Permit Application Status

PRCOM20234789


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20234789
Building Permit - Commercial
Final Completion
LANGSFORD DEV INC
ALTERATION COMMERCIAL
REPAIR EXISTING CATWALK AND REPLACE STAIR FLIGHT
09/20/2023
12/21/2023
03/20/2024
10/23/2024
Locations
Contacts
LANGSFORD DEV INC, Address:PO BOX 607  
Bradlech Construction, LLC, Address:25320 E US Highway, Phone:(816) 588-1341  
AMundy@bradlech.com  
Daniel Nixon Design, Address:11507 E 38th Street South, Phone:(816) 838-8152  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 12/20/2023 12/13/2023
Joe Frogge
Miscellaneous Correction
Resolved
12/13/2023

Specify stair, guard, and handrail geometries. (rise, run, heights, spacing, etc.) Replaced components must meet 2018 IBC regulations.
Misc
Corrective Action Required
12/13/2023

Approval contingent upon the following: - Provide handrail on each side of stair per 2018 IBC 1011.11 - 4" maximum spacing applies to entire assembly (including between treads) per 2018 IBC 1015.4. - Handrails to be terminated (not open ended) per 2018 IBC 1014.6.
Licensed Contractors Approved 12/13/2023 12/13/2023
Joe Frogge
Building Plan Review Rejected 10/02/2023 09/22/2023
Joe Frogge
Miscellaneous Correction
Corrective Action Required
09/22/2023

Specify stair, guard, and handrail geometries. (rise, run, heights, spacing, etc.) Replaced components must meet 2018 IBC regulations.
Licensed Contractors Approved 10/02/2023 09/22/2023
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $200.00 $200.00 Paid 12/15/2023
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Retaining Wall Inspection Failed 03/19/2024
Misc
Corrective Action Required
03/19/2024
-City approved, stamped plans required on site for inspections -Not completed per plan: -Use #4 bar spaced per plan -Epoxy #4 dowels to existing per plan
Suspended Slab Inspection Failed 3/21/2024 3/21/2024 03/19/2024
Misc
Corrective Action Required
03/19/2024
-City approved, stamped plans required on site for inspections -Not completed per plan -Use #4 bar spaced per plan and supported off of deck -Use min 1" galvanized formdeck by cordeck per plan, not light gauge corrugated roofing panels
Retaining Wall Inspection Passed 3/21/2024 3/21/2024 03/21/2024
Misc
Resolved
03/21/2024
-City approved, stamped plans required on site for inspections -Not completed per plan: -Use #4 bar spaced per plan -Epoxy #4 dowels to existing per plan
Suspended Slab Inspection Passed 03/21/2024
Misc
Resolved
03/21/2024
-City approved, stamped plans required on site for inspections -Not completed per plan -Use #4 bar spaced per plan and supported off of deck -Use min 1" galvanized formdeck by cordeck per plan, not light gauge corrugated roofing panels
Final Inspection - Commercial Failed 3/26/2024 3/26/2024 03/26/2024
Misc
Corrective Action Required
03/26/2024
-Provide code compliant handrail at both sides of upper stairs -All stairs to be max 7" in rise and not vary more than 3/8" -Openings at risers to be no more than 4" -Return all handrails per code -Existing handrail at top stairs is required to be 34"-38" aff, extend 12" and return per code
Final Inspection - Commercial Failed 8/14/2024 8/14/2024 08/14/2024
Misc
Corrective Action Required
03/26/2024
-Provide code compliant handrail at both sides of upper stairs-(This is required per denied CMR dated 9/05/23) -All stairs to be max 7" in rise and not vary more than 3/8"-(Bottom riser is 7.75", average remaining risers are 6.75") -Existing handrail at top stairs is required to be 34"-38" aff, extend 12" and return per code-(Required per denied CMR dated 9/05/23)
Final Inspection - Commercial Failed 10/3/2024 10/3/2024 10/03/2024
Misc
Corrective Action Required
08/14/2024
Provide code compliant handrail at both sides of upper stairs-(This is required per denied CMR dated 9/05/23) -Existing handrail at top stairs is required to be 34"-38" aff, extend 12" and return per code-(Required per denied CMR dated 9/05/23)
Final Inspection - Commercial Passed 10/24/2024 10/24/2024 10/23/2024
Misc
Corrective Action Required
10/03/2024
Mark Harding and I visted the site. Because this was an existing stair that was parially modified Mark and I agreed on what needed to be corrected to make the stiar/handrail as code compliant as practically possible. I then met the contractor on site and gave direction. Inspection was performed on 10-23-2024 and pictures are attached. This permit will be closed at this time. TRACY DEISTER 10/23/2024 11:22 AM
Documents & Images
Date Uploaded File Type Document Name
09/20/2023 Application Form SKM_58823092016030
09/20/2023 Engineer Report/Study SE_519_Southwest_3rd_Street__Lee's_Summit__MO_64063_(1)
09/20/2023 Plans 230901_PERMIT_SET
09/22/2023 Letter DS P/R Corrections Document
09/26/2023 Code Mod Request 3rd St. Code Modification Request (denied)
12/01/2023 Plans 231129_PERMIT_SET_REV_1
12/13/2023 Approved Plans approved catwalk plans
12/15/2023 Receipt Receipt for transaction:2023-009121
12/21/2023 Letter DS Building Permit
03/19/2024 Letter INSPECTION SUMMARY
03/19/2024 Letter INSPECTION SUMMARY
03/21/2024 Letter INSPECTION SUMMARY
03/21/2024 Letter INSPECTION SUMMARY
03/21/2024 Letter INSPECTION SUMMARY
03/26/2024 Letter INSPECTION SUMMARY
08/13/2024 Letter Codes 140 Day Letter
08/14/2024 Letter INSPECTION SUMMARY
10/03/2024 Letter INSPECTION SUMMARY
10/23/2024 Photograph 3rd St Stair 1
10/23/2024 Photograph 3rd St Stair 2
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home