Permit Application Status

PRRES20210567


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20210567
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - FINISHED BASEMENT - COVERED DECK
02/10/2021
03/30/2021
08/10/2021
12/27/2022
Locations
Contacts
TRUMARK HOMES, LLC, Address:PO BOX 728, Phone:(816) 564-5613  
C.M. MOSE & SON, Address:6603 ROYAL ST BLDG E, Phone:(816) 781-4707  
IMPACT ELECTRICAL SOLUTIONS LLC, Address:14 ANCHOR DRIVE, Phone:(816) 674-9345  
A BRIGHT PLUMBING LLC, Address:18107 E 18TH TER N, Phone:(816) 215-0730  
TRUMARKHOMES.MARK@GMAIL.COM  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 02/16/2021 02/11/2021
Kim Brennan
Deck location
Corrective Action Required
02/11/2021

Deck location, with dimensions to property lines must be provided on the plot plan.
As-graded plot plan
Corrective Action Required
02/11/2021

A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy.
Misc
Corrective Action Required
02/11/2021

The building elevation on the front left side of 938.0 does not appear to have a 2% slope for proper drainage. Please explain.
Residential Plan Review Approved 02/16/2021 02/11/2021
Kim Brennan
Plot Plan Review Rejected 02/16/2021 02/11/2021
Kim Brennan
Deck location
Corrective Action Required
02/11/2021

Deck location, with dimensions to property lines must be provided on the plot plan.
As-graded plot plan
Corrective Action Required
02/11/2021

A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy.
Misc
Corrective Action Required
02/11/2021

The building elevation on the front left side of 938.0 does not appear to have a 2% slope for proper drainage. Please explain.
Residential Plan Review Approved 02/16/2021 02/11/2021
Kim Brennan
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,140.33 $1,140.33 Paid 03/30/2021
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 03/30/2021
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 03/30/2021
8331507-Sewer Connection Fee $510.00 $510.00 Paid 03/30/2021
8350015-Water Meter Fee $455.54 $455.54 Paid 03/30/2021
8331401-Water Tap Fee $3,581.00 $3,581.00 Paid 03/30/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Sewer Service Inspection - R Passed 4/15/2021 (1:00) 4/15/2021 04/15/2021
Water Service Inspection - R Partial 4/16/2021 (8:30) 4/15/2021 04/15/2021
Misc
Informational
04/15/2021
partial water approval from structure to metallic connection customer side of meter
Footing Inspection - Residential Passed 04/15/2021
Erosion Control Inspection Residential Failed 04/15/2021
Misc
Corrective Action Required
04/15/2021
-Erosion control requires continuous maintenance. Repair damaged sections within 48 hours -immediate street cleanup required -no further inspections until issues are resolved
Miscellaneous Inspection Failed 04/15/2021
Misc
Corrective Action Required
04/15/2021
post site address no further inspections
Water Service Inspection - R Passed 4/16/2021 4/16/2021 04/16/2021
Misc
Resolved
04/16/2021
partial water approval from structure to metallic connection customer side of meter
Underslab Plumbing Inspection - Residential Failed 5/6/2021 5/6/2021 05/06/2021
Misc
Corrective Action Required
05/06/2021
-install sump pit and FD as shown on plan -connect interior underslab drain tile to sump pit -provide continuous bedding under DWV
Erosion Control Inspection Residential Passed 5/6/2021 5/6/2021 05/06/2021
Misc
Resolved
05/06/2021
-Erosion control requires continuous maintenance. Repair damaged sections within 48 hours -immediate street cleanup required -no further inspections until issues are resolved
Underslab Plumbing Inspection - Residential Passed 5/14/2021 5/14/2021 05/14/2021
Misc
Resolved
05/14/2021
-install sump pit and FD as shown on plan -connect interior underslab drain tile to sump pit -provide continuous bedding under DWV
Piers/Caissons Inspection - Residential Passed 6/23/2021 06/23/2021
All Rough Inspection - Residential Partial 7/20/2021 7/20/2021 07/20/2021
Misc
Informational
07/20/2021
: PFH GARAGE PORTAL FRAMING ONLY : OK TO COVER
All Rough Inspection - Residential Failed 9/13/2021 9/13/2021 09/13/2021
Misc
Resolved
09/13/2021
: PFH GARAGE PORTAL FRAMING ONLY : OK TO COVER
Misc
Corrective Action Required
09/13/2021
-Provide BOCA plate for plumbing at laundry top wall plate -Provide CSPF wall at master bedroom per plan -Provide full support for master bedroom ceiling beam above door header -Fully nail master bedroom ceiling beam hanger at rear corner -Strap wall top plates lapped less than 24” at rear dining corner -Provide pressure gauge no more than 30 psi -Fb basement wall space vertically every ten ft or less at front bedroom 4; fb basement bathroom wall from fur down ceiling space -Seal penetrations of ceiling joist return air space in basement -Pan off return air space from soffit above wet bar and outside middle bedroom -Provide 3 trimmer studs all the way to foundation wall at both sides of header that supports the 24” lvl -Security block for basement exterior door; shim the gap at strike plate side with solid wood -Solid block joist ends above I beam; tie together opposite joists across I beam **OK TO INSULATE
Gas Service Inspection - Residential Failed 9/13/2021 9/13/2021 09/13/2021
Misc
Corrective Action Required
09/13/2021
-Provide pressure gauge no more than 30 psi
Electrical Service Inspection Passed 9/13/2021 9/13/2021 09/13/2021
All Rough Inspection - Residential Failed 09/13/2021
Misc
Corrective Action Required
09/13/2021
-Provide BOCA plate for plumbing at laundry top wall plate -Provide CSPF wall at master bedroom per plan -Provide full support for master bedroom ceiling beam above door header -Fully nail master bedroom ceiling beam hanger at rear corner -Strap wall top plates lapped less than 24” at rear dining corner -Provide combustion air openings for mechanical space. Min 100 sq inches per opening -Fb basement wall space vertically every ten ft or less at front bedroom 4; fb basement bathroom wall from fur down ceiling space -Seal penetrations of ceiling joist return air space in basement -Pan off return air space from soffit above wet bar and outside middle bedroom -Provide 3 trimmer studs all the way to foundation wall at both sides of header that supports the 24” lvl -Security block for basement exterior door; shim the gap at strike plate side with solid wood -Solid block joist ends above I beam; tie together opposite joists across I beam **OK TO INSULATE
All Rough Inspection - Residential Failed 9/13/2021 9/13/2021 09/13/2021
Misc
Corrective Action Required
09/13/2021
-Provide BOCA plate for plumbing at laundry top wall plate -Provide CSPF wall at master bedroom per plan -Provide full support for master bedroom ceiling beam above door header -Fully nail master bedroom ceiling beam hanger at rear corner -Strap wall top plates lapped less than 24” at rear dining corner -Provide combustion air openings for mechanical space. Min 100 sq inches per opening -Fb basement wall space vertically every ten ft or less at front bedroom 4; fb basement bathroom wall from fur down ceiling space -Seal penetrations of ceiling joist return air space in basement -Pan off return air space from soffit above wet bar and outside middle bedroom -Provide 3 trimmer studs all the way to foundation wall at both sides of header that supports the 24” lvl -Security block for basement exterior door; shim the gap at strike plate side with solid wood -Solid block joist ends above I beam; tie together opposite joists across I beam **OK TO INSULATE
Gas Service Inspection - Residential Failed 9/17/2021 9/17/2021 09/17/2021
Misc
Corrective Action Required
09/13/2021
-Provide pressure gauge no more than 30 psi, no change still 50psi and 100psi gauge
All Rough Inspection - Residential Failed 9/17/2021 9/17/2021 09/17/2021
Misc
Corrective Action Required
09/13/2021
-Provide CSPF wall at master bedroom per plan , no plans. -Pan off return air space from soffit outside middle bedroom -Solid block joist ends above I beam; tie together opposite joists across I beam, need to check at next inspection.
All Rough Inspection - Residential Failed 9/22/2021 9/22/2021 09/22/2021
Misc
Corrective Action Required
09/17/2021
-Provide CSPF wall at master bedroom per plan **See plan. Header shall be no smaller than 2x12.
Gas Service Inspection - Residential Passed 9/22/2021 9/22/2021 09/22/2021
Misc
Resolved
09/22/2021
-Provide pressure gauge no more than 30 psi, no change still 50psi and 100psi gauge
All Rough Inspection - Residential Failed 9/24/2021 9/24/2021 09/24/2021
Misc
Corrective Action Required
09/22/2021
-Provide CSPF wall at master bedroom per plan **See plan. Header shall be no smaller than 2x12. Strap header from studs to top plate. see plan detail
All Rough Inspection - Residential Failed 9/29/2021 9/29/2021 09/29/2021
Misc
Corrective Action Required
09/24/2021
-Provide CSPF wall at master bedroom per plan **See plan. Header shall be no smaller than 2x12. Strap header from studs to top plate. see plan detail- -Strap from top plate to jack studs-See detail -Provide framing anchors at bottom where sheathing not overlapping rim joist-See detail
All Rough Inspection - Residential Passed 10/4/2021 10/04/2021
Misc
Resolved
10/04/2021
-Provide CSPF wall at master bedroom per plan **See plan. Header shall be no smaller than 2x12. Strap header from studs to top plate. see plan detail- -Strap from top plate to jack studs-See detail -Provide framing anchors at bottom where sheathing not overlapping rim joist-See detail **Ok to sheet rock except master bed wall CSPF
Driveway Inspection Partial 11/29/2021 11/29/2021 11/29/2021
Misc
Informational
11/29/2021
Driveway was framed in with aggregate in and compacted. 11/29 ES
Driveway Inspection Passed 12/3/2021 12/3/2021 12/03/2021
Misc
Informational
11/29/2021
Driveway was framed in with aggregate in and compacted. 11/29 ES
Misc
Informational
12/03/2021
Finished driveway meets LS spec. RP 12-3-21
Occupancy Inspection - Codes Residential Failed 3/23/2022 3/23/2022 03/23/2022
Miscellaneous Correction
Corrective Action Required
03/23/2022
- Provide pier inspection report - Final grading and sod - Complete plumbing master tub - Provide 2 @ 1/2” through bolts at each post to beam connections at deck - Provide handrail for steps in retaining wall to fire pit. R311.7.8
Deck Final Inspection - Residential Passed 03/23/2022
Occupancy Inspection - Codes Residential Temporary C of O 3/23/2022 03/23/2022
Miscellaneous Correction
Resolved
12/27/2022
Plot Plan Inspection Passed 07/22/2022
Misc
Corrective Action Required
04/11/2022
-Verify water meter well is brought up to grade
Occupancy Inspection - Codes Residential Failed 7/22/2022 7/22/2022 07/22/2022
Miscellaneous Correction
Corrective Action Required
03/23/2022
- Complete plumbing master tub - Provide handrail for steps in retaining wall to fire pit. R311.7.8 no access to insde
Occupancy Inspection - Codes Residential Full C of O 12/27/2022 12/27/2022 12/27/2022
Miscellaneous Correction
Resolved
12/27/2022
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home