ALTERATION COMMERCIAL
LEE'S SUMMIT SURGICAL CENTER - COFFEE KIOSK
04/04/2024
06/04/2024
10/13/2024
09/03/2024
Locations
Contacts
EXCEL CONSTRUCTORS, INC, Address:8041 W 47TH ST, Phone:(913) 261-1000  
Derek McCarthy - Excel Constructors, Phone:(913) 265-4852  
KASA ELECTRIC LLC, Address:1206 NW VALLEY RIDGE DR, Phone:(816) 228-4886  
VAUGHAN MECHANICAL INC, Address:4220 NE 34TH , Phone:(816) 453-3400  
GUY GRONBERG ARCHITECTS, Address:113 SE 3RD ST, Phone:(816) 524-0878  
Reviews
Review Type Outcome Est. Completion Date Completed
Health Department Review Approved 05/13/2024
Joe Frogge
Licensed Contractors Approved 04/16/2024 05/13/2024
Joe Frogge
LC - General Contractor
Resolved
05/13/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and the name, email address & phone number for the on-site contact which is where inspection reports will be sent. 4/16/24 - acknowledged in letter
LC - MEP Subs
Resolved
05/13/2024

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 4/16/24 - acknowledged in letter
Building Plan Review Approved with Conditions 04/23/2024 05/01/2024
Joe Frogge
Health Dept Review
Resolved
05/01/2024

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 797-7162. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is informational. 4/16/24 - acknowledged in letter
Health Dept Inspection
Corrective Action Required
04/16/2024

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7162. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 4/16/24 - acknowledged in letter
Fire Plan Review Approved with Conditions 04/23/2024 04/16/2024
Joe Frogge
Miscellaneous Correction
Corrective Action Required
04/16/2024

Extend the automatic fire sprinkler into the space. 4/16/24 - acknowledged in letter
Fire Plan Review Approved with Conditions 04/16/2024 04/15/2024
Jim Eden
Miscellaneous Correction
Corrective Action Required
04/15/2024

Extend the automatic fire sprinkler into the space.
Building Plan Review Rejected 04/16/2024 04/12/2024
Joe Frogge
Health Dept Review
Corrective Action Required
04/11/2024

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 797-7162. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is informational.
Health Dept Inspection
Corrective Action Required
04/11/2024

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7162. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational.
Licensed Contractors Rejected 04/16/2024 04/11/2024
Joe Frogge
LC - General Contractor
Corrective Action Required
04/11/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and the name, email address & phone number for the on-site contact which is where inspection reports will be sent.
LC - MEP Subs
Corrective Action Required
04/11/2024

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $50.00 $50.00 Paid 06/04/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Occupancy Inspection - Codes Commercial Failed 6/7/2024 6/7/2024 06/07/2024
Misc
Corrective Action Required
06/07/2024
-Fire approval required -Provide egress pathway from/to kiosk per code (stair, handrail, etc) -Secure MC within 12” of all boxes -Shall secure all wiring above ceiling per code -Plumbing not per plan. Provide 3” waste drain with waste receptor per plan -Flexible cable shall not installed as a substitute for the fixed wiring of a structure. Provide appropriate wiring method to kiosks -Wiring shall be sized per note 6 of electrical plan -Label all breakers of kitchen panel -All receptacles inside kitchen shall be gfci-protected per NEC 210.8(B)(2)
Occupancy Inspection - Fire Temporary C of O 6/7/2024 6/7/2024 06/07/2024
Occupancy Inspection - Fire Passed 7/22/2024 7/22/2024 07/22/2024
Occupancy Inspection - Codes Commercial Failed 7/22/2024 7/23/2024 07/23/2024
Misc
Corrective Action Required
06/07/2024
-Fire approval required -Provide egress pathway from/to kiosk per code (stair, handrail, etc) **See stair riser height requirement IBC 1011.5, landing requirement IBC 1011.6; handrail IBC 1014 -Plumbing not per plan. Provide 3” waste drain with waste receptor per plan **Plumbing not per plan. Also: improper fiitings used at hor-hor and vert-hor connections; pex line not supported every 32"; venting not compliant with code -Flexible cable shall not installed as a substitute for the fixed wiring of a structure. Provide appropriate wiring method to kiosks **Install insulating bushings at disconnect -All receptacles inside kitchen shall be gfci-protected per NEC 210.8(B)(2) -Fire caulk penetration of the fire-rated wall above Consultation B room
Occupancy Inspection - Codes Commercial Failed 8/29/2024 8/29/2024 08/29/2024
Misc
Corrective Action Required
07/23/2024
-Plumbing-install wye fitting for the hor-hor connection under sink; vent the first trap under CT. You can use air admittance valve to vent this trap
Occupancy Inspection - Codes Commercial Full C of O 9/3/2024 9/3/2024 09/03/2024
Misc
Resolved
09/03/2024
-Plumbing-install wye fitting for the hor-hor connection under sink; vent the first trap under CT. You can use air admittance valve to vent this trap
Documents & Images
Date Uploaded File Type Document Name
04/04/2024 Application Form APPLICATION
04/04/2024 Plans Coffee Kiosk CDs 04-03-2024
04/04/2024 Plans Coffee Kiosk Vendor Info 04-03-2024
04/15/2024 Letter DS P/R Corrections Document
04/16/2024 Letter City Review Response 4-16-24
04/16/2024 Approved Plans Approved constr. set - Coffee Kiosk CDs 04-03-2024
05/01/2024 Letter Health Department approval
06/04/2024 Receipt Receipt for transaction:2024-004300
06/04/2024 Letter DS Building Permit
06/07/2024 Letter INSPECTION SUMMARY
07/17/2024 Plans Coffee Kiosk MPE 07-16-24
07/17/2024 Approved Plans Approved revisions - Coffee Kiosk MPE 07-16-24
07/23/2024 Letter INSPECTION SUMMARY
08/05/2024 Approved Plans Approved revisions
08/29/2024 Letter INSPECTION SUMMARY
09/03/2024 Letter Field Certificate of Occupancy
09/03/2024 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home