Permit Application Status

PRCOM20210833


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20210833
Building Permit - Commercial
Certificate of Occupancy
CITY OF LEES SUMMIT
NEW TENANT FINISH
TENANT FINISH FOR MASSAGE AND SPA
02/26/2021
04/19/2021
08/30/2021
10/15/2021
Locations
Contacts
BEAR CONSTRUCTION SERVICES, Address:9218 METCALF #311, Phone:(913) 674-8004  
PRECISE ELECTRIC LLC, Address:3205 STEEL CIR, Phone:(816) 529-1799  
HEARTLAND PLUMBING INC, Address:800 S CREEKSIDE DR, Phone:(913) 856-5846  
brad@bradley-collins.com, Address:brad@bradley-collins.com  
CITY OF LEES SUMMIT, Address:220 SE GREEN ST  
Bradley Peterson, Address:131 East Drake Avenue  
ATLAS MECHANICAL SERVICES INC, Address:26015 RA HWY, Phone:(913) 708-4695  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 08/25/2021 08/25/2021
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
08/25/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Sprinkler Plan Review Released for Construction 08/09/2021 08/09/2021
Michael Weissenbach
Licensed Contractors Approved 03/29/2021 04/09/2021
Joe Frogge
LC - General Contractor
Resolved
03/22/2021

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact.
LC - MEP Subs
Resolved
04/09/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 3/22/21 - not addressed
Building Plan Review Approved with Conditions 03/29/2021 04/08/2021
Joe Frogge
Miscellaneous Correction
Resolved
04/08/2021

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 3/22/21 - not addressed
Suite address
Corrective Action Required
03/22/2021

This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required: This suite has been assigned as suite "H" making the complete address 940 NW Pryor Rd, Unit:H. Please update your records.
IBC 1004.5.1 Increase occupant load
Resolved
03/22/2021

2018 IBC 1004.5.1 Increased occupant load. The occupant load permitted in any building, or portion thereof, is permitted to be increased from that number established for the occupancies in Table 1004.5, provided that all other requirements of the code are also met based on such modified number and the occupant load does not exceed one occupant per 7 square feet of occupiable floor space. Where required by the building official, an approved aisle, seating or fixed equipment diagram substantiating any increase in occupant load shall be submitted. Where required by the building official, such diagram shall be posted. Action required: Update occupant load in code analysis to more accurately depict nature of salon. Assign 2 occupants per treatment room in addition to office and reception.
IBC 1008.3 Emergency power for illumination - at exit discharge
Resolved
03/22/2021

2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting at exterior side of exit doors or provide verification that emergency lighting is existing.
IBC 1606.2 Design dead load - structural
Resolved
03/22/2021

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide verification by design professional that ceiling structure will support weight of new furnaces.
Misc
Resolved
03/22/2021

Lee's Summit Code of Ordinance, Section 28-63. – Massage facility business license required. (See ordinance for A thru C/2) C/3. No massage facility business license shall be approved by the Director of Finance unless the facility complies with each of these minimum requirements: a. The walls shall be clean and painted with washable, mold-resistant paint in all rooms where massage is provided. Floors shall be free from any accumulation of dust, dirt or refuse. All equipment used in the business operation shall be maintained in a clean and sanitary condition. Towels, linens and items for personal use of massage therapists, employees and patrons shall be in sufficient quantity so that none is used for more than one (1) person. Heavy, white paper may be substituted for sheets if such paper is changed for each patron. No cubicle, room, booth or any area within the facility where service is to be provided patrons shall be fitted with a door capable of being locked. b. Toilet facilities shall be provided in convenient locations. When the facility is designed to accommodate any combination of five (5) or more massage therapists, employees and patrons of different sexes on the premises at the same time, separate toilet facilities shall be provided. A single water closet per sex shall be provided for any combination of twenty (20) or more massage therapists, employees or patrons that the establishment is designed to accommodate on the premises at any one time. Urinals may be substituted for water closets after one (1) water closet has been provided. Toilets shall be designated as to the sex accommodated therein. c. Lavatories or wash basins provided with both hot and cold running water shall be installed in either the toilet room or vestibule. Lavatories or wash basins shall be provided with soap in a dispenser and with sanitary towels. (See ordinance for A thru E) Lee's Summit Code of Ordinance, Section 28-65. – Operating Regulations. Operation of a massage facility shall be subject to the following regulations: (See ordinance for A thru E) F. Sanitation of massage therapists and employees. All massage therapists shall be clean and wear clean clothes. Provisions or a separate massage therapist/employee dressing room for each sex must be available on the premises and individual lockers for each massage therapist and employee. Door to such dressing rooms shall open inward. (See ordinance for G thru J) Address the following: - Mold resistant paint required in massage rooms. - Lockable doors not allowed in service rooms. - Dressing rooms are required and the doors must open inward. - Lockers are required. (A Codes Modification Request can be made to appeal these ordinances. No fee involved)
Fire Plan Review Approved with Conditions 03/29/2021 03/22/2021
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
03/22/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Construction documents - Fire protection systems
Corrective Action Required
03/22/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
03/22/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Building Plan Review Rejected 03/10/2021 03/03/2021
Joe Frogge
Miscellaneous Correction
Corrective Action Required
03/03/2021

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Suite address
Corrective Action Required
03/03/2021

This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located. Action required: This suite has been assigned as suite "H" making the complete address 940 NW Pryor Rd, Unit:H. Please update your records.
IBC 1004.5.1 Increase occupant load
Corrective Action Required
03/03/2021

2018 IBC 1004.5.1 Increased occupant load. The occupant load permitted in any building, or portion thereof, is permitted to be increased from that number established for the occupancies in Table 1004.5, provided that all other requirements of the code are also met based on such modified number and the occupant load does not exceed one occupant per 7 square feet of occupiable floor space. Where required by the building official, an approved aisle, seating or fixed equipment diagram substantiating any increase in occupant load shall be submitted. Where required by the building official, such diagram shall be posted. Action required: Update occupant load in code analysis to more accurately depict nature of salon. Assign 2 occupants per treatment room in addition to office and reception.
IBC 1008.3 Emergency power for illumination - at exit discharge
Corrective Action Required
03/03/2021

2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting at exterior side of exit doors or provide verification that emergency lighting is existing.
IBC 1606.2 Design dead load - structural
Corrective Action Required
03/03/2021

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide verification by design professional that ceiling structure will support weight of new furnaces.
Misc
Corrective Action Required
03/03/2021

Lee's Summit Code of Ordinance, Section 28-63. – Massage facility business license required. (See ordinance for A thru C/2) C/3. No massage facility business license shall be approved by the Director of Finance unless the facility complies with each of these minimum requirements: a. The walls shall be clean and painted with washable, mold-resistant paint in all rooms where massage is provided. Floors shall be free from any accumulation of dust, dirt or refuse. All equipment used in the business operation shall be maintained in a clean and sanitary condition. Towels, linens and items for personal use of massage therapists, employees and patrons shall be in sufficient quantity so that none is used for more than one (1) person. Heavy, white paper may be substituted for sheets if such paper is changed for each patron. No cubicle, room, booth or any area within the facility where service is to be provided patrons shall be fitted with a door capable of being locked. b. Toilet facilities shall be provided in convenient locations. When the facility is designed to accommodate any combination of five (5) or more massage therapists, employees and patrons of different sexes on the premises at the same time, separate toilet facilities shall be provided. A single water closet per sex shall be provided for any combination of twenty (20) or more massage therapists, employees or patrons that the establishment is designed to accommodate on the premises at any one time. Urinals may be substituted for water closets after one (1) water closet has been provided. Toilets shall be designated as to the sex accommodated therein. c. Lavatories or wash basins provided with both hot and cold running water shall be installed in either the toilet room or vestibule. Lavatories or wash basins shall be provided with soap in a dispenser and with sanitary towels. (See ordinance for A thru E) Lee's Summit Code of Ordinance, Section 28-65. – Operating Regulations. Operation of a massage facility shall be subject to the following regulations: (See ordinance for A thru E) F. Sanitation of massage therapists and employees. All massage therapists shall be clean and wear clean clothes. Provisions or a separate massage therapist/employee dressing room for each sex must be available on the premises and individual lockers for each massage therapist and employee. Door to such dressing rooms shall open inward. (See ordinance for G thru J) Address the following: - Mold resistant paint required in massage rooms. - Lockable doors not allowed in service rooms. - Dressing rooms are required and the doors must open inward. - Lockers are required. (A Codes Modification Request can be made to appeal these ordinances. No fee involved)
Licensed Contractors Rejected 03/10/2021 03/03/2021
Joe Frogge
LC - General Contractor
Corrective Action Required
03/03/2021

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the name of the licensed general contractor and an email address for the on-site contact.
LC - MEP Subs
Corrective Action Required
03/03/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 03/10/2021 03/02/2021
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
03/02/2021

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Any modifications to the fire alarm system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Construction documents - Fire protection systems
Corrective Action Required
03/02/2021

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Any modifications to the fire sprinkler system, provide PE stamped electronic shop drawings to mike.weissenbach@cityofls.net
Installation acceptance testing
Corrective Action Required
03/02/2021

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $1,016.00 $1,016.00 Paid 04/19/2021
7232302-Commercial License Tax Fee $5,070.00 $5,070.00 Paid 04/19/2021
8331507-Sewer Connection Fee $270.00 $270.00 Paid 04/19/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Miscellaneous Inspection Passed 6/18/2021 6/18/2021 06/18/2021
Misc
Informational
06/18/2021
COURTESY INSPECTION 1 HOUR FIRE WALLS ADDRESS TO ROOF DECK, DON'T 1 SIDE DRYWALL UNTIL IN WALL COMPLETE DON'T INSTALL BORDERS UNTIL ABOVE CEILING COMPLETE
In-wall Inspection Partial 7/1/2021 07/01/2021
Misc
Informational
07/01/2021
THE FOLLOWING AREAS HAVE BEEN APPROVED - IN WALL DWV WOMENS RESTROOM -
In-wall Inspection Failed 7/7/2021 7/7/2021 07/07/2021
Misc
Corrective Action Required
07/07/2021
REPAIR DRYWALL AT CORRIDOR SEAL FLOOR PENETRATIONS SUPPORT VERTICAL DWV 2" & SMALLER AT MIDPOINT THE FOLLOWING AREAS HAVE BEEN APPROVED - IN WALL DWV WOMENS RESTROOM -
In-wall Inspection Passed 7/13/2021 7/13/2021 07/13/2021
Misc
Resolved
07/13/2021
Above Ceiling Inspection Failed 8/16/2021 8/16/2021 08/16/2021
Miscellaneous Correction
Corrective Action Required
08/16/2021
HARD LID IN LOBBY COMPLETE SPRINKLERS, COMPLETE LIGHT FIXTURES
Above Ceiling Inspection Partial 8/19/2021 8/19/2021 08/19/2021
Miscellaneous Correction
Corrective Action Required
08/16/2021
- HARD LID IN RECEPTION AREA, OK TO COVER -
Above Ceiling Inspection Failed 9/17/2021 9/17/2021 09/17/2021
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
08/19/2021
- HARD LID IN RECEPTION AREA, OK TO COVER -
Miscellaneous Correction
Corrective Action Required
09/17/2021
FIRE CAULK PENETRATIONS IN SOUTH 1 HOUR WALL SUPPORT MC CABLE & LOW VOLT FIRE ALARM
Above Ceiling Inspection Failed 9/21/2021 9/21/2021 09/21/2021
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
09/17/2021
- HARD LID IN RECEPTION AREA, OK TO COVER -
Miscellaneous Correction
Corrective Action Required
09/17/2021
FIRE CAULK PENETRATIONS IN SOUTH 1 HOUR WALL SUPPORT MC CABLE & LOW VOLT FIRE ALARM, still incomplete. open box at entry way, fire alarm wire hanging. Fire caulk rear west wall at bathroom with intumescent fire caulk, not foam. install all heat and return ducts , tape and secure.
Above Ceiling Inspection Passed 9/24/2021 9/24/2021 09/24/2021
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
09/21/2021
- HARD LID IN RECEPTION AREA, OK TO COVER -
Miscellaneous Correction
Corrective Action Required
09/21/2021
Alarm Test Failed 10/12/2021 10/12/2021
Alarm Test Passed 10/13/2021 10/13/2021
Occupancy Inspection - Fire Passed 10/13/2021 10/13/2021
Occupancy Inspection - Codes Commercial Failed 10/14/2021 10/14/2021 10/14/2021
Miscellaneous Correction
Corrective Action Required
10/14/2021
Provide GFCI protection at facial room sink
Occupancy Inspection - Codes Commercial Full C of O 10/15/2021 10/15/2021
Miscellaneous Correction
Corrective Action Required
10/14/2021
Provide GFCI protection at facial room sink
Documents & Images
Date Uploaded File Type Document Name
02/28/2021 Plans 20022 MassageLuXe - Lees Summit - ARCH - Binder
03/01/2021 Plans MassageLuXe - Lees Summit - MEP Binder
03/01/2021 Application Form 20022 MassageLuXe - Lees Summit Bldg Permit App
03/02/2021 Email RE LT question
03/02/2021 Letter Fire Building Plan Review
03/03/2021 Letter DS P/R Corrections Document
03/22/2021 Drawing 20022 A0_1 COVER SHEET - PERMIT - REV1
03/22/2021 Drawing 20022 A6_1 SCHEDULES - PERMIT - REV1
03/22/2021 Drawing E105 FIRST FLOOR PLAN - AREA E - ELECTRICAL
03/22/2021 Letter TRI1806-L031921BP1
03/22/2021 Application Form Code Modification Request
03/22/2021 Letter Fire Building Plan Review
03/22/2021 Letter BCS Contractors License
03/22/2021 Approved Plans approved - 20022 MassageLuXe - Lees Summit - ARCH - Binder
03/23/2021 Application Form MEP Contractors
03/23/2021 Application Form Massage Luxe Tax Application
04/06/2021 Letter MEP Contractors Revised 4-6-2021
04/08/2021 Letter License Tax Bill
04/19/2021 Receipt Receipt for transaction:2021-002053
04/19/2021 Letter DS Building Permit
06/18/2021 Letter INSPECTION SUMMARY
07/01/2021 Letter INSPECTION SUMMARY
07/07/2021 Letter INSPECTION SUMMARY
07/13/2021 Letter INSPECTION SUMMARY
08/09/2021 Massage Luxe Fire Sprinkler Plans
08/09/2021 Letter Fire (Sprinkler) Plan Review
08/16/2021 Letter INSPECTION SUMMARY
08/19/2021 Letter INSPECTION SUMMARY
08/25/2021 MassageLuxe Battery Calc FACP
08/25/2021 15348 MassageLuxe FA PE Stamp
08/25/2021 MassageLuxe Battery Calc NAC
08/25/2021 ProjectReports -Summit at W.Pryor - MassageLuxe-2021-08-24
08/25/2021 Letter Fire (Alarm) Plan Review Notice
09/17/2021 Letter INSPECTION SUMMARY
09/21/2021 Letter INSPECTION SUMMARY
09/24/2021 Letter INSPECTION SUMMARY
10/12/2021 Letter Fire Loss Reduction Form
10/13/2021 Letter Fire Loss Reduction Form
10/13/2021 Letter Fire Loss Reduction Form
10/14/2021 Letter INSPECTION SUMMARY
10/15/2021 Letter Field Certificate of Occupancy
10/15/2021 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home