Permit Application Status

PRRES20204536


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20204536
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - ROOF TRUSS - COVERED DECK - FINISHED BASEMENT
12/01/2020
12/21/2020
06/15/2021
07/21/2021
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
PERMITTING@SUMMITHOMESKC.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 12/23/2020 12/21/2020
Dylan Eppert
Easements
Corrective Action Required
12/21/2020

All easements with dimensions must be provided on the plot plan. MISSING 2.5' UE ON NORTH PROPERTY LINE.
As-graded plot plan
Corrective Action Required
12/21/2020

A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy.
Basement opening elevations
Corrective Action Required
12/21/2020

Minimum Building Opening Elevation (MBOE) and location on structure must be provided on the plot plan. MISSING MLO FROM MDP TABLE FOR THIS LOT.
Residential Plan Review Approved 12/23/2020 12/21/2020
Dylan Eppert
Plot Plan Review Rejected 12/03/2020 12/17/2020
Dylan Eppert
Easements
Corrective Action Required
12/17/2020

All easements with dimensions must be provided on the plot plan. MISSING 2.5' UE ON NORTH PROPERTY LINE.
As-graded plot plan
Corrective Action Required
12/17/2020

A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy.
Basement opening elevations
Corrective Action Required
12/17/2020

Minimum Building Opening Elevation (MBOE) and location on structure must be provided on the plot plan. MISSING MLO FROM MDP TABLE FOR THIS LOT.
Planning Review (RES) Approved 12/18/2020 12/16/2020
Shannon McGuire
Residential Plan Review Approved 12/03/2020 12/02/2020
Dylan Eppert
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $871.64 $871.64 Paid 12/21/2020
8331507-Sewer Connection Fee $390.00 $390.00 Paid 12/21/2020
8331401-Water Tap Fee $3,581.00 $3,581.00 Paid 12/21/2020
8350015-Water Meter Fee $455.54 $455.54 Paid 12/21/2020
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 12/21/2020
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 12/21/2020
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 07/20/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 07/20/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 07/20/2021
9110080-3rd and Subsequent Inspection Fee (Per Hour) $50.00 $50.00 Paid 07/20/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Failed 1/7/2021 01/07/2021
Misc
Corrective Action Required
01/07/2021
- FOOTING & FOUNDATION WALLS POURED NO 3RD PARTY INSPECTION SUBMITTED IN 48 HOURS -
Piers/Caissons Inspection - Residential Passed 12/28/2020 01/20/2021
Misc
Informational
01/20/2021
3RD PARTY PIERS BY DEREK PEREZ @ RES SIGNED & SEALED BY BRADLEY HUXOL
Footing Inspection - Residential Passed 12/28/2020 at 9:55 AM 01/20/2021
Misc
Resolved
01/20/2021
- FOOTING & FOUNDATION WALLS POURED NO 3RD PARTY INSPECTION SUBMITTED IN 48 HOURS -
Misc
Informational
01/20/2021
3RD PARTY FOOTING BY DEREK PEREZ @ RES SIGNED & SEALED BY BRADLEY HUXOL
Underslab Plumbing Inspection - Residential Failed 1/21/2021 1/21/2021 01/21/2021
Misc
Corrective Action Required
01/21/2021
- PROVIDE INTERIOR UNDERSLAB DRAIN TILE - SEC. 7-919 / R 506.2.5 -
Underslab Plumbing Inspection - Residential Not Ready 1/26/2021 1/26/2021 01/26/2021
Misc
Corrective Action Required
01/21/2021
- PROVIDE INTERIOR UNDERSLAB DRAIN TILE - SEC. 7-919 / R 506.2.5 -
Erosion Control Inspection Residential Failed 2/1/2021 02/01/2021
DCM6 ESC INSP DENIED STREET CLEAN UP
Corrective Action Required
02/01/2021
- STREET CLEAN UP REQUIRED IMMEDIATELY - - MAINTAIN SILT FENCE - - MAINTAIN GRAVEL FILTER -
Underslab Plumbing Inspection - Residential Passed 2/1/2021 2/1/2021 02/01/2021
Misc
Resolved
02/01/2021
Piers/Caissons Inspection - Residential Passed 2/26/2021 (1:00) 2/26/2021 02/26/2021
Misc
Informational
02/26/2021
(2) 24 X 36 W/ (4) # 4 VERT BARS PER PLAN
Sewer Service Inspection - R Passed 3/10/2021 (11:15) 3/10/2021 03/10/2021
Water Service Inspection - R Passed 3/11/2021 (10:00) 3/11/2021 03/11/2021
Electrical Service Inspection Passed 4/9/2021 4/9/2021 04/09/2021
Gas Service Inspection - Residential Passed 4/9/2021 4/9/2021 04/09/2021
All Rough Inspection - Residential Failed 4/9/2021 4/9/2021 04/09/2021
Miscellaneous Correction
Corrective Action Required
04/09/2021
-Unable to verify nailing pattern at header PFH -Anchor bolt at PFH not in middle third of plate -Nail top plate to header at PFH (2) rows 16d sinkers 3" OC per code-see detail in plans -Nail corners and intersecting wall studs per code -Seal plate penetrations garage north wall -Seal gap in dead space FB at stairwell/bath ! -Nail stud shoes in bath -Seal gaps in FB at fireplace -Expose all trusses and connections for inspection at front porch and covered deck -FB dead space at fridge -FB tub trap bath 2 -Seal penetrations at dead space Bed 2 -Repair/ replace cracked stud at north wall bed 2 -Repair and support top plate in bed 2 over notched at girder truss bearing -Provide (4) studs at girder truss bearing locations per plan -Expose P1 trusses for inspection -Truss bracing per plan -Address post to beam connections in basement -Address beam extension in basement -Tighten anchor bolt by electrical panel north wall -Seal all gaps and penetrations in FB at fur out walls -Vertical FB is more than 10' OC in fur out walls -Seal penetrations in soffit FB south wall -Support gas line per code with approved means in soffit south wall -Sister 2x6 studs at over notched cripple wall studs south wall -FB at soffit near basement door -Seal gaps and nail furring at beam bed 4 -Provide (3) studs in NW corner wall per code -Missing egress window -Double 2x6 studs under double joists north wall -Provide angle clips at end joists to ledger connection at deck -Provide (2) through bolts at beam to post connections per code
All Rough Inspection - Residential Not Ready 4/15/2021 4/15/2021 04/15/2021
Miscellaneous Correction
Corrective Action Required
04/09/2021
-Unable to verify nailing pattern at header PFH -Nail top plate to header at PFH (2) rows 16d sinkers 3" OC per code-see detail in plans -Nail corners and intersecting wall studs per code -Seal plate penetrations garage north wall -Seal gap in dead space FB at stairwell/bath ! -Seal gaps in FB at fireplace -Expose all trusses and connections for inspection at front porch and covered deck -FB dead space at fridge -FB tub trap bath 2 -Seal penetrations at dead space Bed 2 -Expose P1 trusses for inspection -Truss bracing per plan C-4 -Address post to beam connections in basement -Address beam extension in basement -Tighten anchor bolt by electrical panel north wall -Seal all gaps and penetrations in FB at fur out walls -Vertical FB is more than 10' OC in fur out walls -Seal gaps and nail furring at beam bed 4 -Missing egress window -Double 2x6 studs under double joists north wall -Provide angle clips at end joists to ledger connection at deck -Provide (2) through bolts at beam to post connections per code
All Rough Inspection - Residential Not Ready 4/22/2021 4/22/2021 04/22/2021
Miscellaneous Correction
Corrective Action Required
04/15/2021
-Unable to verify nailing pattern at header PFH -Nail top plate to header at PFH (2) rows 16d sinkers 3" OC per code-see detail in plans -Nail corners and intersecting wall studs per code -Seal plate penetrations garage north wall -Seal gap in dead space FB at stairwell/bath ! -Seal gaps in FB at fireplace -Expose all trusses and connections for inspection at front porch and covered deck -FB dead spac -FB tub trap bath 2 -Seal penetrations at dead space Bed 2 -Expose P1 trusses for inspection -Truss bracing per plan C-4 -Address post to beam connections in basement -Address beam extension in basement -Tighten anchor bolt by electrical panel north wall -Seal all gaps and penetrations in FB at fur out walls -Vertical FB is more than 10' OC in fur out walls -Seal gaps and nail furring at beam bed 4 -Missing egress window -Provide (2) through bolts at beam to post connections per code
All Rough Inspection - Residential Failed 4/27/2021 4/27/2021 04/27/2021
Miscellaneous Correction
Corrective Action Required
04/22/2021
-Seal nail holes in moisture barrier at PFH -Nail top plate to header at PFH (2) rows 16d sinkers 3" OC per code-see detail in plans -Expose all trusses and connections for inspection at covered deck -Complete corrections at P1 trusses per engineered letter -Address post to beam connections in basement where flanges are damaged and bent -Missing egress window -Provide (2) through bolts at beam to post connections per code
All Rough Inspection - Residential Passed 4/29/2021 4/29/2021 04/29/2021
Miscellaneous Correction
Resolved
04/29/2021
Driveway Inspection Partial 4/29/2021 4/29/2021 04/29/2021
Miscellaneous Correction
Corrective Action Required
01/07/2021
- FOOTING & FOUNDATIONS WALLS POURED NO 3RD PARTY INSPECTION SUBMITTED WITHIN 48 HOURS OF POUR -
Misc
Informational
04/29/2021
4-29-21 1:39pm The forms are set and the aggregate is in and compacted.
Driveway Inspection Passed 5/7/2021 5/7/2021 05/07/2021
Miscellaneous Correction
Corrective Action Required
04/29/2021
- FOOTING & FOUNDATIONS WALLS POURED NO 3RD PARTY INSPECTION SUBMITTED WITHIN 48 HOURS OF POUR -
Misc
Informational
04/29/2021
4-29-21 1:39pm The forms are set and the aggregate is in and compacted.
Misc
Informational
05/07/2021
Finished driveway meets LS specs. RP 5-7-21
Plot Plan Inspection Passed 7/19/2021 07/19/2021
Occupancy Inspection - Codes Residential Failed 7/19/2021 7/19/2021 07/19/2021
Misc
Corrective Action Required
04/29/2021
-Provide (2) through bolts at beam to post connections per code - PAY OUTSTANDING FEES - - SUBMIT BACKFLOW CERTIFICATION - Provide sod & splash blocks Sump discharge 36" from foundation Remove dust covers from smoke detectors Provide two 3" screws in each exterior hinge & db strike plate Provide through bolts deck beam Address 6x6 cedar post not continuous per plan Seal exterior penetrations, top of meter can, AC disconnect, top of light fixtures, gas line
Occupancy Inspection - Codes Residential Full C of O 7/21/2021 7/21/2021 07/21/2021
Misc
Resolved
07/21/2021
Documents & Images
Date Uploaded File Type Document Name
12/01/2020 Application Form W2 #6 - Permit App
12/01/2020 6 WOODSIDE RIDGE ROOF LAYOUT
12/01/2020 LOT 6 FINAL
12/01/2020 W2 #6 - Charlotte - Tuscan - Sheets- signed
12/01/2020 2532255 RF SEAL 11232020
12/02/2020 Specifications APPROVED TRUSS PACKAGE
12/02/2020 Drawing APPROVED TRUSS LAYOUT
12/10/2020 Plans APPROVED HOUSE PLAN
12/17/2020 Letter Codes Residential Plan Review
12/21/2020 Plot Plan APPROVED PLOT PLAN
12/21/2020 Receipt Receipt for transaction:2020-008139
12/21/2020 Letter DS Building Permit
01/07/2021 Letter INSPECTION SUMMARY
01/07/2021 Letter INSPECTION SUMMARY
01/20/2021 W2 Lot 6 - 110 nw Grady Ct-- Footing inspection
01/20/2021 Letter INSPECTION SUMMARY
01/20/2021 Letter INSPECTION SUMMARY
01/21/2021 Letter INSPECTION SUMMARY
01/26/2021 Letter INSPECTION SUMMARY
02/01/2021 Letter INSPECTION SUMMARY
02/01/2021 Letter INSPECTION SUMMARY
02/26/2021 Letter INSPECTION SUMMARY
03/10/2021 Letter INSPECTION SUMMARY
03/11/2021 Letter INSPECTION SUMMARY
04/09/2021 Letter INSPECTION SUMMARY
04/09/2021 Letter INSPECTION SUMMARY
04/09/2021 Letter INSPECTION SUMMARY
04/14/2021 2532255 B1 REP 04142021
04/14/2021 2532255 A3 REP 04142021
04/15/2021 Letter INSPECTION SUMMARY
04/15/2021 Letter INSPECTION SUMMARY
04/22/2021 Letter INSPECTION SUMMARY
04/23/2021 Lot 6 Woodside Ridge - I-beam Verification
04/26/2021 Repair for P1 truss W2-6
04/26/2021 Approved Plans Approved Truss Package
04/27/2021 Letter INSPECTION SUMMARY
04/27/2021 Lot 6 Woodside Ridge - I-beam Verification
04/28/2021 Approved Plans Approved Revised Truss Package
04/29/2021 Letter INSPECTION SUMMARY
04/29/2021 Letter INSPECTION SUMMARY
05/07/2021 Letter INSPECTION SUMMARY
07/02/2021 6 Woodside Ridge deck beam attachment letter
07/19/2021 Letter INSPECTION SUMMARY
07/19/2021 Letter INSPECTION SUMMARY
07/20/2021 Receipt Receipt for transaction:2021-005755
07/20/2021 Letter Backflow Letter
07/20/2021 6 Woodside Ridge deck beam attachment and non-continuous post letter
07/21/2021 Letter Field Certificate of Occupancy
07/21/2021 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home