Permit Application Status

PRCOM20233057


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20233057
Building Permit - Commercial
Certificate of Occupancy
230 MAIN INVESTORS LLC
CHANGE OF TENANT
Tenant finish for pizzeria subleased inside drinking establishment
06/26/2023
08/21/2023
10/19/2023
Locations
Contacts
230 MAIN INVESTORS LLC, Address:7200 W 132ND ST STE 150  
JWM CONTRACTING LLC, Address:420 NE BROCKTON DR, Phone:(913) 530-4205  
AIR CARE HEATING & COOLING, Address:10332 W 79TH ST, Phone:(913) 362-5274  
TEAGUE ELECTRIC CONSTRUCTION INC, Address:12425 W 92ND ST, Phone:(913) 529-4600  
PRODIGY PLUMBING & MECHANICAL INC, Address:8402 WESTRIDGE RD, Phone:(816) 984-9292  
Jeff Munden, Address:jeff@jwmcontracting@gmail.com, Phone:(913) 530-4205  
COLLINS WEBB ARCHITECTURE LLC, Address:307 SW MARKET ST, Unit B, Phone:(816) 249-2270  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 08/02/2023 08/08/2023
Joe Frogge
Miscellaneous Correction
Corrective Action Required
07/26/2023

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is for informational purposes. After credit for previous occupant the fee will be $5,651.25 8/1/23 - acknowledged in letter
Health Dept Review
Resolved
08/08/2023

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is informational. 8/1/23 - acknowledged in letter
Health Dept Inspection
Corrective Action Required
07/26/2023

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 8/1/23 - acknowledged in letter
ICC A117.1 904.3 Sales and Service Counters
Resolved
08/01/2023

ICC A117.1 Section 904.3 Sales and service counters and windows. Sales and service counters and windows shall comply with Section 904.3.1 and either 904.3.2 or 904.3.3. Where counters are provided, the accessible portion of the countertop shall extend the same depth as the public portion of the sales and service countertop provided for standing customers. (see code for exception) 904.3.1 Vertical barriers. At service windows or service counters, any vertical barrier between service personnel and customers shall be at a height of 43 inches maximum above the floor. (see code for exception regarding security glazing) 904.3.2 Parallel Approach. A portion of the public use side of the counter surface 36 inches minimum in length and 26 inches minimum and 36 inches maximum in height above the floor shall be provided. A clear floor space positioned for a parallel approach adjacent to the accessible counter shall be provided. The space between the accessible counter surface and any projecting objects above the accessible counter shall be 12 inches minimum. (see code for exception) 904.3.3 Forward Approach. A portion of the public use side of the counter surface 30 inches minimum in length and 36 inches maximum in height above the floor shall be provided. A clear floor space positioned for a forward approach to the accessible counter shall be provided. Knee and toe clearance complying with Section 306 shall be provided under the accessible counter. The space between the accessible counter surface and any projecting objects above the accessible counter shall be 12” minimum. Action required: Provide at least 36 linear inches of accessible service counter. (30" shown at front of front counter - unable to find height of pass thru counter) 8/1/23 - per architect this is a work surface for employees and not intended for transactions which are directed to ADA counter to the south
IMC 506.4.2 Type II exhaust terminations
Resolved
08/01/2023

2018 IMC 506.4.2 Type II terminations. Exhaust outlets serving Type II hoods shall terminate in accordance with the hood manufacturer's installation instructions and shall comply with all of the following: 1. Exhaust outlets shall terminate not less than 3 feet (914 mm) in any direction from openings into the building. 2. Outlets shall terminate not less than 10 feet (3048 mm) from property lines or buildings on the same lot. 3. Outlets shall terminate not less than 10 feet (3048 mm) above grade. 4. Outlets that terminate above a roof shall terminate not less than 30 inches (762 mm) above the roof surface. 5. Outlets shall terminate not less than 30 inches (762 mm) from exterior vertical walls 6. Outlets shall be protected against local weather conditions. 7. Outlets shall not be directed onto walkways. 8. Outlets shall meet the provisions for exterior wall opening protectives in accordance with the International Building Code. Action required: Relocate fan to comply.
Health Department Review Approved 08/08/2023
Joe Frogge
Licensed Contractors Approved 08/02/2023 08/01/2023
Joe Frogge
Fire Plan Review Approved with Conditions 08/02/2023 07/31/2023
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
07/26/2023

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for alarm system modifications.
Construction documents - Fire protection systems
Corrective Action Required
07/26/2023

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for sprinkler system modifications.
Portable fire extinguishers - general
Resolved
07/31/2023

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum 2A,10B,C fire extinguisher in the space. Verified at inspection.
Fire Plan Review Approved with Conditions 07/07/2023 07/25/2023
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
07/06/2023

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for alarm system modifications, including relaty for the Type 1 hood system.
Type I hood - Where required
Resolved
07/25/2023

2018 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Provide a Type 1 hood system. 7/25/2023- Based on oven design and menu, a Type 1 hood is no longer required. Continue with the Type 2 hood.
Construction documents - Fire protection systems
Corrective Action Required
07/06/2023

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for sprinkler system modifications.
Portable fire extinguishers for commercial cooking equipment.
Resolved
07/25/2023

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Provide a K-class extinguisher at the manual pull for the hood system. 7/25/2023- No longer required, Type 2 hood only.
Portable fire extinguishers - general
Corrective Action Required
07/06/2023

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum 2A,10B,C fire extinguisher in the space. Verified at inspection.
Building Plan Review Rejected 07/07/2023 06/30/2023
Joe Frogge
Miscellaneous Correction
Corrective Action Required
06/29/2023

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is for informational purposes. After credit for previous ??? occupant the fee will be $5,651.25
Health Dept Review
Corrective Action Required
06/29/2023

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is informational.
Health Dept Inspection
Corrective Action Required
06/29/2023

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational.
ICC A117.1 904.3 Sales and Service Counters
Corrective Action Required
06/30/2023

ICC A117.1 Section 904.3 Sales and service counters and windows. Sales and service counters and windows shall comply with Section 904.3.1 and either 904.3.2 or 904.3.3. Where counters are provided, the accessible portion of the countertop shall extend the same depth as the public portion of the sales and service countertop provided for standing customers. (see code for exception) 904.3.1 Vertical barriers. At service windows or service counters, any vertical barrier between service personnel and customers shall be at a height of 43 inches maximum above the floor. (see code for exception regarding security glazing) 904.3.2 Parallel Approach. A portion of the public use side of the counter surface 36 inches minimum in length and 26 inches minimum and 36 inches maximum in height above the floor shall be provided. A clear floor space positioned for a parallel approach adjacent to the accessible counter shall be provided. The space between the accessible counter surface and any projecting objects above the accessible counter shall be 12 inches minimum. (see code for exception) 904.3.3 Forward Approach. A portion of the public use side of the counter surface 30 inches minimum in length and 36 inches maximum in height above the floor shall be provided. A clear floor space positioned for a forward approach to the accessible counter shall be provided. Knee and toe clearance complying with Section 306 shall be provided under the accessible counter. The space between the accessible counter surface and any projecting objects above the accessible counter shall be 12” minimum. Action required: Provide at least 36 linear inches of accessible service counter. (30" shown at front of front counter - unable to find height of pass thru counter)
IMC 506.4.2 Type II exhaust terminations
Corrective Action Required
06/30/2023

2018 IMC 506.4.2 Type II terminations. Exhaust outlets serving Type II hoods shall terminate in accordance with the hood manufacturer's installation instructions and shall comply with all of the following: 1. Exhaust outlets shall terminate not less than 3 feet (914 mm) in any direction from openings into the building. 2. Outlets shall terminate not less than 10 feet (3048 mm) from property lines or buildings on the same lot. 3. Outlets shall terminate not less than 10 feet (3048 mm) above grade. 4. Outlets that terminate above a roof shall terminate not less than 30 inches (762 mm) above the roof surface. 5. Outlets shall terminate not less than 30 inches (762 mm) from exterior vertical walls 6. Outlets shall be protected against local weather conditions. 7. Outlets shall not be directed onto walkways. 8. Outlets shall meet the provisions for exterior wall opening protectives in accordance with the International Building Code. Action required: Relocate fan to comply.
Licensed Contractors Approved 07/07/2023 06/27/2023
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
7232302-Commercial License Tax Fee $7,458.00 $7,458.00 Paid 09/20/2023
$1,806.75
9110078-Valuation Fee for Change of Tenant $120.00 $120.00 Paid 08/09/2023
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 09/22/2023
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Electrical Inspection - Commercial Passed 9/5/2023 9/5/2023 09/05/2023
Alarm Test Passed 09/05/2023
Underslab Plumbing Inspection - Commercial Passed 9/5/2023 9/5/2023 09/05/2023
In-wall Inspection Partial 9/13/2023 9/13/2023 09/13/2023
Misc
Informational
09/13/2023
-Knee walls approved
In-wall Inspection Passed 9/19/2023 9/19/2023 09/19/2023
Misc
Resolved
09/19/2023
Knee walls approved
Above Ceiling Inspection Passed 09/22/2023
Occupancy Inspection - Fire Passed 9/21/2023 9/21/2023 09/22/2023
Occupancy Inspection - Codes Commercial Ready for Temp CO 9/22/2023 9/22/2023 09/22/2023
Misc
Corrective Action Required
09/22/2023
-Paint exterior metallic gas line with corrosion resistant paint -Provide label for gas meter
Occupancy Inspection - Codes Commercial Full C of O 10/19/2023 10/19/2023 10/19/2023
Misc
Resolved
10/19/2023
-Paint exterior metallic gas line with corrosion resistant paint -Provide label for gas meter
Documents & Images
Date Uploaded File Type Document Name
06/26/2023 Application Form Johnny Jo's_Commercial Permit Application
06/27/2023 Plans 23063_Johnny Jo's Pizzeria_Permit Set_230627
07/07/2023 Letter DS P/R Corrections Document
07/25/2023 Email menu
07/26/2023 Plans 23063_Johnny Jo's Pizzeria_Revision 1_230725
07/26/2023 Letter 23063_Johnny Jo's_City Response Narrative
08/01/2023 Approved Plans approved - 23063_Johnny Jo's Pizzeria_Revision 1_230725
08/08/2023 Letter Jackson County Health approval
08/09/2023 Receipt Receipt for transaction:2023-006175
08/21/2023 Letter (old address) DS Building Permit
09/05/2023 Letter INSPECTION SUMMARY
09/05/2023 Letter INSPECTION SUMMARY
09/13/2023 Letter INSPECTION SUMMARY
09/13/2023 Letter INSPECTION SUMMARY
09/19/2023 Letter INSPECTION SUMMARY
09/20/2023 Letter DS Building Permit
09/20/2023 Receipt Receipt for transaction: 2023-007197
09/20/2023 Letter License Tax Bill
09/22/2023 Jackson County Health Department
09/22/2023 Letter INSPECTION SUMMARY
09/22/2023 Certificate/License Codes Temporary Certificate of Occupancy
09/22/2023 Receipt Receipt for transaction:2023-007261
10/19/2023 Letter Codes Final Certificate of Occupancy
10/19/2023 Letter Field Certificate of Occupancy
10/19/2023 Letter Fire Building Plan Review
10/19/2023 Letter Fire Building Plan Review
10/19/2023 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home