Permit Application Status

PRCOM20221597


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20221597
Building Permit - Commercial
Certificate of Occupancy
SOUTHPORT BUSINESS CENTER LLC
CHANGE OF TENANT
TENANT FINISH FOR LIQUOR STORE
04/20/2022
06/29/2022
10/30/2022
10/27/2022
Locations
Contacts
Triple Oaks Investments LLC, Address:210 Northwest O St   
tim@tripleoaksinvestments.com  
QUALITY PLUMBING INC, Address:1731 HOWELL ST, Phone:(816) 472-4994  
Harry's Electric Services , Address:16213 Nutmeg Rd  
FIVE STAR MECHANICAL CONTRACT INC, Address:P O BOX 11964, Phone:(816) 358-4444  
DA GROUP INC, Address:5400 JOHNSON DR #149, Phone:(913) 789-8665  
SOUTHPORT BUSINESS CENTER LLC, Address:1485 SW MARKET ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 09/30/2022 09/30/2022
Ben Hicks
Installation acceptance testing
Informational
09/23/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required- Call (816) 969-1300 to schedule testing.
Construction documents for fire alarm systems
Resolved
09/30/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Construction documents - Fire protection systems
Resolved
09/30/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required- Provide shop drawings for review and approval. Confirm the hazard clssification is upgraded for the commodity.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Resolved
09/30/2022

2018 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Acttion required- The existing sprinkler and alarm system shall have a documentation current annual inspection. Verified at inspection.
Zoning Review Approved 09/30/2022 09/26/2022
Hector Soto Jr.
Building Plan Review Approved with Conditions 09/30/2022 09/26/2022
Joe Frogge
Health Dept Inspection
Corrective Action Required
09/23/2022

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
IPC 918.1 Air admittance valve
Corrective Action Required
09/23/2022

2018 IPC 918.1 General. (as amended by LSCO 7-412) Section 918.1 is hereby amended to read as follows: Air admittance valve are only allowed when approved by the Administrative Authority. Vent systems utilizing air admittance valves shall comply with this section. Stack-type air admittance valves shall conform to ASSE 1050. Individual- and branch-type air admittance valves shall conform to ASSE 1051. Action required: In order to utilize air admittance valves you must demonstrate that no other method is viable/practical. In this case IPC 916 Island (loop) fixture vending should work. 5/12/22 - loop vent detailed but cleanouts not shown. Cleanouts to be installed per IPC 916.3 - to be field verified.
Alarm Plan Review Released for Construction 08/04/2022
Jim Eden
Installation acceptance testing
Corrective Action Required
08/04/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule an alarm test.
Construction documents for fire alarm systems
Corrective Action Required
08/04/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Revised plans received July 26, 2022.
Sprinkler Plan Review Released for Construction 07/27/2022
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
07/27/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received 7/19/2022. Revised calulations received 7/26/2022.
Installation acceptance testing
Corrective Action Required
07/27/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule testing.
Licensed Contractors Approved 05/17/2022 06/29/2022
Development Center
LC - MEP Subs
Corrective Action Required
05/10/2022

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 5/12/22 - acknowledged in letter
LC - General Contractor
Corrective Action Required
05/10/2022

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent. 5/12/22 - acknowledged in letter
Fire Plan Review Approved with Conditions 05/17/2022 05/12/2022
Jim Eden
Installation acceptance testing
Informational
05/12/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required- Call (816) 969-1300 to schedule testing.
Construction documents for fire alarm systems
Corrective Action Required
05/10/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Address numbers required
Resolved
05/12/2022

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). The tenant space shall be identified on all doors. Verified at inspection.
Panic and fire exit hardware
Resolved
05/12/2022

2018 IFC 1010.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is a panic hardware or fire exit hardware. Action required- Confirm the panic hardware will remain on the south and west egress doors.
Construction documents - Fire protection systems
Corrective Action Required
05/10/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required- Provide shop drawings for review and approval. Confirm the hazard clssification is upgraded for the commodity.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Informational
05/12/2022

2018 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Acttion required- The existing sprinkler and alarm system shall have a documentation current annual inspection. Verified at inspection.
Egress through intervening spaces.
Resolved
05/12/2022

5. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes. Exceptions: 1. Means of egress are not prohibited through a kitchen area serving adjoining rooms constituting part of the same dwelling unit or sleeping unit. 2. Means of egress are not prohibited through stockrooms in Group M occupancies where all of the following are met: 2.1. The stock is of the same hazard classification as that found in the main retail area. 2.2. Not more than 50 percent of the exit access is through the stockroom. 2.3. The stockroom is not subject to locking from the egress side. 2.4. There is a demarcated, minimum 44- inch-wide (1118 mm) aisle defined by full- or partial-height fixed walls or similar construction that will maintain the required width and lead directly from the retail area to the exit without obstructions. Action required- Provide a maintain a 44-inch wide demarcated path through the product receiving area.
Building Plan Review Approved with Conditions 05/17/2022 05/12/2022
Joe Frogge
IBC 602.1 Type of Construction - general
Resolved
05/12/2022

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Modify Code Info on sheet Code 100 to reflect actual construction type which is 2b.
Health Dept Review
Resolved
05/12/2022

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
05/10/2022

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
IPC 918.1 Air admittance valve
Corrective Action Required
05/10/2022

2018 IPC 918.1 General. (as amended by LSCO 7-412) Section 918.1 is hereby amended to read as follows: Air admittance valve are only allowed when approved by the Administrative Authority. Vent systems utilizing air admittance valves shall comply with this section. Stack-type air admittance valves shall conform to ASSE 1050. Individual- and branch-type air admittance valves shall conform to ASSE 1051. Action required: In order to utilize air admittance valves you must demonstrate that no other method is viable/practical. In this case IPC 916 Island (loop) fixture vending should work. 5/12/22 - loop vent detailed but cleanouts not shown. Cleanouts to be installed per IPC 916.3 - to be field verified.
Health Department Review Approved 05/12/2022
Joe Frogge
Fire Plan Review Rejected 05/02/2022 05/02/2022
Jim Eden
Installation acceptance testing
Corrective Action Required
05/02/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required- Call (816) 969-1300 to schedule testing.
Construction documents for fire alarm systems
Corrective Action Required
05/02/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Address numbers required
Corrective Action Required
05/02/2022

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). The tenant space shall be identified on all doors. Verified at inspection.
Panic and fire exit hardware
Corrective Action Required
05/02/2022

2018 IFC 1010.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is a panic hardware or fire exit hardware. Action required- Confirm the panic hardware will remain on the south and west egress doors.
Construction documents - Fire protection systems
Corrective Action Required
05/02/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required- Provide shop drawings for review and approval. Confirm the hazard clssification is upgraded for the commodity.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
05/02/2022

2018 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Acttion required- The existing sprinkler and alarm system shall have a documentation current annual inspection. Verified at inspection.
Egress through intervening spaces.
Corrective Action Required
05/02/2022

5. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes. Exceptions: 1. Means of egress are not prohibited through a kitchen area serving adjoining rooms constituting part of the same dwelling unit or sleeping unit. 2. Means of egress are not prohibited through stockrooms in Group M occupancies where all of the following are met: 2.1. The stock is of the same hazard classification as that found in the main retail area. 2.2. Not more than 50 percent of the exit access is through the stockroom. 2.3. The stockroom is not subject to locking from the egress side. 2.4. There is a demarcated, minimum 44- inch-wide (1118 mm) aisle defined by full- or partial-height fixed walls or similar construction that will maintain the required width and lead directly from the retail area to the exit without obstructions. Action required- Provide a maintain a 44-inch wide demarcated path through the product receiving area.
Building Plan Review Rejected 05/02/2022 04/29/2022
Joe Frogge
IBC 602.1 Type of Construction - general
Corrective Action Required
04/29/2022

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Modify Code Info on sheet Code 100 to reflect actual construction type which is 2b.
Health Dept Review
Corrective Action Required
04/29/2022

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
04/29/2022

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
IPC 918.1 Air admittance valve
Corrective Action Required
04/29/2022

2018 IPC 918.1 General. (as amended by LSCO 7-412) Section 918.1 is hereby amended to read as follows: Air admittance valve are only allowed when approved by the Administrative Authority. Vent systems utilizing air admittance valves shall comply with this section. Stack-type air admittance valves shall conform to ASSE 1050. Individual- and branch-type air admittance valves shall conform to ASSE 1051. Action required: In order to utilize air admittance valves you must demonstrate that no other method is viable/practical. In this case IPC 916 Island (loop) fixture vending should work.
Licensed Contractors Rejected 05/02/2022 04/28/2022
Joe Frogge
LC - MEP Subs
Corrective Action Required
04/28/2022

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
LC - General Contractor
Corrective Action Required
04/28/2022

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $4,800.00 $4,800.00 Paid 05/17/2022
8331507-Sewer Connection Fee $90.00 $90.00 Paid 05/17/2022
7232302-Commercial License Tax Fee $68,160.00 $68,160.00 Paid 06/29/2022
$4,080.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 7/6/2022 7/6/2022 07/06/2022
In-wall Inspection Passed 7/19/2022 07/19/2022
Above Ceiling Inspection Partial 8/16/2022 8/16/2022 08/16/2022
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
08/16/2022
-HARD LIDS AT CENTER OCTAGON AND COOLER
Above Ceiling Inspection Partial 9/2/2022 9/2/2022 09/02/2022
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
08/16/2022
-HARD LIDS AT CENTER OCTAGON AND COOLER - DROP AROUND OCTAGON AT BACK HALF
Sprinkler - Hydrostatic Test Passed 9/26/2022 09/27/2022
Sprinkler - Hydrostatic Test Passed 9/26/2022 09/27/2022
Alarm Test Passed 9/27/2022 09/27/2022
Sprinkler - Flow Test Passed 9/27/2022 09/27/2022
Rated Assembly Inspection Passed 09/28/2022
Occupancy Inspection - Codes Commercial Failed 9/28/2022 9/28/2022 09/28/2022
Misc
Corrective Action Required
09/28/2022
-Complete all items for other departments -Complete exterior and parking lot lighting -Complete exteroir canopies -Complete electrical for exterior lighting -Provide address at back door -Provide accessible restroom signage -Provide vertical grab bar, mirror in restrooms -Side wall grab bar to be 12" max spacing and 54" min rfom back wall -Secure mc in riser room -Cover plates in stock room -Provide accessible counter at checkout **OK TO STOCK ONLY
Above Ceiling Inspection Passed 09/28/2022
THE FOLLOWING AREAS ARE APPROVED
Resolved
09/28/2022
-HARD LIDS AT CENTER OCTAGON AND COOLER - DROP AROUND OCTAGON AT BACK HALF
Occupancy Inspection - Fire Failed 9/28/2022 9/28/2022 09/28/2022
Corrective Action Required
09/28/2022
Hydraulic specs need to be on sprinkler system.  Label sprinkler room door. Address back doors South and east exterior emergency illumination not installed Ok to stock with approval from cods.
Occupancy Inspection - Codes Commercial Failed 10/11/2022 10/11/2022 10/11/2022
Misc
Corrective Action Required
09/28/2022
-Complete exteroir canopies -Label panels and provide panel schedules -Secure mc in riser room -Provide accessible counter at checkout **OK TO STOCK ONLY
Occupancy Inspection - Fire Failed 10/11/2022 10/11/2022 10/11/2022
Above Ceiling Inspection Failed 10/19/2022 10/19/2022 10/19/2022
Miscellaneous Correction
Corrective Action Required
10/19/2022
-Submit engineered approval for field revisions on front canopy framing and post/ beam connections **above ceiling ok to cover pending engineered letter
Above Ceiling Inspection Passed 10/26/2022
Miscellaneous Correction
Resolved
10/26/2022
-Submit engineered approval for field revisions on front canopy framing and post/ beam connections **above ceiling ok to cover pending engineered letter
Occupancy Inspection - Fire Passed 10/27/2022 10/27/2022 10/27/2022
Occupancy Inspection - Codes Commercial Full C of O 10/27/2022 10/27/2022 10/27/2022
Misc
Resolved
10/27/2022
Documents & Images
Date Uploaded File Type Document Name
04/20/2022 Application Form Commercial Permit Application-04202022
04/22/2022 Plans DA0835-Macadoodles T_I_-Permit Set Binder-04182022-compressed
04/28/2022 Email Jxn cty - applicability
05/03/2022 Letter DS P/R Corrections Document
05/10/2022 Drawing 22035G_P200-r1
05/10/2022 Drawing CODE100-PS-2436-r1-05102022
05/10/2022 Letter DS P_R Corrections Document-05032022-response-05102022
05/12/2022 Email jxn ct approval - Macadoodles
05/13/2022 Approved Plans approved-Macadoodles T_I_-Permit Set Binder-04182022-compressed
05/17/2022 Receipt Receipt for transaction: 2022-003588
06/01/2022 Letter Fire Building Plan Review
06/29/2022 Receipt Receipt for transaction: 2022-005320
06/29/2022 Letter DS Building Permit
07/06/2022 Letter INSPECTION SUMMARY
07/19/2022 Letter INSPECTION SUMMARY
07/27/2022 Letter Fire (Sprinkler) Plan Review
08/04/2022 Macadoodles Battery Calcs and Voltage Drops
08/04/2022 Stamped Macadoodles Fire Alarm Plan R-2
08/04/2022 Letter Fire (Alarm) Plan Review Notice
08/16/2022 Letter INSPECTION SUMMARY
09/02/2022 Letter INSPECTION SUMMARY
09/23/2022 Plans DA0835-Macadoodles T_I_-Permit Set Binder-09232022-Exterior Canopy
09/27/2022 Letter Fire Loss Reduction Form
09/28/2022 Letter INSPECTION SUMMARY
09/28/2022 Letter INSPECTION SUMMARY
09/28/2022 Letter INSPECTION SUMMARY
10/03/2022 Approved Plans approved - DA0835-Macadoodles T_I_-Permit Set Binder-09232022-Exterior Canopy
10/11/2022 Letter INSPECTION SUMMARY
10/11/2022 Letter Fire Loss Reduction Form
10/11/2022 Letter Fire Loss Reduction Form
10/19/2022 Letter INSPECTION SUMMARY
10/19/2022 Letter RFI 01 - Macadoodles LS - BDC RESPONSE-10192022
10/24/2022 Drawing S001-REVISION 1
10/25/2022 Approved Plans approved - S001-REVISION 1
10/26/2022 Letter INSPECTION SUMMARY
10/27/2022 Letter Field Certificate of Occupancy
10/27/2022 Letter Codes Final Certificate of Occupancy
03/16/2023 Letter Fire Loss Reduction Form
Upload Documents
  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:
Browse..





    Portal Home