Permit Application Status

PRRES20242155


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20242155
Building Permit - Residential
Temporary Occupancy
DOMAIN TIMBERLAKE MULTISTATE LLC
NEW SINGLE FAMILY
NEW HOUSE. FINISHED/UNFINISHED BASEMENT. WALKOUT BASEMENT. COVERED DECK. ROOF TRUSSES. STOP WORK ORDER generated on 09/16/2024 12:00 AM by username 'Mitchell Schwarz'. STOP WORK ORDER removed on 09/30/2024 12:00 AM by username 'Shawn Hoffman'.
04/30/2024
05/07/2024
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
DOMAIN TIMBERLAKE MULTISTATE LLC, Address:590 MADISON AVE FL 13TH  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
TYLER@SUMMITHOMESKC.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331401-Water Tap Fee $3,760.00 $3,760.00 Paid 05/07/2024
8350015-Water Meter Fee $680.46 $680.46 Paid 05/07/2024
8331507-Sanitary Sewer Development Fee $2,159.00 $2,159.00 Paid 05/07/2024
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 05/07/2024
7232302-Residential Excise Tax Fee $1,022.72 $1,022.72 Paid 05/07/2024
9110078-Valuation Fee New Single Family $1,470.52 $1,470.52 Paid 05/07/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 11/18/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 11/18/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 11/18/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 11/18/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 11/18/2024
9110080-3rd and Subsequent Inspection Fee (Per Hour) $150.00 $150.00 Paid 11/18/2024
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 12/12/2024
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 03/13/2025
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 03/13/2025
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 03/13/2025
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 03/13/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Erosion Control Inspection Residential Pending
Miscellaneous Correction
Informational
11/18/2024
Erosion control measures are in place and must be properly maintained until CofO
Occupancy Inspection - Codes Residential Pending 4/12/2025
Miscellaneous Correction
Corrective Action Required
12/27/2024
Provide as graded plot plan Cannot check water meter due to water in pit Passed for TCO only
Footing Inspection - Residential Passed 5/17/2024 05/17/2024
Sewer Service Inspection - R Passed 5/31/2024 5/31/2024 05/31/2024
Water Service Inspection - R Passed 6/6/2024 6/6/2024 06/06/2024
Underslab Plumbing Inspection - Residential Failed 6/10/2024 6/10/2024 06/10/2024
Misc
Corrective Action Required
06/10/2024
Provide erosion control at front of lot No address posted Complete interior drain tile
Erosion Control Inspection Residential Failed 6/10/2024 06/10/2024
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
06/10/2024
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
DCM5 ESC INSP DENIED
Corrective Action Required
06/10/2024
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION.
Underslab Plumbing Inspection - Residential Passed 6/19/2024 6/19/2024 06/19/2024
Misc
Resolved
06/19/2024
Provide erosion control at front of lot No address posted Complete interior drain tile
All Rough Inspection - Residential Partial 7/29/2024 7/29/2024 07/29/2024
Misc
Informational
07/29/2024
Garage portal frame only inspected. Okay to cover
Piers/Caissons Inspection - Residential Not Ready 7/30/2024 07/30/2024
Misc
Corrective Action Required
07/30/2024
Pier hole full of water , remove water for inspection
Piers/Caissons Inspection - Residential Passed 8/6/2024 08/06/2024
Misc
Resolved
08/06/2024
Pier hole full of water , remove water for inspection
All Rough Inspection - Residential Failed 9/3/2024 9/3/2024 09/03/2024
Misc
Resolved
09/03/2024
Garage portal frame only inspected. Okay to cover
Misc
Corrective Action Required
09/03/2024
-sister over notched exterior wall stud at garage W wall -2 nails per stud at libs -seal top plate penetrations At dining area -missing king stud at caps in dining room -complete caps nailing -block wall space to ceiling space at great room -will check GB bracing at time of install -seal bottom plate penetration at bed 1/fire place -supply stud shoes at bath 1 exterior wall for dwv -seal low voltage penetrations in bed 2 -provid lateral bracing for trusses throughout where missing -address A7 truss at top of stairs -fire block wall space into furr downs throughout basement -seal gaps in 10’ vertical to horizontal fire blocking -all anchor bolts in basement to be tight , in the middle 1/3 of sill plate and within 12” of plate breaks (not closer than 7x the diameter of the bolt) -missing stud at exterior wall corner NW basement -seal top plate penetrations at basement slider -missing anchor bolts for cspf rec room wall -missing exterior wall stud at bed 3 NW corner -complete 10’ vertical to horizontal fire blocking throughout -exterior nailing to be to plans
Electrical Service Inspection Passed 9/3/2024 9/3/2024 09/03/2024
Gas Service Inspection - Residential Failed 9/3/2024 9/3/2024 09/03/2024
Misc
Corrective Action Required
09/03/2024
Provide pressure at gas gauge for inspection
Gas Service Inspection - Residential Not Ready 9/9/2024 9/9/2024 09/09/2024
Misc
Corrective Action Required
09/03/2024
Provide pressure at gas gauge for inspection Still no pressures 09/09/24
All Rough Inspection - Residential Not Ready 9/9/2024 9/9/2024 09/09/2024
Misc
Corrective Action Required
09/03/2024
1632 -seal top plate penetrations At dining area -missing king stud at cspf in dining room -complete cspf nailing -block wall space to ceiling space at great room(solid block sheathing breaks ) -will check GB bracing at time of install -seal bottom plate penetration at bed 1/fire place -supply stud shoes at bath 1 exterior wall for dwv -seal low voltage penetrations in bed 2 -provid lateral bracing for trusses throughout where missing(could not locate truss plans on site) -address A7 truss at top of stairs (no documentation uploaded to portal for fix) -fire block wall space into furr downs throughout basement -seal gaps in 10’ vertical to horizontal fire blocking -missing stud at exterior wall corner NW basement -seal top plate penetrations at basement slider -missing anchor bolts for cspf rec room wall -complete 10’ vertical to horizontal fire blocking throughout -exterior nailing to be to plans
All Rough Inspection - Residential Not Ready 9/12/2024 9/12/2024 09/12/2024
Misc
Corrective Action Required
09/09/2024
-seal bottom plate penetrations At dining area -complete cspf nailing -block wall space to ceiling space at great room(solid block sheathing breaks ) -will check GB bracing at time of install -seal low voltage penetrations in bed 2 -provid lateral bracing for trusses to throughout where missing(multiple throughout) -address A7 truss at top of stairs (no documentation uploaded to portal for fix) -fire block wall space into furr downs throughout basement -missing stud at exterior wall corner NW basement (missing on N wall) -missing anchor bolts for cspf rec room wall -exterior nailing to be to plans
Gas Service Inspection - Residential Failed 9/12/2024 9/12/2024 09/12/2024
Misc
Corrective Action Required
09/09/2024
Provide pressure at gas gauge for inspection Still no pressures 09/09/24 Use correct pressure gauge 09/12/24
G2417.4 Test pressure measurement
Corrective Action Required
09/12/2024
INSPECTION, TESTING AND PURGING. Test pressure shall be measured with a manometer or with a pressure-measuring device designed and calibrated to read, record, or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be isolated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than five times the test pressure.
G2417.4.1 Test Pressure
Corrective Action Required
09/12/2024
INSPECTION, TESTING AND PURGING. AMENDED 7-945. The test pressure to be used shall be not less than one and one-half times the proposed maximum working pressure, but not less than 10 psig (68.9kPa) irrespective of design pressure. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure, the test pressure shall not be less than 60 psig. Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe.
All Rough Inspection - Residential Not Ready 9/16/2024 9/16/2024 09/16/2024
Misc
Corrective Action Required
09/12/2024
Home insulated without inspection. -seal bottom plate penetrations At dining area -complete cspf nailing -block wall space to ceiling space at great room(solid block sheathing breaks ) -will check GB bracing at time of install -seal low voltage penetrations in bed 2 -provid lateral bracing for trusses to throughout where missing(multiple throughout) -address A7 truss at top of stairs (no documentation uploaded to portal for fix) -fire block wall space into furr downs throughout basement -missing stud at exterior wall corner NW basement (missing on N wall) -missing anchor bolts for cspf rec room wall -exterior nailing to be to plans
All Rough Inspection - Residential Failed - Stop Work 9/16/2024 9/16/2024 09/16/2024
Misc
Corrective Action Required
09/16/2024
Home insulated without inspection. Remove insulation before Reinspection -seal bottom plate penetrations At dining area -complete cspf nailing -block wall space to ceiling space at great room(solid block sheathing breaks ) -will check GB bracing at time of install -seal low voltage penetrations in bed 2 -provid lateral bracing for trusses to throughout where missing(multiple throughout) -address A7 truss at top of stairs (no documentation uploaded to portal for fix) -fire block wall space into furr downs throughout basement -missing stud at exterior wall corner NW basement (missing on N wall) -missing anchor bolts for cspf rec room wall -exterior nailing to be to plans
All Rough Inspection - Residential Failed 9/20/2024 9/20/2024 09/20/2024
Misc
Corrective Action Required
09/16/2024
-complete cspf nailing -will check GB bracing at time of install -provid lateral bracing for trusses to throughout where missing(multiple throughout) -address A7 truss at top of stairs (no documentation uploaded to portal for fix) -fire block wall space into furr downs throughout basement -missing stud at exterior wall corner NW basement (missing on N wall) -missing anchor bolt washers for cspf rec room wall
All Rough Inspection - Residential Failed 9/24/2024 9/24/2024 09/24/2024
Misc
Corrective Action Required
09/20/2024
-will check GB bracing at time of install -address A7 truss at top of stairs (no documentation uploaded to portal for fix)
All Rough Inspection - Residential Passed 9/30/2024 9/30/2024 09/30/2024
Misc
Resolved
09/30/2024
Gas Service Inspection - Residential Passed 10/3/2024 10/3/2024 10/03/2024
Misc
Resolved
10/03/2024
Provide pressure at gas gauge for inspection Still no pressures 09/09/24 Use correct pressure gauge 09/12/24
G2417.4 Test pressure measurement
Resolved
10/03/2024
INSPECTION, TESTING AND PURGING. Test pressure shall be measured with a manometer or with a pressure-measuring device designed and calibrated to read, record, or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be isolated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than five times the test pressure.
G2417.4.1 Test Pressure
Resolved
10/03/2024
INSPECTION, TESTING AND PURGING. AMENDED 7-945. The test pressure to be used shall be not less than one and one-half times the proposed maximum working pressure, but not less than 10 psig (68.9kPa) irrespective of design pressure. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure, the test pressure shall not be less than 60 psig. Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe.
Sidewalk Inspection Partial 11/8/2024 11/08/2024
Misc
Informational
11/08/2024
11-8-24 DP. SW was formed, aggregate compacted, cross slopes in compliance but conditions can change. Approved to pour.
Driveway Inspection Partial 11/14/2024 11/14/2024 11/14/2024
Misc
Informational
11/14/2024
10-13-24 Dustin A, Dw and curb have been formed and compacted. Approved to pour
Occupancy Inspection - Codes Residential Failed 11/18/2024 11/18/2024 11/18/2024
Miscellaneous Correction
Corrective Action Required
11/18/2024
-Overhead garage doors are not completed -Exterior electrical receptacles need to be for wet locations Self -Deck to beam fasteners are not installed -Driveway final is not complete -Sidewalk final is not complete -Sod, splash pads and sump pump extension need to be completed -Seal all exterior penetrations -Pay $525 in fees associated with this permit
Erosion Control Inspection Residential Partial 11/18/2024 11/18/2024
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
11/18/2024
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
DCM5 ESC INSP DENIED
Resolved
11/18/2024
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION.
Miscellaneous Correction
Informational
11/18/2024
Erosion control measures are in place and must be properly maintained until CofO
Driveway Inspection Passed 11/18/2024 11/18/2024 11/18/2024
Misc
Informational
11/14/2024
10-13-24 Dustin A, Dw and curb have been formed and compacted. Approved to pour 11-18-24 Dustin A, Dw is poured and slopes are in compliance. Pass
Sidewalk Inspection Partial 11/18/2024 11/18/2024 11/19/2024
Misc
Corrective Action Required
11/18/2024
11-15-24 Dustin A, Sw is poured and slopes are in compliance. Expansion joints were not used attaching to existing SW's. Failed 11-19-24 Dustin A, SW has been cut back out. Approved to pour with expansion joints
Plot Plan Inspection Failed 11/19/2024 11/19/2024
Miscellaneous Correction
Corrective Action Required
11/19/2024
-Final grade has not been completed -Water meter can not be inspected due to water in the meter pit
Occupancy Inspection - Codes Residential Ready for Temp CO 11/19/2024 11/19/2024 11/19/2024
Miscellaneous Correction
Corrective Action Required
11/18/2024
-Sidewalk final is not complete -Sod, splash pads and sump pump extension need to be completed -Seal all exterior penetrations -Plot plan needs to pass Passed for TCO only
Sidewalk Inspection Passed 11/26/2024 11/26/2024 11/26/2024
Misc
Informational
11/18/2024
11-8-24 DP. SW was formed, aggregate compacted, cross slopes in compliance but conditions can change. Approved to pour. 11-19-24 Dustin A, panels have been removed that had no expansion joints. Approved to repour 11-26-24 Dustin A, passed
Occupancy Inspection - Codes Residential Failed 12/27/2024 12/27/2024 12/27/2024
Miscellaneous Correction
Corrective Action Required
11/19/2024
Provide as graded plot plan Passed for TCO only
Plot Plan Inspection Passed 4/9/2025 04/09/2025
Miscellaneous Correction
Resolved
04/09/2025
-Final grade has not been completed
Documents & Images
Date Uploaded File Type Document Name
04/30/2024 HT #166 - ENGINEERED PLANS
04/30/2024 HT #166 - PERMIT APP
04/30/2024 HT #166 - PLOT PLAN
04/30/2024 HT #166 - TRUSS DETAILS
04/30/2024 HT #166 - TRUSS LAYOUT
05/06/2024 Approved Plans APPROVED PLANS
05/06/2024 Plot Plan APPROVED PLOT PLAN
05/06/2024 Approved Plans APPROVED TRUSS PACKAGE
05/06/2024 Approved Plans APPROVED TRUSS LAYOUT
05/06/2024 Permit Codes Residential Plan Review
05/07/2024 Permit DS Building Permit
05/07/2024 Receipt Receipt for transaction:2024-003040
05/16/2024 M L Crose 1632 SW Buckthorn LSMO Foundation Footing Inspection Report 5-15-24
05/31/2024 Letter INSPECTION SUMMARY
05/31/2024 Letter INSPECTION SUMMARY
06/06/2024 Letter INSPECTION SUMMARY
06/07/2024 Approved Plans APPROVED TRUSS LAYOUT
06/07/2024 Approved Plans APPROVED TRUSS PACKAGE
06/07/2024 Plot Plan 6-7-24 APPROVED PLOT PLAN
06/07/2024 Approved Plans 6-7-24 APPROVED PLANS
06/10/2024 Letter INSPECTION SUMMARY
06/10/2024 Letter INSPECTION SUMMARY
06/19/2024 Letter INSPECTION SUMMARY
07/29/2024 Letter INSPECTION SUMMARY
07/30/2024 Letter INSPECTION SUMMARY
08/06/2024 Letter INSPECTION SUMMARY
09/03/2024 Letter INSPECTION SUMMARY
09/03/2024 Letter INSPECTION SUMMARY
09/03/2024 Letter INSPECTION SUMMARY
09/09/2024 Letter INSPECTION SUMMARY
09/09/2024 Letter INSPECTION SUMMARY
09/12/2024 Letter INSPECTION SUMMARY
09/12/2024 Letter INSPECTION SUMMARY
09/16/2024 Letter INSPECTION SUMMARY
09/16/2024 Letter Stop Work Order
09/20/2024 Letter INSPECTION SUMMARY
09/24/2024 Letter INSPECTION SUMMARY
09/27/2024 3RD Party Insp Report Truss A7 Repair
09/30/2024 Letter INSPECTION SUMMARY
10/03/2024 Letter INSPECTION SUMMARY
11/08/2024 Letter INSPECTION SUMMARY
11/14/2024 Letter INSPECTION SUMMARY
11/18/2024 Letter INSPECTION SUMMARY
11/18/2024 Letter INSPECTION SUMMARY
11/18/2024 Receipt Receipt for transaction:2024-009008
11/18/2024 Letter INSPECTION SUMMARY
11/18/2024 Letter INSPECTION SUMMARY
11/18/2024 Letter INSPECTION SUMMARY
11/19/2024 Letter INSPECTION SUMMARY
11/19/2024 Letter INSPECTION SUMMARY
11/19/2024 Letter INSPECTION SUMMARY
11/26/2024 Letter INSPECTION SUMMARY
12/12/2024 Certificate/License Codes Temporary Certificate of Occupancy
12/12/2024 Receipt Receipt for transaction:2024-009481
12/27/2024 Letter INSPECTION SUMMARY
03/13/2025 Certificate/License Codes Temporary Certificate of Occupancy
03/13/2025 Certificate/License Codes Temporary Certificate of Occupancy
03/13/2025 Certificate/License Codes Temporary Certificate of Occupancy
03/13/2025 Certificate/License Codes Temporary Certificate of Occupancy
03/13/2025 Receipt Receipt for transaction:2025-001518
04/08/2025 Plot Plan APPROVED AS GRADED PLOT PLAN
04/09/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.