Permit Application Status

PRCOM20192576


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20192576
Building Permit - Commercial
Certificate of Occupancy
CMH PARKS INC
NEW COMMERCIAL
CLUBHOUSE POOL AND SHADE STRUCTURE
09/10/2019
10/30/2019
03/16/2020
01/28/2021
Locations
Contacts
CMH PARKS INC, Address:5000 CLAYTON RD  
CLAYTON PROPERTIES GROUP, INC, Address:10450 Holmes Rd Suite 100, Phone:(816) 246-6700  
B & A ARCHITECTURE, Address:100 W 31ST ST STE 100, Phone:(816) 753-6100  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
TEAGUE ELECTRIC CONSTRUCTION LLC, Address:12425 W 92ND ST, Phone:(913) 529-4600  
R & R PLUMBING INC, Address:2001 GASLIGHT DR, Phone:(816) 772-5431  
JEFF.JWMCONTRACTING@GMAIL.COM  
JWM CONTRACTING LLC, Address:420 NE BROCKTON DR, Phone:(913) 530-4205  
HAWTHORN RIDGE HOMES ASSOCIATION INC, Address:10660 BARKLEY ST STE 200  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 10/02/2019 10/29/2019
Joe Frogge
License Tax Application
Corrective Action Required
09/25/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 9/26/19 - acknowledged in letter
Health Dept Review
Resolved
10/29/2019

For the Health Department review contact Amanda Burch with the Jackson County Public Works Department, Environmental Services Division, at (816) 797-7198. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes. 9/26/19 - acknowledged in letter
Health Dept Inspection
Corrective Action Required
09/25/2019

For the Health Department inspection contact Amanda Burch with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7198. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes. 9/26/19 - acknowledged in letter
Plan Submittal 2012 Codes
Resolved
09/26/2019

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit. Action required: Update code analysis.
Engineered truss package
Corrective Action Required
09/25/2019

Copies of the engineered roof truss package and shade structure were not provided at the time of permit application. Action required: Provide roof truss and shade structure plans or request deferral. 9/26/19 - deferred
Bldg - Two exit or exit access doorways 1015.2.1
Resolved
09/26/2019

2018 IBC 1006.2.1 Egress based on occupant load and common path of egress travel distance. Two exits or exit access doorways from any space shall be provided where the design occupant load or the common path of egress travel distance exceeds the values listed in Table 1006.2.1. The cumulative occupant load from adjacent rooms, areas or spaces shall be determined in accordance with Section 1004.2. (see code for special requirements for foyers, lobbies, vestibules, and care suites in I-2 occupancies) Action required: Provide additional exit out of gated pool area.
Bldg - Door swing 1008.1.2
Resolved
09/26/2019

2018 IBC 1010.1.2 -Door swing. Egress doors shall be of the pivoted or side-hinged swinging type. Exceptions: (See code for exceptions.) Actions required: Do not direct exit through sliding doors.
Bldg - Door swing 1008.1.2
Resolved
09/26/2019

2018 IBC 1010.1.2.1 Direction of swing. Pivot or side-hinged swinging doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy. Action required: Doors out of Great Room must swing in direction of travel. (and not impede egress from other areas)
Miscellaneous Correction
Resolved
09/26/2019

Lee's Summit Code of Ordinances Section 7-1010. - Steps or ladders. Two (2) or more means of egress in the form of steps or ladders shall be provided for all swimming pools. At least one such means of egress shall be located on a side of the pool at both the deep end and shallow end of the pool. Treads of steps and ladders shall be constructed of nonslip material and at least three (3) inches wide for their full length. Steps and ladders shall have a handrail on both sides. Exception: Pools accessory to one- and two-family dwellings. Action required: Provide handrails at both sides of all steps.
Miscellaneous Correction
Resolved
09/26/2019

Right-of-way waiver must be provided if irrigation system will be included with this permit. Action required: Waiver attached. Complete form and include in resubmittal.
Health Department Review Approved 10/29/2019
Joe Frogge
Fire Plan Review Approved with Conditions 10/02/2019 09/27/2019
Michael Weissenbach
Posting of occupant load
Corrective Action Required
09/25/2019

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load signs in clubhouse and outside in the pool area. 45 in Clubhouse. 211 in pool area
Material safety and data sheets
Corrective Action Required
09/25/2019

2018 IFC 407.2- Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be readily available on the premises. (Verified At Inspection)
Address numbers required
Corrective Action Required
09/25/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Portable fire extinguishers - conspicuous locations
Corrective Action Required
09/25/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide 1 2A10BC extinguisher in clubhouse and 1 2A10BC extinguisher in the pool area.
Miscellaneous Correction
Resolved
09/27/2019

(Action Required) Add one additional exit to the pool area. Two exits required with occupancy greater than 50.
Misc
Resolved
09/27/2019

(Informational Purposes) 2018 IFC codes apply
Panic and fire exit hardware
Resolved
09/27/2019

2018 IFC 1010.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is a panic hardware or fire exit hardware. (Action Required) All doors and gates are to have panic hardware.
Direction of swing
Resolved
09/27/2019

2018 IFC 1010.1.2.1 Direction of swing. Doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy. (Action Required) Door 002 in clubhouse needs to swing in the direction of egress travel.
Emergency power for illumination
Resolved
09/27/2019

2018 IFC 1008.3.1 & 3.2 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or mor means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. (Action Required) Remove exit sign by multi-slide door.
Licensed Contractors Approved 10/02/2019 09/26/2019
Joe Frogge
Final Development Plan Review Approved 09/20/2019
Joe Frogge
Building Plan Review Rejected 09/24/2019 09/18/2019
Joe Frogge
Final Development Plan
Resolved
09/20/2019

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
License Tax Application
Corrective Action Required
09/18/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Health Dept Review
Corrective Action Required
09/18/2019

For the Health Department review contact Amanda Burch with the Jackson County Public Works Department, Environmental Services Division, at (816) 797-7198. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is for informational purposes.
Health Dept Inspection
Corrective Action Required
09/18/2019

For the Health Department inspection contact Amanda Burch with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7198. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is for informational purposes.
Plan Submittal 2012 Codes
Corrective Action Required
09/18/2019

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit. Action required: Update code analysis.
Engineered truss package
Corrective Action Required
09/18/2019

Copies of the engineered roof truss package and shade structure were not provided at the time of permit application. Action required: Provide roof truss and shade structure plans or request deferral.
Bldg - Two exit or exit access doorways 1015.2.1
Corrective Action Required
09/18/2019

2018 IBC 1006.2.1 Egress based on occupant load and common path of egress travel distance. Two exits or exit access doorways from any space shall be provided where the design occupant load or the common path of egress travel distance exceeds the values listed in Table 1006.2.1. The cumulative occupant load from adjacent rooms, areas or spaces shall be determined in accordance with Section 1004.2. (see code for special requirements for foyers, lobbies, vestibules, and care suites in I-2 occupancies) Action required: Provide additional exit out of gated pool area.
Bldg - Door swing 1008.1.2
Corrective Action Required
09/18/2019

2018 IBC 1010.1.2 -Door swing. Egress doors shall be of the pivoted or side-hinged swinging type. Exceptions: (See code for exceptions.) Actions required: Do not direct exit through sliding doors.
Bldg - Door swing 1008.1.2
Corrective Action Required
09/18/2019

2018 IBC 1010.1.2.1 Direction of swing. Pivot or side-hinged swinging doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy. Action required: Doors out of Great Room must swing in direction of travel. (and not impede egress from other areas)
Miscellaneous Correction
Corrective Action Required
09/18/2019

Lee's Summit Code of Ordinances Section 7-1010. - Steps or ladders. Two (2) or more means of egress in the form of steps or ladders shall be provided for all swimming pools. At least one such means of egress shall be located on a side of the pool at both the deep end and shallow end of the pool. Treads of steps and ladders shall be constructed of nonslip material and at least three (3) inches wide for their full length. Steps and ladders shall have a handrail on both sides. Exception: Pools accessory to one- and two-family dwellings. Action required: Provide handrails at both sides of all steps.
Miscellaneous Correction
Corrective Action Required
09/18/2019

Right-of-way waiver must be provided if irrigation system will be included with this permit. Action required: Waiver attached. Complete form and include in resubmittal.
Fire Plan Review Rejected 09/24/2019 09/12/2019
Michael Weissenbach
Posting of occupant load
Corrective Action Required
09/12/2019

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. (Verified At Inspection) Post occupant load signs in clubhouse and outside in the pool area.
Material safety and data sheets
Corrective Action Required
09/12/2019

2018 IFC 407.2- Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be readily available on the premises. (Verified At Inspection)
Address numbers required
Corrective Action Required
09/12/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Portable fire extinguishers - conspicuous locations
Corrective Action Required
09/12/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Action Required) Provide 1 2A10BC extinguisher in clubhouse and 1 2A10BC extinguisher in the pool area.
Miscellaneous Correction
Corrective Action Required
09/12/2019

(Action Required) Add one additional exit to the pool area. Two exits required with occupancy greater than 50.
Misc
Corrective Action Required
09/12/2019

(Informational Purposes) 2018 IFC codes apply
Panic and fire exit hardware
Corrective Action Required
09/12/2019

2018 IFC 1010.1.10 Panic and fire exit hardware. Doors serving a Group H occupancy and doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock unless it is a panic hardware or fire exit hardware. (Action Required) All doors and gates are to have panic hardware.
Direction of swing
Corrective Action Required
09/12/2019

2018 IFC 1010.1.2.1 Direction of swing. Doors shall swing in the direction of egress travel where serving a room or area containing an occupant load of 50 or more persons or a Group H occupancy. (Action Required) Door 002 in clubhouse needs to swing in the direction of egress travel.
Emergency power for illumination
Corrective Action Required
09/12/2019

2018 IFC 1008.3.1 & 3.2 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or mor means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. (Action Required) Remove exit sign by multi-slide door.
Licensed Contractors Approved 09/24/2019 09/10/2019
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Commercial $2,560.00 $2,560.00 Paid 10/30/2019
8331507-Sewer Connection Fee $330.00 $330.00 Paid 10/30/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Passed 11/1/2019 11/1/2019 11/01/2019
Misc
Informational
11/01/2019
Ok to pour, 3rd party inspected as well
Underslab Plumbing Inspection - Commercial Passed 11/18/2019 11/18/2019 11/18/2019
Foundation Inspection - Commercial Passed 11/20/2019 11/20/2019 11/20/2019
Misc
Informational
11/20/2019
Ok to pour
Pool Steel/Bonding - Commercial Passed 12/13/2019 12/13/2019 12/13/2019
Misc
Informational
12/13/2019
Pool steel bonding approved and okay to cover when ready
All Rough Inspection - Commercial Failed 3/23/2020 3/23/2020 03/23/2020
Misc
Corrective Action Required
03/23/2020
- provide truss drawing & layout - address notched LVL above sliding glass door - Provide roof boot above pool bath floor - provide boca plate vent to roof at ceiling - provide boca plate vtr pool bath - provide missing H2.5 truss above mechanical room door
All Rough Inspection - Commercial Partial 3/27/2020 3/27/2020 03/27/2020
Misc
Corrective Action Required
03/23/2020
- address notched LVL above sliding glass door - engineer fix per letter Alex will email letter to be attached to permit
In-wall Inspection Passed 3/27/2020 3/27/2020 03/27/2020
Pool Steel/Bonding - Commercial Passed 5/14/2020 5/14/2020 05/14/2020
Misc
Informational
05/14/2020
POOL DECK, LADDERS, HANDRAILS, SLIDE
All Rough Inspection - Commercial Passed 5/28/2020 05/28/2020
Misc
Resolved
05/28/2020
Electrical Service Inspection Passed 5/28/2020 5/28/2020 05/28/2020
Misc
Resolved
05/28/2020
Gas Service Inspection - Commercial Passed 6/2/2020 6/2/2020 06/02/2020
Sidewalk Inspection Passed 12/12/2019 7/6/2020 07/06/2020
Driveway Inspection Passed 12/12/2019 7/6/2020 07/06/2020
Occupancy Inspection - Engineering Temporary C of O 7/6/2020 07/06/2020
Occupancy Inspection - Codes Commercial Failed 7/15/2020 7/15/2020 07/15/2020
Misc
Corrective Action Required
07/15/2020
- SECURE CONDUIT AT GATE - - ALL RESTROOM REAR GRAB BARS 6" MAX - - RESTROOM SIGNS SHALL BE WALL MOUNTED - - PROVIDE SIGNAGE POOL EQUIPMENT ROOM - - SECURE WATER LINE & EXTEND TO FLOOR DRAIN IN POOL EQUIPMENT ROOM - - PROVIDE MAX 2" FENCE TO LANDSCAPING NEAR SLIDE - - SECURE A/C WHIP - - PROVIDE SPLIT BOLT BARE COPPER & GREEN GROUND POOL EQUIPMENT ROOM - - POOL FENCE OPENING NOT MORE THAN 1/2" AT GATE - - PROVIDE 42" GUARDRAIL AT SLIDE - - PROVIDE HANDRAIL SLIDE STEPS - - NO FOOTING INSPECTIONS FOR MONUMENT SIGNS -
Occupancy Inspection - Fire Temporary C of O 7/15/2020 7/15/2020 07/15/2020
Occupancy Inspection - Planning Temporary C of O 7/15/2020 07/15/2020
Corrective Action Required
07/15/2020
Incorrect ADA sing was present. The only approved ADA sign is the R7-8 style sign.
Occupancy Inspection - Codes Commercial Temporary C of O 7/17/2020 07/17/2020
Misc
Corrective Action Required
07/15/2020
- SLIDE NOT USEABLE UNTIL GUARDRAIL & HANDRAIL ADDRESSED WITH PERMANENT RAILS - - GATES HAVE TEMP GUARD REPLACE WITH PERMANENT GUARDS ASAP - - ALL RESTROOM REAR GRAB BARS 6" MAX - - PROVIDE SIGNAGE POOL EQUIPMENT ROOM - - SECURE A/C WHIP - - POOL FENCE OPENING NOT MORE THAN 1/2" AT GATE - - PROVIDE 42" GUARDRAIL AT SLIDE - - PROVIDE HANDRAIL SLIDE STEPS - - NO FOOTING INSPECTIONS FOR MONUMENT SIGNS -
Occupancy Inspection - Codes Commercial Temporary C of O 7/31/2020 7/31/2020 07/31/2020
Misc
Corrective Action Required
07/17/2020
- GATES HAVE TEMP GUARD REPLACE WITH PERMANENT GUARDS ASAP - - NO FOOTING INSPECTIONS FOR MONUMENT SIGNS -
Occupancy Inspection - Fire Passed 8/3/2020 08/03/2020
Occupancy Inspection - Water Utilities Passed 8/4/2020 08/04/2020
Occupancy Inspection - Codes Commercial Temporary C of O 8/7/2020 8/7/2020 08/07/2020
Misc
Corrective Action Required
07/31/2020
- NO FOOTING INSPECTIONS FOR MONUMENT SIGNS - SUBMIT ENGINEER REPORT
Occupancy Inspection - Engineering Passed 9/24/2020 09/24/2020
Occupancy Inspection - Planning Passed 9/24/2020 09/24/2020
Occupancy Inspection - Codes Commercial Full C of O 1/28/2021 01/28/2021
Misc
Resolved
01/28/2021
- NO FOOTING INSPECTIONS FOR MONUMENT SIGNS - SUBMIT ENGINEER REPORT
Documents & Images
Date Uploaded File Type Document Name
09/10/2019 Letter License Tax Not Applicable
09/12/2019 Letter Fire Building Plan Review
09/18/2019 Letter DS P/R Corrections Document
09/27/2019 Letter Fire Building Plan Review
10/29/2019 Fw EXTERNAL RE Permit for Swimming Pool - Lee's Summit MO
10/30/2019 Receipt Receipt for transaction: 2019-007086
10/30/2019 Letter DS Building Permit
11/01/2019 Letter INSPECTION SUMMARY
11/18/2019 Letter INSPECTION SUMMARY
11/20/2019 Letter INSPECTION SUMMARY
12/13/2019 Letter INSPECTION SUMMARY
03/23/2020 Letter INSPECTION SUMMARY
03/23/2020 Letter INSPECTION SUMMARY
03/27/2020 Letter INSPECTION SUMMARY
03/27/2020 Letter INSPECTION SUMMARY
04/02/2020 Engineer Report/Study Hawthorn Ridge Clubhouse - Remedial Detail 03-23-20
05/14/2020 Letter INSPECTION SUMMARY
05/28/2020 Letter INSPECTION SUMMARY
05/28/2020 Letter INSPECTION SUMMARY
06/02/2020 Letter INSPECTION SUMMARY
07/06/2020 Letter INSPECTION SUMMARY
07/06/2020 Letter INSPECTION SUMMARY
07/15/2020 Letter INSPECTION SUMMARY
07/16/2020 Engineer Report/Study Pool Slide Railing Issue - 20192576
07/17/2020 Letter Codes Temporary Certificate of Occupancy
07/31/2020 Letter Codes Temporary Certificate of Occupancy
08/07/2020 Letter Codes Temporary Certificate of Occupancy
01/25/2021 Letter INSPECTION SUMMARY
01/28/2021 Letter Codes Final Certificate of Occupancy
01/28/2021 Letter Field Certificate of Occupancy
01/28/2021 Hawthorne Monuments
01/28/2021 Hawthorn Ridge Monument Sign_Foundation Evaluation Report_9-28-20
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home