Permit Application Status

PRRES20113266


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20113266
Building Permit - Residential
Certificate of Occupancy
FRITCHIE LAND DEVELOPMENT LLC
NEW SINGLE FAMILY
HOUSE AND DECK
06/24/2011
07/08/2011
01/03/2012
Locations
Contacts
SUMMIT CUSTOM HOMES LLC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
C.D. MCCLAIN ELECTRICAL, Address:3424 NW DUNCAN RD, Phone:(816) 220-1477  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
CENTURY PLUMBING, Address:14001 CENTURY LN, Phone:(816) 765-6066  
FRITCHIE LAND DEVELOPMENT LLC, Address:1412 NE VALLEY FORGE DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 07/08/2011
Codes Admin
Plot Plan Review Approved 07/07/2011
Gene Williams, P.E.
Plot Plan Review (P&D) Approved 06/28/2011 06/29/2011
Christina Alexander
Corrective Action Required
06/30/2011

Need FE at NW and SW property corners.
Corrective Action Required
06/30/2011

No walkout allowed based on elevations given and MBOE of 963.0'.
Plot Plan Review Rejected 06/29/2011
Christina Alexander
NEEDS FINISH GRADE @ NW & SW CORNERS, NO WALKOUT ALLOWED BASED ON ELEVATIONS GIVEN & MBOE OF 963.0.
License Tax Codes Approved 06/28/2011 06/24/2011
Codes Admin
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $790.84 $790.84 Paid 07/08/2011
8350015-Water Meter Fee $253.99 $253.99 Paid 07/08/2011
8331401-Water Tap Fee $2,994.00 $2,994.00 Paid 07/08/2011
8331507-Sewer Connection Fee $330.00 $330.00 Paid 07/08/2011
9110073-Right of Way Permit Fee $60.00 $60.00 Paid 07/08/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 7/27/2011 (11:30) 7/27/2011 at 12:00 AM 07/27/2011
Underslab Plumbing Inspection - Residential Passed 8/10/2011 8/10/2011 at 12:00 AM 08/10/2011
Sewer Service Inspection - R Partial 8/10/2011 at 12:00 AM 08/10/2011
Sewer Service Inspection - R Passed 8/10/2011 (10:30) 8/10/2011 at 12:00 AM 08/10/2011
Water Service Inspection - R Partial 8/10/2011 (10:30) 8/10/2011 at 12:00 AM 08/10/2011
Water Service Inspection - R Passed 8/11/2011 (8:45) 8/11/2011 at 12:00 AM 08/11/2011
Electrical Service Inspection Passed 9/21/2011 at 12:00 AM 09/21/2011
Gas Service Inspection - Residential Passed 9/21/2011 at 12:00 AM 09/21/2011
Gas Piping Inspection - Residential Passed 9/21/2011 at 12:00 AM 09/21/2011
All Rough Inspection - Residential Failed 9/21/2011 (8:00 to 5:00) 9/21/2011 at 12:00 AM 09/21/2011
Misc
Corrective Action Required
09/21/2011
-BRACE INTERIOR WALLS PER PLAN -INSTALL DOUBLE JOIST IN LINE WITH DOUBLE PAD IN BASEMENT PER PLAN
Misc
Corrective Action Required
09/21/2011
INSTALL FLASHING ABOVE GARAGE TRIMS
Misc
Corrective Action Required
09/21/2011
PROTECT NM ELECTRICAL WIRE AT GARAGE BRACE WALL CORNER; AT KITCHEN WALL NEAR SINK; INSTALL RUNNING BOARD TO PROTECT WIRING WITHIN 6FT OF ATTIC ACCESS
Misc
Corrective Action Required
09/21/2011
ANCHOR GARAGE AND BASEMENT SILL PLATE: ANCHOR WITHIN 12" OF BREAK, MINIMUM 2 ANCHORS PER PLATE
Misc
Corrective Action Required
09/21/2011
INSTALL ATTIC ACCESS TO ROOF ABOVE GARAGE
Misc
Corrective Action Required
09/21/2011
GARAGE FRAMING NOT COMPLETED. COMPLETE SOFFIT AND CHASE AND FIREBLOCK AS REQUIRED
Misc
Corrective Action Required
09/21/2011
FIREBLOCKING: -FB B-VENT/DUCT CHASE FROM JOIST SPACE -FB ALL FLOOR PENETRATIONS BY DUCTS -FB AT ALL TRAPS
Misc
Corrective Action Required
09/21/2011
EXTERIOR DOOR: -BLOCK STUD AT STRIKE PLATE HEIGHT -FILL IN VOID BEHIND HINGES AND AT STRIKE PLATE SIDE (FROM 12" ABOVE TO 12" BELOW STRIKE PLATE)
Misc
Corrective Action Required
09/21/2011
PROVIDE MINIMUM 1" CLEARANCE FROM FIREPLACE B-VENT TO COMBUSTIBLE
Misc
Corrective Action Required
09/21/2011
ABOVE LIVING ROOM: -PROVIDE ENGINEER REPORT FOR CONSECUTIVE OVERBORED JOISTS BY 3" PVC ABOVE LIVING RM -INSTALL DOUBLE TRIMMER JOIST FOR FRAME OPENING MORE THAN 3 FT FROM WALL SUPPORT
Misc
Corrective Action Required
09/21/2011
OVERFILLED DOUBLE GANG ELECTRICAL BOX AT STAIR BOTTOM LANDING IN BASEMENT
Misc
Corrective Action Required
09/21/2011
BASEMENT: -INSTALL HANGERS FOR DOUBLE JOIST UNDER FIREPLACE -INSTALL HANGERS (OR OTHER CONNECTOR) TO CONNECT JOISTS TO WINDOW HEADERS -STRAP ALL CUT WALL TOP PLATE AND NAIL MINIMUM 8-16D NAILS ON EACH SIDE -ANCHOR SILL PLATE WITHIN MINIMUM 2 ANCHORS PER PLATE -INSTALL CORNER STUD AND NAIL SIDING
All Rough Inspection - Residential Failed 9/23/2011 (8:00 to 5:00) 9/23/2011 at 12:00 AM 09/23/2011
Misc
Resolved
09/23/2011
-BRACE INTERIOR WALLS PER PLAN -INSTALL DOUBLE JOIST IN LINE WITH DOUBLE PAD IN BASEMENT PER PLAN
Misc
Resolved
09/23/2011
INSTALL FLASHING ABOVE GARAGE TRIMS
Misc
Corrective Action Required
09/21/2011
PROTECT NM ELECTRICAL WIRE AT GARAGE BRACE WALL CORNER; AT KITCHEN WALL NEAR SINK; INSTALL RUNNING BOARD TO PROTECT WIRING WITHIN 6FT OF ATTIC ACCESS
Misc
Resolved
09/23/2011
ANCHOR GARAGE AND BASEMENT SILL PLATE: ANCHOR WITHIN 12" OF BREAK, MINIMUM 2 ANCHORS PER PLATE
Misc
Resolved
09/23/2011
INSTALL ATTIC ACCESS TO ROOF ABOVE GARAGE
Misc
Resolved
09/23/2011
GARAGE FRAMING NOT COMPLETED. COMPLETE SOFFIT AND CHASE AND FIREBLOCK AS REQUIRED
Misc
Resolved
09/23/2011
FIREBLOCKING: -FB ALL FLOOR PENETRATIONS BY DUCTS
Misc
Resolved
09/23/2011
EXTERIOR DOOR: -BLOCK STUD AT STRIKE PLATE HEIGHT -FILL IN VOID BEHIND HINGES AND AT STRIKE PLATE SIDE (FROM 12" ABOVE TO 12" BELOW STRIKE PLATE)
Misc
Resolved
09/23/2011
PROVIDE MINIMUM 1" CLEARANCE FROM FIREPLACE B-VENT TO COMBUSTIBLE
Misc
Resolved
09/23/2011
ABOVE LIVING ROOM: -PROVIDE ENGINEER REPORT FOR CONSECUTIVE OVERBORED JOISTS BY 3" PVC ABOVE LIVING RM -INSTALL DOUBLE TRIMMER JOIST FOR FRAME OPENING MORE THAN 3 FT FROM WALL SUPPORT
Misc
Corrective Action Required
09/21/2011
OVERFILLED DOUBLE GANG ELECTRICAL BOX AT STAIR BOTTOM LANDING IN BASEMENT
Misc
Resolved
09/23/2011
BASEMENT: -INSTALL HANGERS FOR DOUBLE JOIST UNDER FIREPLACE -INSTALL HANGERS (OR OTHER CONNECTOR) TO CONNECT JOISTS TO WINDOW HEADERS -STRAP ALL CUT WALL TOP PLATE AND NAIL MINIMUM 8-16D NAILS ON EACH SIDE -ANCHOR SILL PLATE WITHIN MINIMUM 2 ANCHORS PER PLATE -INSTALL CORNER STUD AND NAIL SIDING
All Rough Inspection - Residential Failed 9/26/2011 (8:00 to 5:00) 9/26/2011 at 12:00 AM 09/26/2011
Misc
Corrective Action Required
09/23/2011
PROTECT NM ELECTRICAL WIRE AT GARAGE BRACE WALL CORNER; AT KITCHEN WALL NEAR SINK; INSTALL RUNNING BOARD TO PROTECT WIRING WITHIN 6FT OF ATTIC ACCESS
Misc
Corrective Action Required
09/23/2011
OVERFILLED DOUBLE GANG ELECTRICAL BOX AT STAIR BOTTOM LANDING IN BASEMENT *THIS IS A 3RD INSPECTION AND ELECTRCIAN FAILED TO CORRECT THE DEFICIENCIES. WASTED TRIP FEE ACCESSED
All Rough Inspection - Residential Passed 9/27/2011 9/27/2011 at 12:00 AM 09/27/2011
Misc
Resolved
09/27/2011
PROTECT NM ELECTRICAL WIRE AT GARAGE BRACE WALL CORNER; AT KITCHEN WALL NEAR SINK; INSTALL RUNNING BOARD TO PROTECT WIRING WITHIN 6FT OF ATTIC ACCESS
Misc
Resolved
09/27/2011
OVERFILLED DOUBLE GANG ELECTRICAL BOX AT STAIR BOTTOM LANDING IN BASEMENT *THIS IS A 3RD INSPECTION AND ELECTRCIAN FAILED TO CORRECT THE DEFICIENCIES. WASTED TRIP FEE ACCESSED
Driveway Inspection Passed 11/9/2011 at 10:00 AM 11/09/2011
Sidewalk Inspection Passed 11/09/2011
Occupancy Inspection - Codes Residential Failed 12/6/2011 12/6/2011 at 12:00 AM 12/06/2011
Misc
Corrective Action Required
12/06/2011
EXTERIOR: -SEAL EXTERIOR WALL PENETRATIONS AND EXTERIOR LUMINAIRES -ELECTRICAL: FRONT GFCI RECEPTACLE MISSING, DECK GFCI NOT TRIPPING, OPEN NEUTRAL A/C GFCI, ID A/C UNGROUNDED CONDUCTORS WITH PROPER COLOR -SECURE FRONT HOSE BIBB -DECK: LAG LEDGE BOARD AT EVERY JOIST; BLOCK NEWAL POSTS PER LS DECK GUILDLINE
Misc
Corrective Action Required
12/06/2011
GARAGE 1/2 HR FIRE SEPARATION SHALL BE PROVIDED AT GARAGE OPENERS AND AT WALL OPENING BELOW GARAGE OPENERS
Misc
Corrective Action Required
12/06/2011
SECURE AND SUPPORT ALL RECEPTACLES AT KITCHEN COUNTER
Misc
Corrective Action Required
12/06/2011
DECK DOOR: INSTALL 3" SCREWS AT UPPER STRIKE PLATE; INSTALL 2-3" SCREWS AT EACH HINGE
Misc
Corrective Action Required
12/06/2011
PROVIDE HOROZONTAL CLEARANCE FROM LUMINAIRE TO CLOTHES CLOSET SHELF PER CODE: 6" FOR FLOURESCENT OR 12" FOR INCANDESCENT LUMINAIRE
Misc
Corrective Action Required
12/06/2011
HYDROTUB MOTOR AND RECEPTACLE SHALL BE ACCESSIBLE. WHERE MOTOR IS LOCATED MORE THAN 2 FT FROM OPENING, OPENING SHALL BE MINIMUM 18"X18"
Misc
Corrective Action Required
12/06/2011
IN BASEMENT: -CORRECT FAULT IN "GUEST BEDROOM" AFCI BREAKER. RE-LABEL THIS BREAKER SINCE IT SERVES TWO BEDROOMS(?). LABEL WITH DIRECTION, IE SW, SE ETC -INSTALL MAXIMUM 35 AMP BREAKER FOR A/C UNIT -INSTALL CUTLER HAMMER BREAKER FOR KITCHEN GFCI -FIX FRAMING (CUT JOIST) UNDER 1ST FL 1/2 BATH
Occupancy Inspection - Codes Residential Temporary C of O 12/30/2011 at 12:00 AM 12/30/2011
Misc
Corrective Action Required
12/06/2011
EXTERIOR: -A/C GFCI NOT TRIPPING
Misc
Resolved
12/30/2011
GARAGE 1/2 HR FIRE SEPARATION SHALL BE PROVIDED AT GARAGE OPENERS AND AT WALL OPENING BELOW GARAGE OPENERS
Misc
Resolved
12/30/2011
SECURE AND SUPPORT ALL RECEPTACLES AT KITCHEN COUNTER
Misc
Resolved
12/30/2011
DECK DOOR: INSTALL 3" SCREWS AT UPPER STRIKE PLATE LS SECURITY CODE FYI: Sec. 7-1408.2. - Strike plates. Exterior door strike plates shall be a minimum of eighteen (18) gauge metal with four (4) offset screw holes. Strike plates shall be attached to wood with not less than three (3) inch wood screws, which shall have a minimum of one (1) inch penetration into the nearest stud. Note: For side lighted units, refer to Section 7-1408.5. (Ord. No. 6600, § 1, 3-13-2008; Ord. No. 6634, § 5, 6-5-2008)
Misc
Resolved
12/30/2011
PROVIDE HOROZONTAL CLEARANCE FROM LUMINAIRE TO CLOTHES CLOSET SHELF PER CODE: 6" FOR FLOURESCENT OR 12" FOR INCANDESCENT LUMINAIRE
Misc
Resolved
12/30/2011
HYDROTUB MOTOR AND RECEPTACLE SHALL BE ACCESSIBLE. WHERE MOTOR IS LOCATED MORE THAN 2 FT FROM OPENING, OPENING SHALL BE MINIMUM 18"X18"
Misc
Resolved
12/30/2011
IN BASEMENT: -CORRECT FAULT IN "GUEST BEDROOM" AFCI BREAKER. RE-LABEL THIS BREAKER SINCE IT SERVES TWO BEDROOMS(?). LABEL WITH DIRECTION, IE SW, SE ETC -INSTALL MAXIMUM 35 AMP BREAKER FOR A/C UNIT -INSTALL CUTLER HAMMER BREAKER FOR KITCHEN GFCI -FIX FRAMING (CUT JOIST) UNDER 1ST FL 1/2 BATH
Occupancy Inspection - Codes Residential Full C of O 1/3/2012 at 12:00 AM 01/03/2012
Misc
Resolved
01/03/2012
EXTERIOR: -A/C GFCI NOT TRIPPING
Misc
Resolved
12/30/2011
DECK DOOR: INSTALL 3" SCREWS AT UPPER STRIKE PLATE LS SECURITY CODE FYI: Sec. 7-1408.2. - Strike plates. Exterior door strike plates shall be a minimum of eighteen (18) gauge metal with four (4) offset screw holes. Strike plates shall be attached to wood with not less than three (3) inch wood screws, which shall have a minimum of one (1) inch penetration into the nearest stud. Note: For side lighted units, refer to Section 7-1408.5. (Ord. No. 6600, § 1, 3-13-2008; Ord. No. 6634, § 5, 6-5-2008)
Documents & Images
Date Uploaded File Type Document Name
07/08/2011 Letter Building Permit
07/08/2011 Plot Plan 20110708141202684.pdf
07/27/2011 Letter Inspection Summary
08/10/2011 Letter Inspection Summary
08/10/2011 Letter Inspection Summary
08/10/2011 Letter Inspection Summary
08/10/2011 Letter Inspection Summary
08/11/2011 Letter Inspection Summary
09/21/2011 Letter Inspection Summary
09/23/2011 Letter Inspection Summary
09/26/2011 Letter Re-Inspection Fee
09/26/2011 Letter Inspection Summary
09/27/2011 Letter Inspection Summary
12/06/2011 Letter Inspection Summary
12/30/2011 Letter Temporary Certificate of Occupancy
12/30/2011 Letter Temporary Certificate of Occupancy
01/03/2012 Letter Field Certificate of Occupancy
01/03/2012 Letter Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home