Permit Application Status

PRRES20241487


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20241487
Building Permit - Residential
Certificate of Occupancy
CMH PARKS INC
NEW SINGLE FAMILY
NEW HOUSE. UNFINISHED BASEMENT. ROOF TRUSSES. COVERED PATIO.
03/28/2024
04/11/2024
09/24/2024
08/05/2025
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
CMH PARKS INC, Address:5000 CLAYTON RD  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
TYLER@SUMMITHOMESKC.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
Water Tap Fee $3,760.00 $3,760.00 Paid 04/11/2024
Water Meter Fee $680.46 $680.46 Paid 04/11/2024
Sanitary Sewer Development Fee $2,159.00 $2,159.00 Paid 04/11/2024
Right of Way Permit Fee $85.00 $85.00 Paid 04/11/2024
Residential Excise Tax Fee $1,022.72 $1,022.72 Paid 04/11/2024
Valuation Fee New Single Family $1,853.94 $1,853.94 Paid 04/11/2024
Not Ready Inspection Fee $75.00 $75.00 Paid 11/07/2024
Not Ready Inspection Fee $75.00 $75.00 Paid 11/07/2024
Not Ready Inspection Fee $75.00 $75.00 Paid 11/07/2024
Not Ready Inspection Fee $75.00 $75.00 Paid 11/07/2024
Not Ready Inspection Fee $75.00 $75.00 Paid 11/07/2024
Temporary Occupancy Fee $50.00 $50.00 Paid 11/08/2024
Temporary Occupancy Fee $50.00 $50.00 Paid 03/13/2025
Temporary Occupancy Fee $50.00 $50.00 Paid 03/13/2025
Temporary Occupancy Fee $50.00 $50.00 Paid 03/13/2025
Temporary Occupancy Fee $50.00 $50.00 Paid 03/13/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Sewer Service Inspection - R Passed 4/26/2024 4/26/2024 04/26/2024
Water Service Inspection - R Passed 4/30/2024 4/30/2024 04/30/2024
Footing Inspection - Residential Passed 5/23/2024 05/23/2024
Underslab Plumbing Inspection - Residential Passed 5/23/2024 5/23/2024 05/23/2024
All Rough Inspection - Residential Partial 6/19/2024 6/19/2024 06/19/2024
Misc
Informational
06/19/2024
Garage Portal frame inspection only
Piers/Caissons Inspection - Residential Failed 7/30/2024 07/30/2024
Misc
Corrective Action Required
07/30/2024
Inspected 2 24”x 36” piers with 4 #4 vertical rebar in each. Plans do not specify sizing to confirm correct
All Rough Inspection - Residential Failed 8/16/2024 8/16/2024 08/16/2024
Misc
Resolved
08/16/2024
Garage Portal frame inspection only
Misc
Corrective Action Required
08/16/2024
-Secure steel column in garage -fireblock hvac chases into fruit down -missing lib bracing in flex room -address holes drilled to close to one another above pantry -strap top plate where lapped less than 24” kitchen wall -uncover covered patio for inspection -fireblock hvac chases at rear great room -2x6 wall at great room/ stairs not full height to plans -fire block dead space and hvac chase at bath 2 -complete lib bracing in bed 3 -missing lib bracing bed 1 -block sheathing breaks breaks in bed 1 -seal gaps in wall space to ceiling space fire blocking in bed 1 -anchor all steel columns in basement -complete ufer ground -solid blocking in joist space under kitchen island per plans -no gas line installed at time of inspection
Electrical Service Inspection Failed 8/16/2024 8/16/2024 08/16/2024
Misc
Corrective Action Required
08/16/2024
Complete ufer ground bonding
All Rough Inspection - Residential Not Ready 8/21/2024 8/21/2024 08/21/2024
Misc
Corrective Action Required
08/16/2024
-Secure steel column in garage (can not confirm) -fireblock hvac chases into frurr down -missing lib bracing in flex room -address holes drilled to close to one another above pantry -strap top plate where lapped less than 24” kitchen wall -uncover covered patio for inspection -fireblock hvac chases at rear great room -2x6 wall at great room/ stairs not full height to plans -fire block dead space and hvac chase at bath 2 -complete lib bracing in bed 3 (missing nails) -block sheathing breaks breaks in bed 1 -seal gaps in wall space to ceiling space fire blocking in bed 1 -anchor all steel columns in basement -complete ufer ground -solid blocking in joist space under kitchen island per plans -no gas line installed at time of inspection
All Rough Inspection - Residential Failed 8/22/2024 8/22/2024 08/22/2024
Misc
Corrective Action Required
08/21/2024
-address holes drilled to close to one another above pantry (provide engineering for fix) -2x6 wall at great room/ stairs not full height to plans -complete ufer ground -no gas line installed at time of inspection
Driveway Inspection Partial 9/25/2024 9/25/2024 09/25/2024
Misc
Informational
09/25/2024
9-25-24 Dustin A, DW is formed and compacted. Approved to pour
All Rough Inspection - Residential Not Ready 10/3/2024 10/3/2024 10/03/2024
Misc
Corrective Action Required
08/22/2024
-address holes drilled to close to one another above pantry (provide engineering for fix) -2x6 wall at great room/ stairs not full height to plans -complete ufer ground -no gas line installed at time of inspection
Misc
Informational
10/03/2024
Missing erosion control and address. Inspection denied.
Electrical Service Inspection Failed 10/3/2024 10/3/2024 10/03/2024
Misc
Corrective Action Required
08/16/2024
Missing erosion control and address. Inspection denied. Complete ufer ground bonding
Gas Service Inspection - Residential Failed 10/3/2024 10/3/2024 10/03/2024
All Rough Inspection - Residential Not Ready 10/7/2024 10/7/2024 10/07/2024
Misc
Corrective Action Required
10/03/2024
-address holes drilled to close to one another above pantry (provide engineering for fix) -2x6 wall at great room/ stairs not full height to plans -complete ufer ground -no gas line installed at time of inspection
Misc
Informational
10/03/2024
Missing erosion control and address. Inspection denied. No address posted still. NOT READY- Mitchell Schwarz 10/07/24 08:40AM
Electrical Service Inspection Failed 10/7/2024 10/7/2024 10/07/2024
Misc
Corrective Action Required
10/03/2024
Missing erosion control and address. Inspection denied. (No address posted still. 10/07/24 ) Complete ufer ground bonding
Gas Service Inspection - Residential Failed 10/7/2024 10/7/2024 10/07/2024
Misc
Corrective Action Required
10/07/2024
No address posted. Inspection denied 10/07/24
All Rough Inspection - Residential Passed 10/8/2024 10/8/2024 10/08/2024
Misc
Resolved
10/08/2024
-address holes drilled to close to one another above pantry (provide engineering for fix) -2x6 wall at great room/ stairs not full height to plans -complete ufer ground -no gas line installed at time of inspection
Misc
Resolved
10/08/2024
Missing erosion control and address. Inspection denied. No address posted still. NOT READY- Mitchell Schwarz 10/07/24 08:40AM
Gas Service Inspection - Residential Failed 10/8/2024 10/8/2024 10/08/2024
Misc
Corrective Action Required
10/07/2024
No pressure at gas gauge
Electrical Service Inspection Passed 10/8/2024 10/8/2024 10/08/2024
Misc
Resolved
10/08/2024
Missing erosion control and address. Inspection denied. (No address posted still. 10/07/24 ) Complete ufer ground bonding
Gas Service Inspection - Residential Failed 10/30/2024 10/30/2024 10/30/2024
Misc
Corrective Action Required
10/08/2024
No pressure at gas gauge No address posted inspection denied
Driveway Inspection Passed 10/31/2024 10/31/2024 10/30/2024
Misc
Informational
09/25/2024
9-25-24 Dustin A, DW is formed and compacted. Approved to pour 10-30-24 Dustin A, Dw is poured to city specs. Passed
Gas Service Inspection - Residential Not Ready 11/1/2024 11/1/2024 11/01/2024
Misc
Corrective Action Required
10/30/2024
No pressure at gas gauge No address posted inspection denied Fire place not installed gas line capped no shut off.
Gas Service Inspection - Residential Not Ready 11/4/2024 11/4/2024 11/04/2024
Misc
Corrective Action Required
11/01/2024
No pressure at gas gauge No address posted inspection denied Fire place not installed gas line capped no shut off at fireplace DONT CALL FOR INSPECTION UNTIL READY. NOT READY FEE ASSESSED.
Gas Service Inspection - Residential Failed 11/5/2024 11/5/2024 11/05/2024
Misc
Corrective Action Required
11/04/2024
gauge not working correctly, stuck at 9psi
Gas Service Inspection - Residential Passed 11/6/2024 11/6/2024 11/06/2024
Misc
Resolved
11/06/2024
gauge not working correctly, stuck at 9psi
Occupancy Inspection - Codes Residential Failed 11/6/2024 11/6/2024 11/06/2024
Misc
Corrective Action Required
11/06/2024
-address pending pier inspection -pay all fees -final grade and sod -will check water meter at time of final grade and sod -splash blocks and sump pump discharge to extend 36” from foundation -Guard rail required at front stoop where greater than 30” from grade -fireplace needs afci protection -fridge needs afci protection -washer needs afci protection -complete electrical in kitchen for inspection -label all non gfci outlets in unfinished spaces -hand rail to basement not installed
Occupancy Inspection - Codes Residential Failed 11/7/2024 11/7/2024 11/07/2024
Misc
Corrective Action Required
11/06/2024
-address pending pier inspection -pay all fees -final grade and sod -will check water meter at time of final grade and sod -splash blocks and sump pump discharge to extend 36” from foundation -Guard rail required at front stoop where greater than 30” from grade -fireplace needs afci protection -fridge needs afci protection -washer needs afci protection -complete electrical in kitchen for inspection -label all non gfci outlets in unfinished spaces -hand rail to basement not installed Electrical still incomplete and handrails still not installed at time of inspection
Occupancy Inspection - Codes Residential Ready for Temp CO 11/8/2024 11/8/2024 11/08/2024
Misc
Corrective Action Required
11/07/2024
EROSION CONTOL MUST BE MAINTAINED AROUND LOT UNTIL SOD IS IN PLACE -address pending pier inspection -pay all fees -final grade and sod -will check water meter at time of final grade and sod -splash blocks and sump pump discharge to extend 36” from foundation
Piers/Caissons Inspection - Residential Passed 03/14/2025
Misc
Resolved
03/14/2025
Inspected 2 24”x 36” piers with 4 #4 vertical rebar in each. Plans do not specify sizing to confirm correct
Occupancy Inspection - Codes Residential Failed 3/14/2025 3/14/2025 03/14/2025
Misc
Corrective Action Required
11/08/2024
- water meter must be 14”-18” from top of meter to well ring lid
Plot Plan Inspection Passed 03/14/2025
Erosion Control Inspection Residential Passed 8/5/2025 08/05/2025
Occupancy Inspection - Codes Residential Full C of O 4/12/2025 08/05/2025
Misc
Corrective Action Required
03/14/2025
- water meter must be 14”-18” from top of meter to well ring lid
Documents & Images
Date Uploaded File Type Document Name
03/28/2024 H4 # 119 - ENGINEERED PLANS
03/28/2024 H4 # 119 - PLOT PLAN
03/28/2024 H4 # 119 - TRUSS DETAILS
03/28/2024 H4 # 119 - TRUSS LAYOUT
03/28/2024 Permit Codes Residential Plan Review
04/04/2024 Approved Plans APPROVED PLANS
04/04/2024 Approved Plans APPROVED TRUSS LAYOUT
04/04/2024 Approved Plans APPROVED TRUSS PACKAGE
04/10/2024 LOT 119 CITY
04/10/2024 H4 # 119 - PERMIT APP
04/11/2024 Plot Plan APPROVED PLOT PLAN
04/11/2024 Permit Codes Residential Plan Review
04/11/2024 Permit DS Building Permit
04/11/2024 Receipt Receipt for transaction:2024-002319
04/19/2024 3RD Party Insp Report THIRD PARTY FOOTING INSPECTION
04/26/2024 Letter INSPECTION SUMMARY
04/30/2024 Letter INSPECTION SUMMARY
05/23/2024 Letter INSPECTION SUMMARY
05/23/2024 Letter INSPECTION SUMMARY
06/19/2024 Letter INSPECTION SUMMARY
07/30/2024 Letter INSPECTION SUMMARY
08/16/2024 Letter INSPECTION SUMMARY
08/16/2024 Letter INSPECTION SUMMARY
08/21/2024 Letter INSPECTION SUMMARY
08/22/2024 Letter INSPECTION SUMMARY
09/04/2024 H4 #119 Field Letter
09/25/2024 Letter INSPECTION SUMMARY
10/03/2024 Letter INSPECTION SUMMARY
10/03/2024 Letter INSPECTION SUMMARY
10/03/2024 Letter INSPECTION SUMMARY
10/07/2024 Letter INSPECTION SUMMARY
10/07/2024 Letter INSPECTION SUMMARY
10/07/2024 Letter INSPECTION SUMMARY
10/08/2024 Letter INSPECTION SUMMARY
10/08/2024 Letter INSPECTION SUMMARY
10/08/2024 Letter INSPECTION SUMMARY
10/30/2024 Letter INSPECTION SUMMARY
10/30/2024 Letter INSPECTION SUMMARY
11/01/2024 Letter INSPECTION SUMMARY
11/04/2024 Letter INSPECTION SUMMARY
11/05/2024 Letter INSPECTION SUMMARY
11/06/2024 Letter INSPECTION SUMMARY
11/07/2024 Letter INSPECTION SUMMARY
11/07/2024 Letter INSPECTION SUMMARY
11/07/2024 Receipt Receipt for transaction:2024-008841
11/08/2024 Letter INSPECTION SUMMARY
11/08/2024 119 Hawthorn Ridge Field Letter - 241108
11/08/2024 Certificate/License Codes Temporary Certificate of Occupancy
11/08/2024 Receipt Receipt for transaction:2024-008857
01/03/2025 Application Form EXTENSION FORM
03/13/2025 Certificate/License Codes Temporary Certificate of Occupancy
03/13/2025 Certificate/License Codes Temporary Certificate of Occupancy
03/13/2025 Certificate/License Codes Temporary Certificate of Occupancy
03/13/2025 Certificate/License Codes Temporary Certificate of Occupancy
03/13/2025 Receipt Receipt for transaction:2025-001516
03/14/2025 Letter INSPECTION SUMMARY
03/14/2025 Letter INSPECTION SUMMARY
03/14/2025 Letter INSPECTION SUMMARY
08/05/2025 Letter INSPECTION SUMMARY
08/05/2025 Letter Field Certificate of Occupancy
08/05/2025 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home