Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 05/26/2021 05/24/2021
Kim Brennan
Right-of-way
Corrective Action Required
05/24/2021

The right-of-way with dimensions must be provided on the plot plan. Please add Alabaster Cr and the ROW dimensions to the plot plan
Residential Plan Review Approved 05/26/2021 05/24/2021
Kim Brennan
Plot Plan Review Rejected 04/23/2021 04/21/2021
Kim Brennan
Right-of-way
Corrective Action Required
04/21/2021

The right-of-way with dimensions must be provided on the plot plan. Please add Alabaster Cr and the ROW dimensions to the plot plan
Residential Plan Review Approved 04/23/2021 04/21/2021
Kim Brennan
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $947.22 $947.22 Paid 05/24/2021
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 05/24/2021
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 05/24/2021
8331504-EFHB Middle Big Creek, Full $401.76 $401.76 Paid 05/24/2021
8331507-Sewer Connection Fee $360.00 $360.00 Paid 05/24/2021
8331401-Water Tap Fee $3,581.00 $3,581.00 Paid 05/24/2021
8350015-Water Meter Fee $455.54 $455.54 Paid 05/24/2021
9110080-3rd and Subsequent Inspection Fee (Per Hour) $100.00 $100.00 Paid 07/20/2022
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 07/20/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 8/3/2021 8/3/2021 08/03/2021
Misc
Informational
08/03/2021
APPROVED PER BRADLEY HUXOL 7/6/21
Erosion Control Inspection Residential Failed 8/3/2021 8/3/2021 08/03/2021
Misc
Informational
08/03/2021
CLEAN ALL MUD AND GRAVEL FROM STREET
Underslab Plumbing Inspection - Residential Passed 8/3/2021 8/3/2021 08/03/2021
Sewer Service Inspection - R Passed 8/12/2021 (8:15) 8/12/2021 08/12/2021
Water Service Inspection - R Partial 8/12/2021 8/12/2021 08/12/2021
Misc
Informational
08/12/2021
PARTIAL ON PEX TO HOUSE ENTRANCE
Water Service Inspection - R Passed 8/16/2021 (9:00) 8/16/2021 08/16/2021
Misc
Informational
08/12/2021
PARTIAL ON PEX TO HOUSE ENTRANCE
Electrical Service Inspection Passed 3/16/2022 3/16/2022 03/16/2022
Gas Service Inspection - Residential Failed 3/16/2022 3/16/2022 03/16/2022
Misc
Corrective Action Required
03/16/2022
GAS LINE BOND REQUIRED
All Rough Inspection - Residential Failed 3/16/2022 3/16/2022 03/16/2022
Misc
Corrective Action Required
03/16/2022
-move John off street and onto lot -maintain gravel filter on drive, min 3/4” gravel with 6” lift -install all anchor bolts at garage and tighten all anchor bolts -anchor bolts required within 12” of plate breaks, see basement and garage -H2.5 truss hold down required at all hip trusses -H2.5 truss hold required at dbl girder truss ends garage -address top plate to top plate connection required by code to tie corners together at west garage corner/mud room wall, plate removed for girder, not tie for (3) corners, have engineer address -nail all truss hangers throughout -min 24” offset between dbl top plate breaks - see garage -anchor bolts garage PFH design per plans/R602.10.6.4, 5/8” anchor bolt with 2”x2”x3/16” plate washer, plates have been notched around bolts, nuts not making contact with bottom plate, missing washer -nail all girder trusses together per plans -12” oc nailing at all abutting and intersecting wall corners -shim all trimmer studs short of header throughout -seal bottom plate penetrations at breakfast -secure gas flex line at fireplace -protect gas flex line at fireplace casing entry -fireblock fireplace lid -front entry wall not tied together at top plates per code -seal top plate owner penetrations at master bath -provide stud at corner for CS-WSP smart siding to be nailed off on edge, at covered deck north corner, see in master bedroom gap at edge of smart siding -LIB bracing all locations per plans -min (4) 2X stud packs at all girder truss bearing ends per plans -CS-PF portal bracing design at dining room windows and dining room sliding glass door per plans -Unable to inspect trusses at front covered porch or covered deck with lid installed -solid block all sheathing breaks throughout -provide protection plate at gas flex line bottom plate at master bedroom -provide lateral bracing at all truss locations as shown in plans -nail off all portal tension straps -fireblock vertical every 10’ between studs and foundation/framing throughout finished basement -fireblock vertical to horizontal at furred down soffit ends -install proper code compliant headers at joists removed for DWV, see basement bedroom closet -fur out for DWV waster stack clean out basement bedroom -fireblock between top plate and foundation wall at basement bedroom soffit for furred down -provide joist hangers at joist to header connection basement bathroom -secure electrical box to stud at basement bedroom -provide bocca protection plates at top and bottom plate basement bath/gym -wall bracing per plans at sliding glass door basement, LVL corner to corner with 15/32 pan on interior and exterior side of wall 8D fasteners at 6” edge 12” field, blocking 2’ oc vert, see detail page A4.0 bracing methods for description ( will need to reinspect for lvl header as one installed is not corner to corner before approval to install pan on interior, no osb present on exterior -wall bracing per plans at Rec room windows, see above for sliding glass door description, bracing description page A4.0 of plans -solid block between joists every 48” oc for kitchen island per plans -all corners exterior 2x6 stud walls must have (3) studs nailed 12” oc, add plate at daylight wall see west wall basement bath north and south sides -secure ward flex gas line to joist at basement den, cannot be less than 3” from end of joist -nail garage portal PFH exterior sheathing per plans/IRC R602.10.6.4 -nail all exterior sheathing per plans -Gas line bond required
Erosion Control Inspection Residential Failed 3/16/2022 3/16/2022 03/16/2022
Misc
Corrective Action Required
03/16/2022
-move John off street and onto lot -maintain gravel filter on drive, min 3/4” gravel with 6” lift
Gas Service Inspection - Residential Passed 3/24/2022 3/24/2022 03/24/2022
Misc
Resolved
03/24/2022
GAS LINE BOND REQUIRED
All Rough Inspection - Residential Failed 3/24/2022 3/24/2022 03/24/2022
Misc
Corrective Action Required
03/16/2022
-front entry wall not tied together at top plates per code -LIB bracing all locations per plans -LIB bracing at fireplace per engineer letter -min (4) 2X stud packs at all girder truss bearing ends per plans -CS-PF portal bracing design at dining room windows and dining room sliding glass door per plans, nail exterior sheathing per plans/IRC R602.10.6.4 -Fireblock deadspace front bedroom -provide lateral bracing at all truss locations as shown in plans -fireblock vertical every 10’ between studs and foundation/framing throughout finished basement -fireblock vertical to horizontal at furred down soffit ends -wall bracing per plans at sliding glass door basement, LVL corner to corner with 15/32 pan on interior and exterior side of wall 8D fasteners at 6” edge 12” field, blocking 2’ oc vert, see detail page A4.0 bracing methods for description ( will need to reinspect for lvl header as one installed is not corner to corner before approval to install pan on interior, no osb present on exterior -wall bracing per plans at Rec room windows, see above for sliding glass door description, bracing description page A4.0 of plans -all corners exterior 2x6 stud walls must have (3) studs nailed 12” oc, add plate at daylight wall see west wall basement bath north and south sides -nail all exterior sheathing per plans
All Rough Inspection - Residential Failed 3/30/2022 3/30/2022 03/30/2022
Misc
Corrective Action Required
03/24/2022
-CS-PF portal bracing design at dining room windows and dining room sliding glass door per plans, nail exterior sheathing per plans/IRC R602.10.6.4 -Fireblock deadspace front bedroom, solid fireblock, that loose insulation is not packed right enough and will fall with a space that large -fireblock vertical to horizontal at furred down soffit ends
All Rough Inspection - Residential Failed 4/4/2022 4/4/2022 04/04/2022
Misc
Corrective Action Required
03/30/2022
-CS-PF portal bracing design at dining room windows and dining room sliding glass door per plans, nail exterior sheathing per plans/IRC R602.10.6.4, check the nailing, remove trim can’t see nail pattern -fireblock vertical to horizontal at furred down soffit ends, see the south end of furred down soffit that runs along the den, the furred down is open to the wall beside it and needs to be fireblocked, this is furred down I pointed out to you during 1st inspection
All Rough Inspection - Residential Failed 4/7/2022 4/7/2022 04/07/2022
Misc
Corrective Action Required
04/04/2022
-CS-PF portal bracing design at dining room windows and dining room sliding glass door per plans, nail exterior sheathing per plans/IRC R602.10.6.4, check the nailing, remove trim can’t see nail pattern see manufactures listing on siding. over driven nails need to be caulked and re-nailed. see email.MARK HARDING 04/07/2022 4:21 PM
All Rough Inspection - Residential Passed 4/21/2022 4/21/2022 04/21/2022
Misc
Resolved
04/21/2022
Driveway Inspection Partial 4/29/2022 4/29/2022 04/29/2022
Misc
Informational
04/29/2022
On 4.29.2022 I performed a driveway inspection and passed the sub grade to pour concrete
Occupancy Inspection - Codes Residential Failed 7/19/2022 7/19/2022 07/19/2022
Misc
Corrective Action Required
07/19/2022
-resolve outstanding inspection fees -final driveway inspection required, contact development services to schedule -final grade and sod -splash blocks -provide gravel base water meter pit -provide joist hanger at joist to beam connection deck -(2) 1/2” through bolts each post/beam connection deck -GFCI front porch test hot/neut reverse -cover plate fridge outlet, basement outlets -secure main water line to foundation wall
Driveway Inspection Passed 7/19/2022 7/19/2022 07/19/2022
Misc
Informational
04/29/2022
On 4.29.2022 I performed a driveway inspection and passed the sub grade to pour concrete 7.19.2022 Driveway appears to be in compliance
Occupancy Inspection - Codes Residential Ready for Temp CO 7/20/2022 7/20/2022 07/20/2022
Misc
Corrective Action Required
07/19/2022
TCO until 8/20/22 -resolve outstanding inspection fees -final grade and sod -splash blocks -provide gravel base water meter pit -(2) 1/2” through bolts each post/beam connection deck -GFCI front porch test hot/neut reve
Occupancy Inspection - Codes Residential Temporary C of O 07/20/2022
Misc
Corrective Action Required
07/20/2022
TCO until 8/20/22 -resolve outstanding inspection fees -final grade and sod -splash blocks -provide gravel base water meter pit -(2) 1/2” through bolts each post/beam connection deck -GFCI front porch test hot/neut reve
Plot Plan Inspection Passed 7/21/2022 07/21/2022
Occupancy Inspection - Codes Residential Full C of O 7/21/2022 7/21/2022 07/21/2022
Misc
Resolved
07/21/2022
Documents & Images
Date Uploaded File Type Document Name
04/21/2021 Application Form Permit Application and License Tax Form
04/21/2021 Approved Plans Approved Drawings
04/21/2021 Approved Plans Approved Truss Layout
04/21/2021 Approved Plans Approved Truss Package
04/21/2021 Letter Codes Residential Plan Review
05/24/2021 Plot Plan Approved Plot Plan
05/24/2021 Permit DS Building Permit
05/24/2021 Receipt Receipt for transaction:2021-003406
08/02/2021 Lot 92 Manor at Stoney Creek Footing Inspection
08/03/2021 Letter INSPECTION SUMMARY
08/03/2021 Letter INSPECTION SUMMARY
08/03/2021 Letter INSPECTION SUMMARY
08/03/2021 Letter INSPECTION SUMMARY
08/12/2021 Letter INSPECTION SUMMARY
08/12/2021 Letter INSPECTION SUMMARY
08/16/2021 Letter INSPECTION SUMMARY
03/16/2022 Letter INSPECTION SUMMARY
03/16/2022 Letter INSPECTION SUMMARY
03/16/2022 Letter INSPECTION SUMMARY
03/16/2022 Letter INSPECTION SUMMARY
03/23/2022 engineer letter MN92
03/24/2022 Letter INSPECTION SUMMARY
03/24/2022 Letter INSPECTION SUMMARY
03/28/2022 92 manor at stoney creek letter 2
03/28/2022 engineer letter MN92 (revised)
03/30/2022 Letter INSPECTION SUMMARY
04/04/2022 Letter INSPECTION SUMMARY
04/07/2022 Letter INSPECTION SUMMARY
04/18/2022 92 Manor at Stoney Creek Field Letter
04/21/2022 Letter INSPECTION SUMMARY
05/03/2022 Letter INSPECTION SUMMARY
07/19/2022 Letter INSPECTION SUMMARY
07/20/2022 Plot Plan Approved As Graded Plot Plan
07/20/2022 Letter INSPECTION SUMMARY
07/20/2022 Receipt Receipt for transaction:2022-005919
07/20/2022 Letter Codes Temporary Certificate of Occupancy
07/21/2022 Letter INSPECTION SUMMARY
07/21/2022 Letter Field Certificate of Occupancy
07/21/2022 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home