Review Type |
Outcome |
Est. Completion Date |
Completed |
Fire Plan Review
|
Approved with Conditions
|
11/15/2018
|
05/06/2019
|
|
Joe Dir
|
|
Address numbers required
Corrective Action Required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
ACTION REQUIRED: (verified at inspection)
Building address (2320) shall be readable from the roadway (Independence Ave.)
|
|
Portable fire extinguishers - general
Corrective Action Required
2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
ACTION REQUIRED: (verified at inspection)
Provide a minimum of one 2A-10BC (5 pound) fire extinguisher for every 3,000 square feet of useable space. Provide one fire extinguisher located within a 75' travel distance to the fuel dispensing pump.
|
|
Miscellaneous Correction
Duct detection
ACTION REQUIRED:(verified at inspection)
Duct detection shall comply with the IFC 2012 code requirements. Reference section
IFC 2012 907.3.1 Duct smoke detectors.
|
|
Locks on gates or barriers
Corrective Action Required
2012 IFC 506.1.1-Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official.
ACTION REQUIRED:(verified at inspection)
An electronic controlled gate will require a (knox key switch), a chained gate will require a (knox padlock).
Padlock or key switch can be obtained on line at knoxbox.com
|
|
Hazardous material identification
2012 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5.
ACTION REQUIRED: (verified at inspection)
Fuel tank shall be clearly labeled and marked with all appropriate labels, warnings and palcards.
|
|
Miscellaneous Correction
Emergency shut-off switch
ACTION REQUIRED:(verified at inspection)
Intall the emergency shut off switch for the fuel dispensing areaaccording to the requirements listed.
IFC 2012 2303.2 Emergency disconnect switches. An approved, clearly identified and readily accessible emergency disconnect switch shall be provided at an approved location to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. An emergency disconnect switch for exterior fuel dispensers shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations,
the emergency disconnect switch shall be installed at an approved location. Such devices shall be distinctly labeled as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations.
|
|
Material safety and data sheets
2012 IFC 407.2- Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be readily available on the premises.
ACTION REQUIRED:(information purposes)
A Hazardous Materials Permit will be required in order for the fuel tank to be located on the premises. The Haz-Mat permit can be obtained through the Fire Department.
|
|
Miscellaneous Correction
Private Fire hydrant
ACTION REQUIRED: (verified at inspection)
The top bonnet portion of the private fire hydrant shall be painted (silver) to designate a private fire hydrant
|
|
Miscellaneous Correction
Corrective Action Required
Signs
ACTION REQUIRED:(verified at inspection)
Establish a fire lane for the access roadway to the rear of the building.
IFC 2012 D103.6 Signs. Where required by the fire code official, fire apparatus access roads shall be marked with permanent NO PARKING—FIRE LANE signs complying with Figure D103.6. Signs shall have a minimum dimension of 12 inches (305 mm) wide by 18 inches (457 mm) high and have red letters on a white reflective background. Signs shall be posted on one or both sides of the fire apparatus road as required by Section D103.6.1 or D103.6.2
|
|
|
Alarm Plan Review
|
Released for Construction
|
|
04/09/2019
|
|
Joe Dir
|
|
Installation acceptance testing
Corrective Action Required
2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
ACTION REQUIRED:(information purposes)
Acceptance testing of the alarm system will be required prior to the final occupancy inspection. Contact the fire department to schedule testing.
(816)969-1300
|
|
Misc
Corrective Action Required
Sequence of operations
ACTION REQUIRED:(verified at inspection)
Duct detection shall not activate building notification devices. Duct detection shall not release doors.
|
|
|
Final Development Plan Review
|
Approved
|
05/01/2019
|
12/04/2018
|
|
Joe Frogge
|
|
|
Fire Plan Review
|
Approved with Conditions
|
11/15/2018
|
11/12/2018
|
|
Joe Dir
|
|
Address numbers required
Corrective Action Required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
ACTION REQUIRED: (verified at inspection)
Building address (2320) shall be readable from the roadway (Independence Ave.)
|
|
Installation acceptance testing
2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
ACTION REQUIRED: (information purposes)
Acceptance testing of the fire alarm system will be required prior to the final occupancy inspection.
|
|
Portable fire extinguishers - general
Corrective Action Required
2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
ACTION REQUIRED: (verified at inspection)
Provide a minimum of one 2A-10BC (5 pound) fire extinguisher for every 3,000 square feet of useable space. the extinguishers shall be mounted on walls or in extinguisher cabinets on a normal path of travel close to exits.
|
|
Miscellaneous Correction
General fire protection and life safety requirements.
ACTION REQUIRED:
IFC 2012 3206.2 Extent and type of protection. Where required by Table 3206.2, fire detection systems, smoke and heat removal, draft curtains and automatic sprinkler design densities
shall extend the lesser of 15 feet (4572 mm) beyond the high-piled storage area or to a permanent partition. Where portions of high-piled storage areas have different fire protection
requirements because of commodity, method of storage or storage height, the fire protection features required by Table 3206.2 within this area shall be based on the most restrictive design requirements.
ACTION REQUIRED: Reference IFC table 3206.2 Option-2 of class I-IV commodity and provide information on how the requirements will be met.
ACTION REQUIRED:
IFC 2012 3206.7 Smoke and heat removal. Where smoke and heat removal are required by Table 3206.2, smoke and heat vents shall be provided in accordance with Section 910. Where draft curtains are required by Table 3206.2, they shall be provided in accordance with Section 910.3.5.
|
|
Miscellaneous Correction
Corrective Action Required
Duct detection
ACTION REQUIRED:(verified at inspection)
Duct detection shall comply with the IFC 2012 code requirements. Reference section
IFC 2012 907.3.1 Duct smoke detectors.
|
|
Misc
Door hardware
ACTION REQUIRED: Correction needed for the following doors and hardware.
Panic hardware needed for warehouse (door 05)
Panic hardware not required for IT room (door 07)
Panic hardware for entry (door 06) if door 06 is to be secured no keyed locks on the egress side of an exit. IFC 2012 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
|
|
Locks on gates or barriers
Corrective Action Required
2012 IFC 506.1.1-Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official.
ACTION REQUIRED:(verified at inspection)
An electronic controlled gate will require a (knox key switch), a chained gate will require a (knox padlock).
Padlock or key switch can be obtained on line at knoxbox.com
|
|
Hazardous material identification
Corrective Action Required
2012 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5.
ACTION REQUIRED: (verified at inspection)
Fuel tank shall be clearly labeled and marked with all appropriate labels, warnings and palcards.
|
|
Miscellaneous Correction
Corrective Action Required
Emergency shut-off switch
ACTION REQUIRED:(verified at inspection)
Intall the emergency shut off switch for the fuel dispensing areaaccording to the requirements listed.
IFC 2012 2303.2 Emergency disconnect switches. An approved, clearly identified and readily accessible emergency disconnect switch shall be provided at an approved location to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. An emergency disconnect switch for exterior fuel dispensers shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations,
the emergency disconnect switch shall be installed at an approved location. Such devices shall be distinctly labeled as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations.
|
|
Material safety and data sheets
Corrective Action Required
2012 IFC 407.2- Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be readily available on the premises.
ACTION REQUIRED:(information purposes)
A Hazardous Materials Permit will be required in order for the fuel tank to be located on the premises. The Haz-Mat permit can be obtained through the Fire Department.
|
|
Miscellaneous Correction
Corrective Action Required
Private Fire hydrant
ACTION REQUIRED: (verified at inspection)
The top bonnet portion of the private fire hydrant shall be painted (silver) to designate a private fire hydrant
|
|
Miscellaneous Correction
Corrective Action Required
Signs
ACTION REQUIRED:(verified at inspection)
Establish a fire lane for the access roadway to the rear of the building.
IFC 2012 D103.6 Signs. Where required by the fire code official, fire apparatus access roads shall be marked with permanent NO PARKING—FIRE LANE signs complying with Figure D103.6. Signs shall have a minimum dimension of 12 inches (305 mm) wide by 18 inches (457 mm) high and have red letters on a white reflective background. Signs shall be posted on one or both sides of the fire apparatus road as required by Section D103.6.1 or D103.6.2
|
|
|
Building Plan Review
|
Approved with Conditions
|
11/15/2018
|
11/08/2018
|
|
Joe Frogge
|
|
Final Development Plan
The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department.
Action required: Comment is for informational purposes.
11/8/18 - not addressed
|
|
License Tax Application
Corrective Action Required
A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Action required: Comment is for informational purposes.
11/8/18 - not addressed
|
|
Miscellaneous Correction
Corrective Action Required
Design for retaining wall not found in submittal.
Action required: Provide retaining wall design or request deferral.
11/8/18 - deferred per request
|
|
Screening - Ground mounted equipment
Unified Development Ordinance Article 7, Section 7.180.F
Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened.
Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section.
|
|
Bldg - Common path of egress travel 1014.3
2012 IBC 1014.3 – Common path of egress travel. The common path of egress travel shall not exceed the common path of egress travel distances in Table 1014.3.
Actions required (2):
- Modify mezzanine plan to show common path measurement at right angles. (will be compliant as 100' will be allowed)
- Modify design where common path of travel is exceeded from Gym/Office 109 and Jeff's Office 117.
|
|
Accessibility - Vertical clearance 307.4
ICC A117.1-2009 Section 307.4 Vertical Clearance. Vertical clearance shall be 80 inches minimum. Rails or other barriers shall be provided where the vertical clearance is less than 80 inches. The leading edge of such rails or barrier shall be located 27 inches maximum above the floor.
Action required: Provide blocking, guards, or other approved method to comply at area under stairs.
|
|
Engineered truss package
Corrective Action Required
Copies of the pre-engineered metal building package were not provided at the time of permit application.
Action required: Provide metal building package or request deferral.
11/8/18 - deferred per request
|
|
Accessibility - Dining surface height 902.4
ICC A117.1-2009 Section 902.4 Height. The tops of dining surfaces and work surfaces shall be 28 inches minimum and 34 inches maximum in height above the floor.
Action required: Provide accessible portions of dining surfaces in break rooms.
|
|
Bldg - Toilet room wall finish 1210.2.2
2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.)
Action required: Specify compliant wall finish materials at mop sink.
|
|
Mech - Condensate disposal - Evaporators and cooling coils 307.2
2012 IMC 307.2.1 Condensate disposal. Condensate from all cooling coils and evaporators shall be conveyed from the drain pan outlet to an approved place of disposal. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than one-eighth unit vertical in 12 units horizontal. Condensate shall not discharge into a street, alley or other areas so as to cause a nuisance.
Action required: Specify condensate drain terminations at furnaces.
|
|
Miscellaneous Correction
2011 NEC Article 500.1 Scope – Articles 500 Through 504. Articles 500 through 504 cover the requirements for electrical and electronic equipment and wiring for all voltages in Class I, Divisions 1 and 2; Class II, Divisions 1 and 2; and Class III, Divisions 1 and 2 locations where fire or explosion hazards may exist due to flammable gases, flammable liquid-produces vapors, combustible liquid-produced vapors, combustible liquid-produced vapors, combustible dusts, or ignitable fibers/flyings. (see code for additional information and specific requirements)
Action required: Specify compliant electrical design at fuel tank.
|
|
|
Licensed Contractors
|
Approved
|
11/08/2018
|
11/08/2018
|
|
Joe Frogge
|
|
|
Special Inspections Review
|
Approved
|
05/01/2019
|
11/08/2018
|
|
Joe Frogge
|
|
|
Building Plan Review
|
Rejected
|
11/09/2018
|
11/02/2018
|
|
Joe Frogge
|
|
Final Development Plan
Corrective Action Required
The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department.
Action required: Comment is for informational purposes.
|
|
License Tax Application
Corrective Action Required
A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Action required: Comment is for informational purposes.
|
|
Miscellaneous Correction
2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions)
Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
|
|
Miscellaneous Correction
Corrective Action Required
Design for retaining wall not found in submittal.
Action required: Provide retaining wall design or request deferral.
|
|
Screening - Ground mounted equipment
Corrective Action Required
Unified Development Ordinance Article 7, Section 7.180.F
Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened.
Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section.
|
|
Bldg - Common path of egress travel 1014.3
Corrective Action Required
2012 IBC 1014.3 – Common path of egress travel. The common path of egress travel shall not exceed the common path of egress travel distances in Table 1014.3.
Actions required (2):
- Modify mezzanine plan to show common path measurement at right angles. (will be compliant as 100' will be allowed)
- Modify design where common path of travel is exceeded from Gym/Office 109 and Jeff's Office 117.
|
|
Accessibility - Vertical clearance 307.4
Corrective Action Required
ICC A117.1-2009 Section 307.4 Vertical Clearance. Vertical clearance shall be 80 inches minimum. Rails or other barriers shall be provided where the vertical clearance is less than 80 inches. The leading edge of such rails or barrier shall be located 27 inches maximum above the floor.
Action required: Provide blocking, guards, or other approved method to comply at area under stairs.
|
|
Engineered truss package
Corrective Action Required
Copies of the pre-engineered metal building package were not provided at the time of permit application.
Action required: Provide metal building package or request deferral.
|
|
Accessibility - Dining surface height 902.4
Corrective Action Required
ICC A117.1-2009 Section 902.4 Height. The tops of dining surfaces and work surfaces shall be 28 inches minimum and 34 inches maximum in height above the floor.
Action required: Provide accessible portions of dining surfaces in break rooms.
|
|
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.)
Action required: Specify compliant wall finish materials at mop sink.
|
|
Miscellaneous Correction
2012 IMC 501.3.1 Location of exhaust outlets. The termination point of exhaust outlets and ducts discharging to the outdoors shall be located with the following minimum distances:
(see code for items 1, 2, 4, & 5)
3. For all environmental air exhaust: 3 feet from property lines; 3 feet from operable openings into building for all occupancies other than Group U, and 10 feet from mechanical air intakes. Such exhaust shall not be considered hazardous or noxious.
Action required: Modify design to provide minimum 10' clearance between exhaust fan and furnace combustion air intakes.
|
|
Mech - Condensate disposal - Evaporators and cooling coils 307.2
Corrective Action Required
2012 IMC 307.2.1 Condensate disposal. Condensate from all cooling coils and evaporators shall be conveyed from the drain pan outlet to an approved place of disposal. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than one-eighth unit vertical in 12 units horizontal. Condensate shall not discharge into a street, alley or other areas so as to cause a nuisance.
Action required: Specify condensate drain terminations at furnaces.
|
|
Miscellaneous Correction
Corrective Action Required
2011 NEC Article 500.1 Scope – Articles 500 Through 504. Articles 500 through 504 cover the requirements for electrical and electronic equipment and wiring for all voltages in Class I, Divisions 1 and 2; Class II, Divisions 1 and 2; and Class III, Divisions 1 and 2 locations where fire or explosion hazards may exist due to flammable gases, flammable liquid-produces vapors, combustible liquid-produced vapors, combustible liquid-produced vapors, combustible dusts, or ignitable fibers/flyings. (see code for additional information and specific requirements)
Action required: Specify compliant electrical design at fuel tank.
|
|
|
Fire Plan Review
|
Rejected
|
11/09/2018
|
11/01/2018
|
|
Joe Dir
|
|
Address numbers required
Corrective Action Required
2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
ACTION REQUIRED: (verified at inspection)
Building address (2320) shall be readable from the roadway (Independence Ave.)
|
|
Installation acceptance testing
Corrective Action Required
2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
ACTION REQUIRED: (information purposes)
Acceptance testing of the fire alarm system will be required prior to the final occupancy inspection.
|
|
Portable fire extinguishers - general
Corrective Action Required
2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
ACTION REQUIRED: (verified at inspection)
Provide a minimum of one 2A-10BC (5 pound) fire extinguisher for every 3,000 square feet of useable space. the extinguishers shall be mounted on walls or in extinguisher cabinets on a normal path of travel close to exits.
|
|
Miscellaneous Correction
Corrective Action Required
General fire protection and life safety requirements.
ACTION REQUIRED:
IFC 2012 3206.2 Extent and type of protection. Where required by Table 3206.2, fire detection systems, smoke and heat removal, draft curtains and automatic sprinkler design densities
shall extend the lesser of 15 feet (4572 mm) beyond the high-piled storage area or to a permanent partition. Where portions of high-piled storage areas have different fire protection
requirements because of commodity, method of storage or storage height, the fire protection features required by Table 3206.2 within this area shall be based on the most restrictive design requirements.
ACTION REQUIRED: Reference IFC table 3206.2 Option-2 of class I-IV commodity and provide information on how the requirements will be met.
ACTION REQUIRED:
IFC 2012 3206.7 Smoke and heat removal. Where smoke and heat removal are required by Table 3206.2, smoke and heat vents shall be provided in accordance with Section 910. Where draft curtains are required by Table 3206.2, they shall be provided in accordance with Section 910.3.5.
|
|
Miscellaneous Correction
Corrective Action Required
Duct detection
ACTION REQUIRED: Duct detection shall comply with the IFC 2012 code requirements. Reference section
IFC 2012 907.3.1 Duct smoke detectors.
|
|
Misc
Corrective Action Required
Door hardware
ACTION REQUIRED: Correction needed for the following doors and hardware.
Panic hardware needed for warehouse (door 05)
Panic hardware not required for IT room (door 07)
Panic hardware for entry (door 06) if door 06 is to be secured no keyed locks on the egress side of an exit. IFC 2012 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
|
|
Locks on gates or barriers
Corrective Action Required
2012 IFC 506.1.1-Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official.
ACTION REQUIRED: An electronic controlled gate will require a (knox key switch), a chained gate will require a (knox padlock).
Padlock or key switch can be obtained on line at knoxbox.com
|
|
Hazardous material identification
Corrective Action Required
2012 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5.
ACTION REQUIRED: (verified at inspection)
Fuel tank shall be clearly labeled and marked with all appropriate labels, warnings and palcards.
|
|
Miscellaneous Correction
Corrective Action Required
Emergency shut-off switch
ACTION REQUIRED: Show the location of the emergency shut off switch for the fuel dispensing area.
IFC 2012 2303.2 Emergency disconnect switches. An approved, clearly identified and readily accessible emergency disconnect switch shall be provided at an approved location to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. An emergency disconnect switch for exterior fuel dispensers shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations,
the emergency disconnect switch shall be installed at an approved location. Such devices shall be distinctly labeled as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations.
|
|
Material safety and data sheets
Corrective Action Required
2012 IFC 407.2- Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be readily available on the premises.
ACTION REQUIRED:(information purposes)
A Hazardous Materials Permit will be required in order for the fuel tank to be located on the premises. The Haz-Mat permit can be obtained through the Fire Department.
|
|
Miscellaneous Correction
Corrective Action Required
Private Fire hydrant
ACTION REQUIRED: (verified at inspection)
The top bonnet portion of the private fire hydrant shall be painted (silver) to designate a private fire hydrant
|
|
Miscellaneous Correction
Corrective Action Required
Signs
ACTION REQUIRED: Establish a fire lane for the access roadway to the rear of the building.
IFC 2012 D103.6 Signs. Where required by the fire code official, fire apparatus access roads shall be marked with permanent NO PARKING—FIRE LANE signs complying with Figure D103.6. Signs shall have a minimum dimension of 12 inches (305 mm) wide by 18 inches (457 mm) high and have red letters on a white reflective background. Signs shall be posted on one or both sides of the fire apparatus road as required by Section D103.6.1 or D103.6.2
|
|
|
Licensed Contractors
|
Approved
|
11/07/2018
|
10/29/2018
|
|
Joe Frogge
|
|
|