners to code •Fire block to of chase in garage •Truss hangers are not installed in garage above overhead garage door •Cantilever blocking is missing in one cavity above garage overhead door •Neutral is not connected in electrical panel •Fire block hole in floor above powder bathroom •Fire block 1 1/2 DWV in powder bathroom at ceiling height •Fire block top of chase in pantry •Nail pantry corner to code •One ceiling joist hangers is cut above kitchen/greatroom •Nails missing in joist hanger above basement stairwell entry •Install office LIB per plan •Nail king studs to jack studs at great room window •Truss tie downs screws are missing in stairwell •Top of stairs to upper rooms, the stair stringer beams do not rest on 1 1/2 inches of support against double 2x10’s •Nail stairwell corner to code •LGT2’s are not installed upstairs •Lateral support is not installed for trusses in attic •Nail all corners to code •Vent fans in upstairs bathrooms are not wired •Fire block top of chase in in primary bathroom •Floor joist above basement window needs joist hangers installed •Electrical panel is not bonded to the UFER •14/2 wire is looped and hanging from floor joist in the basement Added requirements for original list •2 inches washers with a 5/8 inch bolt are required at the garage sole plate •Fasten double truss together above the primary bedroom •12/2 wire above the electrical panel is below the ceiling joist •Snow block step flashing at gable over second floor
Miscellaneous Correction
Corrective Action Required
10/09/2024
3808 SW Ravengate. All rough (2) • •LGT2’s are not installed upstairs •Floor joist above basement window needs joist hangers installed (missing nails) •Fire block at electrical bonding wire from panel to UFER at bottom plate in garage Added requirements for original list •2 inches washers with a 5/8 inch bolt are required at the garage sole plate •Fasten double truss together above the primary bedroom •12/2 wire above the electrical panel is below the ceiling joist •Snow block step flashing at gable over second floor
All Rough Inspection - Residential Passed 10/15/2024 10/15/2024 10/15/2024
Miscellaneous Correction
Resolved
10/15/2024
Exterior garage portal fame inspection passed and is okay to cover. This is a partial pass only
Miscellaneous Correction
Resolved
10/15/2024
House and truss plans are not on property at the time of inspection. Second time Not ready for inspection 10/01/24 KBEARD time 8:51am
Miscellaneous Correction
Resolved
10/15/2024
•Plans call for 3 inch steel columns in garage at steel Ibeam •(3) 2x4’s are not installed in garage along south and north walls •Nail garage corners to code •Fire block to of chase in garage •Truss hangers are not installed in garage above overhead garage door •Cantilever blocking is missing in one cavity above garage overhead door •Neutral is not connected in electrical panel •Fire block hole in floor above powder bathroom •Fire block 1 1/2 DWV in powder bathroom at ceiling height •Fire block top of chase in pantry •Nail pantry corner to code •One ceiling joist hangers is cut above kitchen/greatroom •Nails missing in joist hanger above basement stairwell entry •Install office LIB per plan •Nail king studs to jack studs at great room window •Truss tie downs screws are missing in stairwell •Top of stairs to upper rooms, the stair stringer beams do not rest on 1 1/2 inches of support against double 2x10’s •Nail stairwell corner to code •LGT2’s are not installed upstairs •Lateral support is not installed for trusses in attic •Nail all corners to code •Vent fans in upstairs bathrooms are not wired •Fire block top of chase in in primary bathroom •Floor joist above basement window needs joist hangers installed •Electrical panel is not bonded to the UFER •14/2 wire is looped and hanging from floor joist in the basement
Miscellaneous Correction
Resolved
10/15/2024
3808 SW Ravengate. All rough •Plans call for 3 inch steel columns in garage at steel Ibeam •(3) 2x4’s are not installed in garage along south and north walls •Nail garage corners to code •Fire block to of chase in garage •Truss hangers are not installed in garage above overhead garage door •Cantilever blocking is missing in one cavity above garage overhead door •Neutral is not connected in electrical panel •Fire block hole in floor above powder bathroom •Fire block 1 1/2 DWV in powder bathroom at ceiling height •Fire block top of chase in pantry •Nail pantry corner to code •One ceiling joist hangers is cut above kitchen/greatroom •Nails missing in joist hanger above basement stairwell entry •Install office LIB per plan •Nail king studs to jack studs at great room window •Truss tie downs screws are missing in stairwell •Top of stairs to upper rooms, the stair stringer beams do not rest on 1 1/2 inches of support against double 2x10’s •Nail stairwell corner to code •LGT2’s are not installed upstairs •Lateral support is not installed for trusses in attic •Nail all corners to code •Vent fans in upstairs bathrooms are not wired •Fire block top of chase in in primary bathroom •Floor joist above basement window needs joist hangers installed •Electrical panel is not bonded to the UFER •14/2 wire is looped and hanging from floor joist in the basement Added requirements for original list •2 inches washers with a 5/8 inch bolt are required at the garage sole plate •Fasten double truss together above the primary bedroom •12/2 wire above the electrical panel is below the ceiling joist •Snow block step flashing at gable over second floor
Miscellaneous Correction
Resolved
10/15/2024
3808 SW Ravengate. All rough (2) • •LGT2’s are not installed upstairs •Floor joist above basement window needs joist hangers installed (missing nails) •Fire block at electrical bonding wire from panel to UFER at bottom plate in garage Added requirements for original list •2 inches washers with a 5/8 inch bolt are required at the garage sole plate •Fasten double truss together above the primary bedroom •12/2 wire above the electrical panel is below the ceiling joist •Snow block step flashing at gable over second floor
Erosion Control Inspection Residential Partial 10/15/2024 10/15/2024
Miscellaneous Correction
Informational
10/09/2024
Full erosion control measures are in place and must be maintained until CofO
Driveway Inspection Partial 10/28/2024 10/28/2024 10/28/2024
Misc
Informational
10/28/2024
10-28-24 Dustin A, dw is formed and compacted, approved to pour
Sidewalk Inspection Partial 10/28/2024 10/28/2024 10/28/2024
Misc
Informational
10/28/2024
10-28-24 Dustin A, sw is formed and compacted and slopes are in compliance. Approved to pour .
Sidewalk Inspection Passed 11/4/2024 11/4/2024 11/04/2024
Misc
Informational
10/28/2024
10-28-24 Dustin A, sw is formed and compacted and slopes are in compliance. Approved to pour . 11-4-24 Dustin A, sw poured to city specs. Passed
Driveway Inspection Passed 11/4/2024 11/4/2024 11/04/2024
Misc
Informational
10/28/2024
10-28-24 Dustin A, dw is formed and compacted, approved to pour 11-4-24 Dustin A, Dw poured to city specs, Passed
Erosion Control Inspection Residential Failed 11/19/2024 11/19/2024 11/19/2024
Miscellaneous Correction
Informational
10/15/2024
Full erosion control measures are in place and must be maintained until CofO
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
11/19/2024
11-19-24 Dustin A, remove restroom from drive. EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Erosion Control Inspection Residential Failed - Stop Work 11/22/2024 11/22/2024 11/22/2024
Miscellaneous Correction
Informational
11/19/2024
Full erosion control measures are in place and must be maintained until CofO
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
11/19/2024
11-19-24 Dustin A, remove restroom from drive. EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. 11-22-24 Dustin A, Restroom still there
Erosion Control Inspection Residential Partial 12/5/2024 12/5/2024 12/05/2024
Miscellaneous Correction
Informational
11/22/2024
Full erosion control measures are in place and must be maintained until CofO
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
11/22/2024
11-19-24 Dustin A, remove restroom from drive. EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. 11-22-24 Dustin A, Restroom still there
Miscellaneous Correction
Informational
12/05/2024
Erosion control is in place at the time of inspection
Occupancy Inspection - Codes Residential Failed 12/6/2024 12/6/2024 12/06/2024
Misc
Corrective Action Required
12/06/2024
- Final grading and sod - Land sewer trace wire at grade - Provide splash pads at down spouts - Handrail at front door stairs are too low( to be 34-38”)
Plot Plan Inspection Passed 12/6/2024 12/06/2024
Occupancy Inspection - Codes Residential Ready for Temp CO 12/10/2024 12/10/2024 12/10/2024
Misc
Corrective Action Required
12/06/2024
- Final grading and sod - Land sewer trace wire at grade - Provide splash pads at down spouts
Occupancy Inspection - Codes Residential Ready for Temp CO 1/13/2025 01/13/2025
Misc
Resolved
01/13/2025
- Final grading and sod - Land sewer trace wire at grade - Provide splash pads at down spouts
Miscellaneous Correction
Corrective Action Required
01/13/2025
- Final grading and sod - Land sewer trace wire at grade - Provide splash pads at down spouts City requested a TCO extension form and builder replied TCO extended until 02/10/25
Occupancy Inspection - Codes Residential Ready for Temp CO 2/6/2025 02/06/2025
Miscellaneous Correction
Resolved
02/06/2025
- Final grading and sod - Land sewer trace wire at grade - Provide splash pads at down spouts City requested a TCO extension form and builder replied TCO extended until 02/10/25
Miscellaneous Correction
Corrective Action Required
02/06/2025
- Sod - Land sewer trace wire at grade - Provide splash pads at down spouts TCO extension submitted TCO extended until 03/10/2025
Occupancy Inspection - Codes Residential Ready for Temp CO 2/27/2025 02/27/2025
Miscellaneous Correction
Resolved
02/27/2025
- Sod - Land sewer trace wire at grade - Provide splash pads at down spouts TCO extension submitted TCO extended until 03/10/2025
Miscellaneous Correction
Corrective Action Required
02/27/2025
- Sod - Land sewer trace wire at grade - Provide splash pads at down spouts TCO extension submitted (Weather delays sighted)
Erosion Control Inspection Residential Passed 4/11/2025 04/11/2025
Miscellaneous Correction
Resolved
04/11/2025
Full erosion control measures are in place and must be maintained until CofO
DCM3 ESC REQUIRED 2 DAY
Resolved
04/11/2025
11-19-24 Dustin A, remove restroom from drive. EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. 11-22-24 Dustin A, Restroom still there
Miscellaneous Correction
Resolved
04/11/2025
Erosion control is in place at the time of inspection
Occupancy Inspection - Codes Residential Failed 4/11/2025 4/11/2025 04/11/2025
Miscellaneous Correction
Corrective Action Required
02/27/2025
- Land sewer trace wire at grade ( PUT IN ENCLOSER AT GRADE )
Occupancy Inspection - Codes Residential Full C of O 4/17/2025 4/17/2025 04/17/2025
Miscellaneous Correction
Resolved
04/17/2025
- Land sewer trace wire at grade ( PUT IN ENCLOSER AT GRADE )
Documents & Images
Date Uploaded File Type Document Name
05/21/2024 OS #61 - ENGINEERED PLANS
05/21/2024 OS #61 - PERMIT APP
05/21/2024 OS #61 - PLOT PLAN
05/21/2024 OS #61 - TRUSS DETAILS
05/21/2024 OS #61 - TRUSS LAYOUT
05/22/2024 Approved Plans APPROVED PLANS
05/22/2024 Plot Plan APPROVED PLOT PLAN
05/22/2024 Approved Plans APPROVED TRUSS LAYOUT
05/22/2024 Approved Plans APPROVED TRUSS PACKAGE
05/22/2024 Permit Codes Residential Plan Review
05/22/2024 Permit DS Building Permit
05/22/2024 Receipt Receipt for transaction:2024-003858
06/27/2024 3RD Party Insp Report THIRD PARTY FOOTING INSPECTION
06/28/2024 Letter INSPECTION SUMMARY
06/28/2024 Letter INSPECTION SUMMARY
07/09/2024 Letter INSPECTION SUMMARY
07/09/2024 Letter INSPECTION SUMMARY
07/11/2024 Letter INSPECTION SUMMARY
07/12/2024 Letter INSPECTION SUMMARY
07/22/2024 Letter INSPECTION SUMMARY
07/22/2024 Letter INSPECTION SUMMARY
07/23/2024 Letter INSPECTION SUMMARY
07/23/2024 Letter INSPECTION SUMMARY
08/13/2024 Letter INSPECTION SUMMARY
08/28/2024 Letter INSPECTION SUMMARY
08/28/2024 Letter INSPECTION SUMMARY
09/04/2024 Letter INSPECTION SUMMARY
09/11/2024 Letter INSPECTION SUMMARY
09/27/2024 Letter INSPECTION SUMMARY
09/27/2024 Letter INSPECTION SUMMARY
10/01/2024 Letter INSPECTION SUMMARY
10/02/2024 Letter INSPECTION SUMMARY
10/02/2024 Letter INSPECTION SUMMARY
10/02/2024 Letter INSPECTION SUMMARY
10/02/2024 Letter INSPECTION SUMMARY
10/09/2024 Letter INSPECTION SUMMARY
10/09/2024 Letter INSPECTION SUMMARY
10/09/2024 Letter INSPECTION SUMMARY
10/11/2024 Letter INSPECTION SUMMARY
10/15/2024 Letter INSPECTION SUMMARY
10/15/2024 Letter INSPECTION SUMMARY
10/15/2024 Letter INSPECTION SUMMARY
10/28/2024 Letter INSPECTION SUMMARY
10/28/2024 Letter INSPECTION SUMMARY
10/28/2024 Letter INSPECTION SUMMARY
11/04/2024 Letter INSPECTION SUMMARY
11/04/2024 Letter INSPECTION SUMMARY
11/19/2024 Letter INSPECTION SUMMARY
11/19/2024 Letter INSPECTION SUMMARY
11/22/2024 Letter Stop Work Order
11/22/2024 Letter Stop Work Order
12/04/2024 Receipt Receipt for transaction:2024-009324
12/05/2024 Letter INSPECTION SUMMARY
12/06/2024 Letter INSPECTION SUMMARY
12/06/2024 Letter INSPECTION SUMMARY
12/10/2024 Certificate/License Codes Temporary Certificate of Occupancy
12/10/2024 Receipt Receipt for transaction:2024-009422
01/13/2025 Letter INSPECTION SUMMARY
01/13/2025 Letter INSPECTION SUMMARY
01/13/2025 Letter INSPECTION SUMMARY
01/13/2025 Certificate/License Codes Temporary Certificate of Occupancy
01/13/2025 Receipt Receipt for transaction:2025-000188
02/05/2025 OS #61 - TCO Extension 2_5_25
02/06/2025 Letter INSPECTION SUMMARY
02/06/2025 Certificate/License Codes Temporary Certificate of Occupancy
02/06/2025 Receipt Receipt for transaction:2025-000779
02/26/2025 Application Form OS #61 - TCO Extension 2_26_25
02/27/2025 Letter INSPECTION SUMMARY
02/27/2025 Certificate/License Codes Temporary Certificate of Occupancy
02/27/2025 Receipt Receipt for transaction:2025-001150
04/11/2025 Letter INSPECTION SUMMARY
04/11/2025 Letter INSPECTION SUMMARY
04/17/2025 Letter Codes Final Certificate of Occupancy
04/17/2025 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home