Permit Application Status

PRRES20191083


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20191083
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE, UNFINISHED BASEMENT
04/26/2019
05/07/2019
05/12/2020
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
VALERIE@SUMMITHOMESKC.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
KIMBEL MECHANICAL SYSTEMS, INC, Address:1936 N SHILOH DR, Phone:(479) 756-1099  
Reviews
Review Type Outcome Est. Completion Date Completed
Residential Plan Review Approved 04/30/2019 05/07/2019
Development Center
Miscellaneous Correction
Corrective Action Required
04/29/2019

The address on the application shows 109 SE Meadowbrook Dr. it needs to show 109 SW Meadowbrook Dr. on the application and the 2 sets of drawings.
Plot Plan Review Approved 04/30/2019 05/03/2019
Steve Conrick
Legal description
Corrective Action Required
04/29/2019

The legal description, including plat or phase number and lot number, and street address must be provided on the plot plan. *Change SE to SW Meadowbrook
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,245.63 $1,245.63 Paid 05/07/2019
8331507-Sewer Connection Fee $600.00 $600.00 Paid 05/07/2019
8331401-Water Tap Fee $3,409.00 $3,409.00 Paid 05/07/2019
8350015-Water Meter Fee $408.37 $408.37 Paid 05/07/2019
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 05/07/2019
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 05/07/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 6/13/2019 06/13/2019
Sewer Service Inspection - R Passed 7/11/2019 (9:30) 7/11/2019 at 9:45 AM 07/11/2019
Water Service Inspection - R Partial 7/11/2019 07/11/2019
Water Service Inspection - R Passed 7/11/2019 at 2:00 PM 07/11/2019
Underslab Plumbing Inspection - Residential Passed 7/16/2019 7/16/2019 at 9:16 AM 07/16/2019
Piers/Caissons Inspection - Residential Passed 7/23/2019 7/23/2019 07/23/2019
Electrical Service Inspection Failed 10/7/2019 10/7/2019 10/07/2019
Miscellaneous Correction
Corrective Action Required
10/07/2019
No key in lock box
Gas Piping Inspection - Residential Failed 10/7/2019 10/7/2019 10/07/2019
Miscellaneous Correction
Corrective Action Required
10/07/2019
No key in lock box
All Rough Inspection - Residential Failed 10/7/2019 10/7/2019 10/07/2019
Misc
Corrective Action Required
10/07/2019
No key in lock box
Electrical Service Inspection Passed 10/9/2019 10/9/2019 10/09/2019
Miscellaneous Correction
Corrective Action Required
10/07/2019
No key in lock box
Gas Piping Inspection - Residential Passed 10/9/2019 10/9/2019 10/09/2019
Miscellaneous Correction
Corrective Action Required
10/07/2019
No key in lock box
All Rough Inspection - Residential Passed 10/9/2019 10/9/2019 10/09/2019
Misc
Corrective Action Required
10/07/2019
No key in lock box
Driveway Inspection Passed 11/1/2019 11/1/2019 11/05/2019
Sidewalk Inspection Partial 11/20/2019 11/20/2019 11/20/2019
Misc
Informational
11/20/2019
PRE POUR INSPECTION The forms are set and there appears to be sufficient compacted aggregate.
Sidewalk Inspection Partial 11/27/2019 12/09/2019
Misc
Informational
11/20/2019
PRE POUR INSPECTION The forms are set and there appears to be sufficient compacted aggregate.
Misc
Corrective Action Required
12/09/2019
The sidewalk is not complete. The ADA ramp that the sidewalk will be tying into on the west side of the property is not the correct type of ramp. The ramp will need to be removed and replaced with a Type B ADA ramp.
Occupancy Inspection - Codes Residential Failed 1/7/2020 1/7/2020 01/07/2020
Misc
Corrective Action Required
01/07/2020
- Final grade, sod, splash blocks - sidewalk approval and needs poured - guard rail needs to be installed on front porch, east side - dish washer water line needs hammer arrestor installed - dishwasher drain line needs to be secured above connection to garbage disposal - Landing needed for the deck stairs - label garage electrical panel - window adjacent to back door needs to be tempered - anti siphon devise screw needs to be installed correctly - sump pump discharge pipe needs to be cut back to code
Sidewalk Inspection Partial 2/3/2020 (P.M.) 2/3/2020 02/03/2020
Misc
Informational
12/09/2019
PRE POUR INSPECTION The forms are set and there appears to be sufficient compacted aggregate.
Misc
Corrective Action Required
12/09/2019
The sidewalk is not complete. The ADA ramp that the sidewalk will be tying into on the west side of the property is not the correct type of ramp. The ramp will need to be removed and replaced with a Type B ADA ramp.
Misc
Informational
02/03/2020
PRE POUR INSPECTION ADA ramp is formed up. There appears to be sufficient compacted aggregate.
Sidewalk Inspection Passed 2/7/2020 03/03/2020
Misc
Corrective Action Required
02/03/2020
The sidewalk is not complete. The ADA ramp that the sidewalk will be tying into on the west side of the property is not the correct type of ramp. The ramp will need to be removed and replaced with a Type B ADA ramp.
Misc
Informational
02/03/2020
PRE POUR INSPECTION The forms are set and there appears to be sufficient compacted aggregate.
Misc
Informational
02/03/2020
PRE POUR INSPECTION ADA ramp is formed up. There appears to be sufficient compacted aggregate.
Misc
Informational
03/03/2020
Sidewalk and ADA ramp are complete and appear to be in compliance.
Gas Service Inspection - Residential Passed 10/9/2019 03/10/2020
Occupancy Inspection - Codes Residential Temporary C of O 3/10/2020 3/10/2020 03/10/2020
Misc
Corrective Action Required
01/07/2020
- Final grade, sod, splash blocks - guard rail needs to be installed on front porch, east side or raise grade to 30” - sump pump discharge pipe needs to be cut back to code
Erosion Control Inspection Residential Passed 05/12/2020
Plot Plan Inspection Passed 05/12/2020
Occupancy Inspection - Codes Residential Full C of O 5/12/2020 5/12/2020 05/12/2020
Misc
Resolved
05/12/2020
- Final grade, sod, splash blocks - guard rail needs to be installed on front porch, east side or raise grade to 30” - sump pump discharge pipe needs to be cut back to code
Documents & Images
Date Uploaded File Type Document Name
04/29/2019 Letter Codes Residential Plan Review
04/29/2019 Letter Codes Residential Plan Review
05/07/2019 Receipt Receipt for transaction: 2019-001802
05/07/2019 Letter Codes Building Permit
05/08/2019 Plot Plan DOC050819-05082019131410
06/13/2019 Letter INSPECTION SUMMARY
07/11/2019 Letter INSPECTION SUMMARY
07/11/2019 Letter INSPECTION SUMMARY
07/11/2019 Letter INSPECTION SUMMARY
07/16/2019 Letter INSPECTION SUMMARY
07/23/2019 Letter INSPECTION SUMMARY
10/07/2019 Letter INSPECTION SUMMARY
10/07/2019 Letter INSPECTION SUMMARY
10/07/2019 Letter INSPECTION SUMMARY
10/09/2019 Letter INSPECTION SUMMARY
10/09/2019 Letter INSPECTION SUMMARY
10/09/2019 Letter INSPECTION SUMMARY
11/05/2019 Letter INSPECTION SUMMARY
11/20/2019 Letter INSPECTION SUMMARY
12/09/2019 Letter INSPECTION SUMMARY
01/07/2020 Letter INSPECTION SUMMARY
02/03/2020 Letter INSPECTION SUMMARY
03/03/2020 Letter INSPECTION SUMMARY
03/03/2020 Letter INSPECTION SUMMARY
03/10/2020 Letter Codes Temporary Certificate of Occupancy
03/10/2020 Letter INSPECTION SUMMARY
05/12/2020 Letter Codes Final Certificate of Occupancy
05/12/2020 Letter Field Certificate of Occupancy
05/12/2020 Letter INSPECTION SUMMARY
05/12/2020 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home