Summary
PRRES20183473
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - UNFINISHED BASEMENT - COVERED DECK
10/09/2018
11/07/2018
11/04/2019
Locations
Contacts
SPELLERBERG ENTERPRISES LLC, Address:613 NE VIEWPARK DR, Phone:(816) 550-5535  
AFC HEATING AND COOLING, Address:824 NW MAIN ST , Phone:(816) 347-8388  
O'CONNELL ELECTRIC LLC, Address:11017 S ALLEY JACKSON RD, Phone:(816) 547-4706  
TRI-COUNTY PLUMBING LLC, Address:PO BOX 234, Phone:(816) 720-3222  
SPELLERBERGENTERPRISES@GMAIL.COM  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 10/31/2018 10/30/2018
Kim Brennan
Residential Plan Review Approved 10/11/2018 10/23/2018
Kim Brennan
03 Two (2) plot plans
Corrective Action Required
10/09/2018

Two (2) plot plans
12 Detail required separation between garage and living area including door
Corrective Action Required
10/09/2018

Detail required separation between garage and living area including door, door closer and gypsum board. (IRC R302.5)
22 Beam and column locations, sizes and material.
Corrective Action Required
10/09/2018

Beam and column locations, sizes and material. Please dimensionally locate column pad in garage
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,180.62 $1,180.62 Paid 11/07/2018
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 11/07/2018
8331507-Sewer Connection Fee $450.00 $450.00 Paid 11/07/2018
8331401-Water Tap Fee $3,409.00 $3,409.00 Paid 11/07/2018
8350015-Water Meter Fee $408.37 $408.37 Paid 11/07/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 11/8/2018 (11:30) 11/8/2018 at 1:10 PM 11/08/2018
Water Service Inspection - R Passed 12/6/2018 (1:00) 12/6/2018 at 2:50 PM 12/06/2018
Sewer Service Inspection - R Passed 12/13/2018 (11:15) 12/13/2018 at 1:15 PM 12/13/2018
Underslab Plumbing Inspection - Residential Passed 12/17/2018 12/17/2018 at 8:15 AM 12/17/2018
Gas Piping Inspection - Residential Passed 4/5/2019 at 10:45 AM 04/05/2019
Electrical Service Inspection Passed 4/5/2019 at 10:55 AM 04/05/2019
All Rough Inspection - Residential Passed 4/5/2019 4/5/2019 at 11:05 AM 04/05/2019
Gas Service Inspection - Residential Passed 04/05/2019
Piers/Caissons Inspection - Residential Passed 5/15/2019 at 1:20 PM 05/15/2019
Driveway Inspection Partial 5/17/2019 at 8:00 AM 05/17/2019
Misc
Informational
05/17/2019
The driveway has been formed, 4" of rock has been compacted. It appears to have 6" of dept. He said they are planning on pouring on Monday. If it rains we will need to re-check the subgrade.Steve Robbins 05/17/2019 8:44 AM
Driveway Inspection Passed 5/24/2019 at 8:00 AM 05/24/2019
Misc
Informational
05/17/2019
The driveway has been formed, 4" of rock has been compacted. It appears to have 6" of dept. He said they are planning on pouring on Monday. If it rains we will need to re-check the subgrade.Steve Robbins 05/17/2019 8:44 AM
Misc
Informational
05/24/2019
The subgrade was re-checked and the approach has been poured and appears to meet all standard. On the plot plan is shows a sidewalk and ADA ramp being installed at the corner of Orchard and Main. I spoke with Hector, Kent and the builder and it appears that they paid a fee to not have to install the sidewalk, it will be a future development and as of now there are no sidewalks in the area.Steve Robbins 05/24/2019 9:24 AM
Occupancy Inspection - Codes Residential Failed 6/7/2019 6/7/2019 at 12:40 PM 06/07/2019
Misc
Corrective Action Required
06/07/2019
COMPLETE FINISH SITEWORK, GRADING PER APPROVED PLOT PLAN. ALL EXTERIOR SUBJECT TO APPROVAL WHEN COMPLETED.
Misc
Corrective Action Required
06/07/2019
PROVIDE EROSION CONTROL BEFORE REQUESTING TCO.
Misc
Corrective Action Required
06/07/2019
PAPER FACED INSULATION LEFT EXPOSED AT CLOSETS AT 2ND FLOOR NE & SE CONTRARY TO MANUFACTURER WARNING. SEE INSTRUCTIONS ON FACE OF MATERIAL.
Misc
Corrective Action Required
06/07/2019
NEC 210-8(B)(5); IRC 3902: GFCI PROTECTION OF ELECTRICAL RECEPTACLES: ELECTRICAL RECEPTACLES WITHIN 6' OF EDGE OF SINK MUST BE GFCI-PROTECTED. SEE UNDER COUNTER AT DINING AREA BAR.
Misc
Corrective Action Required
06/07/2019
ELECTRICAL RECEPTACLE BOX UNDER HYDRO TUB NOT SECURED TO STRUCTURE.
SEC. 7-1408.2 STRIKE PLATES
Corrective Action Required
06/07/2019
Exterior door strike plates shall be a minimum of 18 gauge metal with four offset screw holes. Strike plates shall be attached to wood with not less than three inch (3") wood screws, which shall have a minimum of one inch (1") penetration into the nearest stud. Note: For side lighted units, refer to Section 7-1408.5.
Misc
Corrective Action Required
06/07/2019
NEC 422.31B CIRCUIT BREAKERS FOR APPLIANCES RATED OVER 300 VOLT-AMPS OR 1/8 HORSEPOWER: IF TO SERVE AS DISCONNECT MUST BE LOCKABLE IF APPLIANCE IS WITHIN SIGHT OF PANELBOARD. INSTALL LOCK-OUT DEVICE ON KITCHEN RANGE CIRCUIT BREAKER. SEE KITCHEN RANGE CIRCUIT.
Occupancy Inspection - Codes Residential Failed 6/12/2019 6/12/2019 at 7:05 AM 06/12/2019
Misc
Corrective Action Required
06/07/2019
COMPLETE FINISH SITEWORK, GRADING PER APPROVED PLOT PLAN. ALL EXTERIOR SUBJECT TO APPROVAL WHEN COMPLETED.
Misc
Resolved
06/12/2019
PROVIDE EROSION CONTROL BEFORE REQUESTING TCO.
Misc
Resolved
06/12/2019
PAPER FACED INSULATION LEFT EXPOSED AT CLOSETS AT 2ND FLOOR NE & SE CONTRARY TO MANUFACTURER WARNING. SEE INSTRUCTIONS ON FACE OF MATERIAL.
Misc
Resolved
06/12/2019
NEC 210-8(B)(5); IRC 3902: GFCI PROTECTION OF ELECTRICAL RECEPTACLES: ELECTRICAL RECEPTACLES WITHIN 6' OF EDGE OF SINK MUST BE GFCI-PROTECTED. SEE UNDER COUNTER AT DINING AREA BAR.
Misc
Resolved
06/12/2019
ELECTRICAL RECEPTACLE BOX UNDER HYDRO TUB NOT SECURED TO STRUCTURE.
SEC. 7-1408.2 STRIKE PLATES
Resolved
06/12/2019
Exterior door strike plates shall be a minimum of 18 gauge metal with four offset screw holes. Strike plates shall be attached to wood with not less than three inch (3") wood screws, which shall have a minimum of one inch (1") penetration into the nearest stud. Note: For side lighted units, refer to Section 7-1408.5.
Misc
Corrective Action Required
06/12/2019
NEC 422.31B CIRCUIT BREAKERS FOR APPLIANCES RATED OVER 300 VOLT-AMPS OR 1/8 HORSEPOWER: IF TO SERVE AS DISCONNECT MUST BE LOCKABLE IF APPLIANCE IS NOT WITHIN SIGHT OF PANELBOARD. INSTALL LOCK-OUT DEVICE ON BREAKER. SEE OVEN CIRCUIT.
Occupancy Inspection - Codes Residential Temporary C of O 6/17/2019 at 1:10 PM 06/17/2019
Misc
Corrective Action Required
06/12/2019
COMPLETE FINISH SITEWORK, GRADING PER APPROVED PLOT PLAN. ALL EXTERIOR SUBJECT TO APPROVAL WHEN COMPLETED.
Misc
Corrective Action Required
06/12/2019
NEC 422.31B CIRCUIT BREAKERS FOR APPLIANCES RATED OVER 300 VOLT-AMPS OR 1/8 HORSEPOWER: IF TO SERVE AS DISCONNECT MUST BE LOCKABLE IF APPLIANCE IS NOT WITHIN SIGHT OF PANELBOARD. INSTALL LOCK-OUT DEVICE ON BREAKER. SEE OVEN CIRCUIT.
Erosion Control Inspection Residential Passed 06/17/2019
Miscellaneous Inspection Passed 6/17/2019 06/17/2019
Occupancy Inspection - Codes Residential Full C of O 11/4/2019 11/04/2019
Misc
Resolved
11/04/2019
COMPLETE FINISH SITEWORK, GRADING PER APPROVED PLOT PLAN. ALL EXTERIOR SUBJECT TO APPROVAL WHEN COMPLETED.
Misc
Resolved
11/04/2019
NEC 422.31B CIRCUIT BREAKERS FOR APPLIANCES RATED OVER 300 VOLT-AMPS OR 1/8 HORSEPOWER: IF TO SERVE AS DISCONNECT MUST BE LOCKABLE IF APPLIANCE IS NOT WITHIN SIGHT OF PANELBOARD. INSTALL LOCK-OUT DEVICE ON BREAKER. SEE OVEN CIRCUIT.
Plot Plan Inspection Passed 11/04/2019
Documents & Images
Date Uploaded File Type Document Name
10/09/2018 Letter Codes Residential Plan Review
11/07/2018 Receipt Receipt for transaction: 2018-007153
11/07/2018 Letter Codes Building Permit
11/08/2018 Letter Inspection Summary
11/12/2018 Plot Plan DOC111218-11122018100647
12/06/2018 Letter INSPECTION SUMMARY
12/13/2018 Letter INSPECTION SUMMARY
12/17/2018 Letter INSPECTION SUMMARY
04/05/2019 Letter INSPECTION SUMMARY
04/05/2019 Letter INSPECTION SUMMARY
04/05/2019 Letter INSPECTION SUMMARY
04/05/2019 Letter INSPECTION SUMMARY
05/15/2019 Letter INSPECTION SUMMARY
05/17/2019 Letter DE-Daily Inspection Summary
05/24/2019 Letter DE-Daily Inspection Summary
06/07/2019 Letter INSPECTION SUMMARY
06/12/2019 Letter INSPECTION SUMMARY
06/17/2019 Letter Codes Temporary Certificate of Occupancy
11/04/2019 Letter Field Certificate of Occupancy
11/05/2019 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home