Review Type |
Outcome |
Est. Completion Date |
Completed |
Sprinkler Plan Review
|
Released for Construction
|
05/08/2025
|
04/25/2025
|
|
Craig Hill
|
|
|
Alarm Plan Review
|
Rejected
|
12/24/2024
|
12/18/2024
|
|
Craig Hill
|
|
Misc
Corrective Action Required
Remove horn strobes on the North patio. They are not required.
|
|
|
Fire Plan Review
|
Approved
|
08/20/2024
|
08/19/2024
|
|
Craig Hill
|
|
Construction documents - Fire protection systems
Corrective Action Required
2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Provide sprinkler plans for review and approval,and hood and hood suppression specifications.
|
|
Miscellaneous Correction
Corrective Action Required
Widen the cased opening into Corridor 110 to 44 inches.
|
|
Portable fire extinguishers - general
Corrective Action Required
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Show proposed locations of the fire extinguishers.
|
|
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
Location not shown. Provide at the manual pull station for the hood system with appropriate signage.
|
|
Emergency power for illumination
Corrective Action Required
2018 IFC 1008.3.1 & 3.2 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, an emergency electrical
system shall automatically illuminate all of the following:
1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress.
2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits.
3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits.
Provide exterior emergency lighting ove the exterior doors and patio.
|
|
|
Health Department Review
|
Approved
|
|
08/19/2024
|
|
Joe Frogge
|
|
|
Building Plan Review
|
Approved with Conditions
|
08/20/2024
|
08/13/2024
|
|
Joe Frogge
|
|
Health Dept Review
For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 797-7162. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit.
Action required: Comment is informational.
8/13/24 - Acknowledged in letter.
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7162. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required: Comment is informational.
8/13/24 - Acknowledged in letter.
|
|
Gen - Plan submittals 2018 codes
All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit.
Action required: Comment is informational. We have reviewed and will inspect golf area per ICC/ANSI A117.1-2009 1107. (1007 noted on drawings)
|
|
License Tax - Payment
Corrective Action Required
A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process.
Action required: Comment is for informational purposes. The fee will be $874.50.
(cooler is considered a building addition)
8/13/24 - Acknowledged in letter.
|
|
|
Licensed Contractors
|
Approved
|
08/13/2024
|
08/13/2024
|
|
Joe Frogge
|
|
|
Fire Plan Review
|
Rejected
|
08/09/2024
|
08/08/2024
|
|
Jim Eden
|
|
Construction documents - Fire protection systems
Corrective Action Required
2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Provide sprinkler plans for review and approval,and hood and hood suppression specifications.
|
|
Portable fire extinguishers - general
Corrective Action Required
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Show proposed locations of the fire extinguishers.
|
|
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
Location not shown. Provide at the manual pull station for the hood system with appropriate signage.
|
|
Emergency power for illumination
Corrective Action Required
2018 IFC 1008.3.1 & 3.2 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, an emergency electrical
system shall automatically illuminate all of the following:
1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress.
2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits.
3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits.
Provide exterior emergency lighting ove the exterior doors and patio.
|
|
|
Building Plan Review
|
Rejected
|
08/09/2024
|
08/07/2024
|
|
Joe Frogge
|
|
Health Dept Review
Corrective Action Required
For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 797-7162. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit.
Action required: Comment is informational.
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7162. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required: Comment is informational.
|
|
Gen - Plan submittals 2018 codes
Corrective Action Required
All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit.
Action required: Comment is informational. We have reviewed and will inspect golf area per ICC/ANSI A117.1-2009 1107. (1007 noted on drawings)
|
|
License Tax - Payment
Corrective Action Required
A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process.
Action required: Comment is for informational purposes. The fee will be $874.50.
(cooler is considered a building addition)
|
|
|
Licensed Contractors
|
Approved
|
08/09/2024
|
08/07/2024
|
|
Joe Frogge
|
|
|