Permit Application Status

PRCOM20183710


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20183710
Building Permit - Commercial
Certificate of Occupancy
L & M INVESTMENTS LLC
NEW COMMERCIAL
NEW OFFICE/WAREHOUSE **MEZZANINE OMITTED
10/26/2018
12/04/2018
05/07/2019
11/27/2019
Locations
Contacts
L & M INVESTMENTS LLC, Address:301 DUCK RD  
A L HUBER INC, Address:10770 EL MONTE, Phone:(913) 341-4880  
DAVIDSON ARCHITECTURE & ENGINEERING, Address:4301 INDIAN CREEK PKWY, Phone:(913) 451-9390  
LBA AIR CONDITIONING, HEATING AND PLUMBING INC, Address:6850 W 47TH TER, Phone:(913) 268-6822  
TEAGUE ELECTRIC CONSTRUCTION INC, Address:12425 W 92ND ST, Phone:(913) 529-4600  
LBA AIR CONDITIONING, HEATING AND PLUMBING INC, Address:6850 W 47TH TER, Phone:(913) 268-6822  
KDORRIAN@ASHUBER.COM  
KANSAS CITY TESTING AND ENGINEERING LLC, Address:1141 SOUTHWEST BLVD, Phone:(913) 321-8100  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 11/15/2018 05/06/2019
Joe Dir
Address numbers required
Corrective Action Required
05/06/2019

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED: (verified at inspection) Building address (2320) shall be readable from the roadway (Independence Ave.)
Portable fire extinguishers - general
Corrective Action Required
05/06/2019

2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED: (verified at inspection) Provide a minimum of one 2A-10BC (5 pound) fire extinguisher for every 3,000 square feet of useable space. Provide one fire extinguisher located within a 75' travel distance to the fuel dispensing pump.
Miscellaneous Correction
Resolved
05/06/2019

Duct detection ACTION REQUIRED:(verified at inspection) Duct detection shall comply with the IFC 2012 code requirements. Reference section IFC 2012 907.3.1 Duct smoke detectors.
Locks on gates or barriers
Corrective Action Required
05/06/2019

2012 IFC 506.1.1-Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official. ACTION REQUIRED:(verified at inspection) An electronic controlled gate will require a (knox key switch), a chained gate will require a (knox padlock). Padlock or key switch can be obtained on line at knoxbox.com
Hazardous material identification
Resolved
05/06/2019

2012 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. ACTION REQUIRED: (verified at inspection) Fuel tank shall be clearly labeled and marked with all appropriate labels, warnings and palcards.
Miscellaneous Correction
Resolved
05/06/2019

Emergency shut-off switch ACTION REQUIRED:(verified at inspection) Intall the emergency shut off switch for the fuel dispensing areaaccording to the requirements listed. IFC 2012 2303.2 Emergency disconnect switches. An approved, clearly identified and readily accessible emergency disconnect switch shall be provided at an approved location to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. An emergency disconnect switch for exterior fuel dispensers shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations, the emergency disconnect switch shall be installed at an approved location. Such devices shall be distinctly labeled as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations.
Material safety and data sheets
Resolved
05/06/2019

2012 IFC 407.2- Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be readily available on the premises. ACTION REQUIRED:(information purposes) A Hazardous Materials Permit will be required in order for the fuel tank to be located on the premises. The Haz-Mat permit can be obtained through the Fire Department.
Miscellaneous Correction
Resolved
05/06/2019

Private Fire hydrant ACTION REQUIRED: (verified at inspection) The top bonnet portion of the private fire hydrant shall be painted (silver) to designate a private fire hydrant
Miscellaneous Correction
Corrective Action Required
05/06/2019

Signs ACTION REQUIRED:(verified at inspection) Establish a fire lane for the access roadway to the rear of the building. IFC 2012 D103.6 Signs. Where required by the fire code official, fire apparatus access roads shall be marked with permanent NO PARKING—FIRE LANE signs complying with Figure D103.6. Signs shall have a minimum dimension of 12 inches (305 mm) wide by 18 inches (457 mm) high and have red letters on a white reflective background. Signs shall be posted on one or both sides of the fire apparatus road as required by Section D103.6.1 or D103.6.2
Alarm Plan Review Released for Construction 04/09/2019
Joe Dir
Installation acceptance testing
Corrective Action Required
04/09/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED:(information purposes) Acceptance testing of the alarm system will be required prior to the final occupancy inspection. Contact the fire department to schedule testing. (816)969-1300
Misc
Corrective Action Required
04/09/2019

Sequence of operations ACTION REQUIRED:(verified at inspection) Duct detection shall not activate building notification devices. Duct detection shall not release doors.
Final Development Plan Review Approved 05/01/2019 12/04/2018
Joe Frogge
Fire Plan Review Approved with Conditions 11/15/2018 11/12/2018
Joe Dir
Address numbers required
Corrective Action Required
11/08/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED: (verified at inspection) Building address (2320) shall be readable from the roadway (Independence Ave.)
Installation acceptance testing
Resolved
11/12/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: (information purposes) Acceptance testing of the fire alarm system will be required prior to the final occupancy inspection.
Portable fire extinguishers - general
Corrective Action Required
11/08/2018

2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED: (verified at inspection) Provide a minimum of one 2A-10BC (5 pound) fire extinguisher for every 3,000 square feet of useable space. the extinguishers shall be mounted on walls or in extinguisher cabinets on a normal path of travel close to exits.
Miscellaneous Correction
Resolved
11/12/2018

General fire protection and life safety requirements. ACTION REQUIRED: IFC 2012 3206.2 Extent and type of protection. Where required by Table 3206.2, fire detection systems, smoke and heat removal, draft curtains and automatic sprinkler design densities shall extend the lesser of 15 feet (4572 mm) beyond the high-piled storage area or to a permanent partition. Where portions of high-piled storage areas have different fire protection requirements because of commodity, method of storage or storage height, the fire protection features required by Table 3206.2 within this area shall be based on the most restrictive design requirements. ACTION REQUIRED: Reference IFC table 3206.2 Option-2 of class I-IV commodity and provide information on how the requirements will be met. ACTION REQUIRED: IFC 2012 3206.7 Smoke and heat removal. Where smoke and heat removal are required by Table 3206.2, smoke and heat vents shall be provided in accordance with Section 910. Where draft curtains are required by Table 3206.2, they shall be provided in accordance with Section 910.3.5.
Miscellaneous Correction
Corrective Action Required
11/08/2018

Duct detection ACTION REQUIRED:(verified at inspection) Duct detection shall comply with the IFC 2012 code requirements. Reference section IFC 2012 907.3.1 Duct smoke detectors.
Misc
Resolved
11/12/2018

Door hardware ACTION REQUIRED: Correction needed for the following doors and hardware. Panic hardware needed for warehouse (door 05) Panic hardware not required for IT room (door 07) Panic hardware for entry (door 06) if door 06 is to be secured no keyed locks on the egress side of an exit. IFC 2012 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Locks on gates or barriers
Corrective Action Required
11/08/2018

2012 IFC 506.1.1-Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official. ACTION REQUIRED:(verified at inspection) An electronic controlled gate will require a (knox key switch), a chained gate will require a (knox padlock). Padlock or key switch can be obtained on line at knoxbox.com
Hazardous material identification
Corrective Action Required
11/08/2018

2012 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. ACTION REQUIRED: (verified at inspection) Fuel tank shall be clearly labeled and marked with all appropriate labels, warnings and palcards.
Miscellaneous Correction
Corrective Action Required
11/08/2018

Emergency shut-off switch ACTION REQUIRED:(verified at inspection) Intall the emergency shut off switch for the fuel dispensing areaaccording to the requirements listed. IFC 2012 2303.2 Emergency disconnect switches. An approved, clearly identified and readily accessible emergency disconnect switch shall be provided at an approved location to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. An emergency disconnect switch for exterior fuel dispensers shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations, the emergency disconnect switch shall be installed at an approved location. Such devices shall be distinctly labeled as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations.
Material safety and data sheets
Corrective Action Required
11/08/2018

2012 IFC 407.2- Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be readily available on the premises. ACTION REQUIRED:(information purposes) A Hazardous Materials Permit will be required in order for the fuel tank to be located on the premises. The Haz-Mat permit can be obtained through the Fire Department.
Miscellaneous Correction
Corrective Action Required
11/08/2018

Private Fire hydrant ACTION REQUIRED: (verified at inspection) The top bonnet portion of the private fire hydrant shall be painted (silver) to designate a private fire hydrant
Miscellaneous Correction
Corrective Action Required
11/08/2018

Signs ACTION REQUIRED:(verified at inspection) Establish a fire lane for the access roadway to the rear of the building. IFC 2012 D103.6 Signs. Where required by the fire code official, fire apparatus access roads shall be marked with permanent NO PARKING—FIRE LANE signs complying with Figure D103.6. Signs shall have a minimum dimension of 12 inches (305 mm) wide by 18 inches (457 mm) high and have red letters on a white reflective background. Signs shall be posted on one or both sides of the fire apparatus road as required by Section D103.6.1 or D103.6.2
Building Plan Review Approved with Conditions 11/15/2018 11/08/2018
Joe Frogge
Final Development Plan
Resolved
12/04/2018

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes. 11/8/18 - not addressed
License Tax Application
Corrective Action Required
11/08/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 11/8/18 - not addressed
Miscellaneous Correction
Corrective Action Required
11/08/2018

Design for retaining wall not found in submittal. Action required: Provide retaining wall design or request deferral. 11/8/18 - deferred per request
Screening - Ground mounted equipment
Resolved
11/08/2018

Unified Development Ordinance Article 7, Section 7.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section.
Bldg - Common path of egress travel 1014.3
Resolved
11/08/2018

2012 IBC 1014.3 – Common path of egress travel. The common path of egress travel shall not exceed the common path of egress travel distances in Table 1014.3. Actions required (2): - Modify mezzanine plan to show common path measurement at right angles. (will be compliant as 100' will be allowed) - Modify design where common path of travel is exceeded from Gym/Office 109 and Jeff's Office 117.
Accessibility - Vertical clearance 307.4
Resolved
11/08/2018

ICC A117.1-2009 Section 307.4 Vertical Clearance. Vertical clearance shall be 80 inches minimum. Rails or other barriers shall be provided where the vertical clearance is less than 80 inches. The leading edge of such rails or barrier shall be located 27 inches maximum above the floor. Action required: Provide blocking, guards, or other approved method to comply at area under stairs.
Engineered truss package
Corrective Action Required
11/08/2018

Copies of the pre-engineered metal building package were not provided at the time of permit application. Action required: Provide metal building package or request deferral. 11/8/18 - deferred per request
Accessibility - Dining surface height 902.4
Resolved
11/08/2018

ICC A117.1-2009 Section 902.4 Height. The tops of dining surfaces and work surfaces shall be 28 inches minimum and 34 inches maximum in height above the floor. Action required: Provide accessible portions of dining surfaces in break rooms.
Bldg - Toilet room wall finish 1210.2.2
Resolved
11/08/2018

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant wall finish materials at mop sink.
Mech - Condensate disposal - Evaporators and cooling coils 307.2
Resolved
11/08/2018

2012 IMC 307.2.1 Condensate disposal. Condensate from all cooling coils and evaporators shall be conveyed from the drain pan outlet to an approved place of disposal. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than one-eighth unit vertical in 12 units horizontal. Condensate shall not discharge into a street, alley or other areas so as to cause a nuisance. Action required: Specify condensate drain terminations at furnaces.
Miscellaneous Correction
Resolved
11/08/2018

2011 NEC Article 500.1 Scope – Articles 500 Through 504. Articles 500 through 504 cover the requirements for electrical and electronic equipment and wiring for all voltages in Class I, Divisions 1 and 2; Class II, Divisions 1 and 2; and Class III, Divisions 1 and 2 locations where fire or explosion hazards may exist due to flammable gases, flammable liquid-produces vapors, combustible liquid-produced vapors, combustible liquid-produced vapors, combustible dusts, or ignitable fibers/flyings. (see code for additional information and specific requirements) Action required: Specify compliant electrical design at fuel tank.
Licensed Contractors Approved 11/08/2018 11/08/2018
Joe Frogge
Special Inspections Review Approved 05/01/2019 11/08/2018
Joe Frogge
Building Plan Review Rejected 11/09/2018 11/02/2018
Joe Frogge
Final Development Plan
Corrective Action Required
11/02/2018

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
License Tax Application
Corrective Action Required
11/02/2018

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Miscellaneous Correction
Resolved
11/08/2018

2012 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
Miscellaneous Correction
Corrective Action Required
11/02/2018

Design for retaining wall not found in submittal. Action required: Provide retaining wall design or request deferral.
Screening - Ground mounted equipment
Corrective Action Required
11/02/2018

Unified Development Ordinance Article 7, Section 7.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened per referenced UDO section.
Bldg - Common path of egress travel 1014.3
Corrective Action Required
11/02/2018

2012 IBC 1014.3 – Common path of egress travel. The common path of egress travel shall not exceed the common path of egress travel distances in Table 1014.3. Actions required (2): - Modify mezzanine plan to show common path measurement at right angles. (will be compliant as 100' will be allowed) - Modify design where common path of travel is exceeded from Gym/Office 109 and Jeff's Office 117.
Accessibility - Vertical clearance 307.4
Corrective Action Required
11/02/2018

ICC A117.1-2009 Section 307.4 Vertical Clearance. Vertical clearance shall be 80 inches minimum. Rails or other barriers shall be provided where the vertical clearance is less than 80 inches. The leading edge of such rails or barrier shall be located 27 inches maximum above the floor. Action required: Provide blocking, guards, or other approved method to comply at area under stairs.
Engineered truss package
Corrective Action Required
11/02/2018

Copies of the pre-engineered metal building package were not provided at the time of permit application. Action required: Provide metal building package or request deferral.
Accessibility - Dining surface height 902.4
Corrective Action Required
11/02/2018

ICC A117.1-2009 Section 902.4 Height. The tops of dining surfaces and work surfaces shall be 28 inches minimum and 34 inches maximum in height above the floor. Action required: Provide accessible portions of dining surfaces in break rooms.
Bldg - Toilet room wall finish 1210.2.2
Corrective Action Required
11/02/2018

2012 IBC 1210.2.2 – Walls and partitions. Walls and partitions with 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Specify compliant wall finish materials at mop sink.
Miscellaneous Correction
Resolved
11/06/2018

2012 IMC 501.3.1 Location of exhaust outlets. The termination point of exhaust outlets and ducts discharging to the outdoors shall be located with the following minimum distances: (see code for items 1, 2, 4, & 5) 3. For all environmental air exhaust: 3 feet from property lines; 3 feet from operable openings into building for all occupancies other than Group U, and 10 feet from mechanical air intakes. Such exhaust shall not be considered hazardous or noxious. Action required: Modify design to provide minimum 10' clearance between exhaust fan and furnace combustion air intakes.
Mech - Condensate disposal - Evaporators and cooling coils 307.2
Corrective Action Required
11/02/2018

2012 IMC 307.2.1 Condensate disposal. Condensate from all cooling coils and evaporators shall be conveyed from the drain pan outlet to an approved place of disposal. Such piping shall maintain a minimum horizontal slope in the direction of discharge of not less than one-eighth unit vertical in 12 units horizontal. Condensate shall not discharge into a street, alley or other areas so as to cause a nuisance. Action required: Specify condensate drain terminations at furnaces.
Miscellaneous Correction
Corrective Action Required
11/02/2018

2011 NEC Article 500.1 Scope – Articles 500 Through 504. Articles 500 through 504 cover the requirements for electrical and electronic equipment and wiring for all voltages in Class I, Divisions 1 and 2; Class II, Divisions 1 and 2; and Class III, Divisions 1 and 2 locations where fire or explosion hazards may exist due to flammable gases, flammable liquid-produces vapors, combustible liquid-produced vapors, combustible liquid-produced vapors, combustible dusts, or ignitable fibers/flyings. (see code for additional information and specific requirements) Action required: Specify compliant electrical design at fuel tank.
Fire Plan Review Rejected 11/09/2018 11/01/2018
Joe Dir
Address numbers required
Corrective Action Required
11/01/2018

2012 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). ACTION REQUIRED: (verified at inspection) Building address (2320) shall be readable from the roadway (Independence Ave.)
Installation acceptance testing
Corrective Action Required
11/01/2018

2012 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. ACTION REQUIRED: (information purposes) Acceptance testing of the fire alarm system will be required prior to the final occupancy inspection.
Portable fire extinguishers - general
Corrective Action Required
11/01/2018

2012 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ACTION REQUIRED: (verified at inspection) Provide a minimum of one 2A-10BC (5 pound) fire extinguisher for every 3,000 square feet of useable space. the extinguishers shall be mounted on walls or in extinguisher cabinets on a normal path of travel close to exits.
Miscellaneous Correction
Corrective Action Required
11/01/2018

General fire protection and life safety requirements. ACTION REQUIRED: IFC 2012 3206.2 Extent and type of protection. Where required by Table 3206.2, fire detection systems, smoke and heat removal, draft curtains and automatic sprinkler design densities shall extend the lesser of 15 feet (4572 mm) beyond the high-piled storage area or to a permanent partition. Where portions of high-piled storage areas have different fire protection requirements because of commodity, method of storage or storage height, the fire protection features required by Table 3206.2 within this area shall be based on the most restrictive design requirements. ACTION REQUIRED: Reference IFC table 3206.2 Option-2 of class I-IV commodity and provide information on how the requirements will be met. ACTION REQUIRED: IFC 2012 3206.7 Smoke and heat removal. Where smoke and heat removal are required by Table 3206.2, smoke and heat vents shall be provided in accordance with Section 910. Where draft curtains are required by Table 3206.2, they shall be provided in accordance with Section 910.3.5.
Miscellaneous Correction
Corrective Action Required
11/01/2018

Duct detection ACTION REQUIRED: Duct detection shall comply with the IFC 2012 code requirements. Reference section IFC 2012 907.3.1 Duct smoke detectors.
Misc
Corrective Action Required
11/01/2018

Door hardware ACTION REQUIRED: Correction needed for the following doors and hardware. Panic hardware needed for warehouse (door 05) Panic hardware not required for IT room (door 07) Panic hardware for entry (door 06) if door 06 is to be secured no keyed locks on the egress side of an exit. IFC 2012 1008.1.9 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Locks on gates or barriers
Corrective Action Required
11/01/2018

2012 IFC 506.1.1-Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official. ACTION REQUIRED: An electronic controlled gate will require a (knox key switch), a chained gate will require a (knox padlock). Padlock or key switch can be obtained on line at knoxbox.com
Hazardous material identification
Corrective Action Required
11/01/2018

2012 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. ACTION REQUIRED: (verified at inspection) Fuel tank shall be clearly labeled and marked with all appropriate labels, warnings and palcards.
Miscellaneous Correction
Corrective Action Required
11/01/2018

Emergency shut-off switch ACTION REQUIRED: Show the location of the emergency shut off switch for the fuel dispensing area. IFC 2012 2303.2 Emergency disconnect switches. An approved, clearly identified and readily accessible emergency disconnect switch shall be provided at an approved location to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. An emergency disconnect switch for exterior fuel dispensers shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations, the emergency disconnect switch shall be installed at an approved location. Such devices shall be distinctly labeled as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations.
Material safety and data sheets
Corrective Action Required
11/01/2018

2012 IFC 407.2- Material Safety Data Sheets. Material Safety Data Sheets (MSDS) for all hazardous materials shall be readily available on the premises. ACTION REQUIRED:(information purposes) A Hazardous Materials Permit will be required in order for the fuel tank to be located on the premises. The Haz-Mat permit can be obtained through the Fire Department.
Miscellaneous Correction
Corrective Action Required
11/01/2018

Private Fire hydrant ACTION REQUIRED: (verified at inspection) The top bonnet portion of the private fire hydrant shall be painted (silver) to designate a private fire hydrant
Miscellaneous Correction
Corrective Action Required
11/02/2018

Signs ACTION REQUIRED: Establish a fire lane for the access roadway to the rear of the building. IFC 2012 D103.6 Signs. Where required by the fire code official, fire apparatus access roads shall be marked with permanent NO PARKING—FIRE LANE signs complying with Figure D103.6. Signs shall have a minimum dimension of 12 inches (305 mm) wide by 18 inches (457 mm) high and have red letters on a white reflective background. Signs shall be posted on one or both sides of the fire apparatus road as required by Section D103.6.1 or D103.6.2
Licensed Contractors Approved 11/07/2018 10/29/2018
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $4,409.32 $4,409.32 Paid 11/28/2018
8331506-EFHB Maybrook, Full $553.93 $553.93 Paid 11/28/2018
8331507-Sewer Connection Fee $390.00 $390.00 Paid 11/28/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Failed 4/3/2019 (10:00) 4/3/2019 at 9:50 AM 04/03/2019
Misc
Corrective Action Required
04/03/2019
RE-BAR AT INTEGRAL COLUMN FOOTINGS NOT AT LENGTHS PER SHOP DRAWINGS. 3" MIN CLEARANCE PER ACI NOT PROVIDED AT TRENCH BOTTOMS AND BANKS.
Footing Inspection - Commercial Partial 4/3/2019 at 1:25 PM 04/03/2019
Misc
Partial Correction
04/03/2019
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: 1/D.8 TO 1/A TO A/4.7;
Footing Inspection - Commercial Partial 4/5/2019 4/5/2019 at 11:10 AM 04/05/2019
Misc
Partial Correction
04/03/2019
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: 1/D.8 TO 1/A TO A/4.7; A/4.7 TO A/6 TO D/6 TO D/4.2
Footing Inspection - Commercial Passed 4/8/2019 (1:00) 4/8/2019 at 1:15 PM 04/08/2019
Misc
Resolved
04/08/2019
OK TO POUR WHEN READY SECTIONS OF CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS AS FOLLOWS: 1/D.8 TO 1/A TO A/4.7; A/4.7 TO A/6 TO D/6 TO D/4.2
Underslab Electrical Inspection - Commercial Passed 4/11/2019 04/11/2019
Underslab Plumbing Inspection - Commercial Passed 4/11/2019 4/11/2019 at 2:40 PM 04/11/2019
Rough Framing Inspection - Commercial Partial 6/21/2019 6/21/2019 at 1:50 PM 06/21/2019
Misc
Partial Correction
06/21/2019
-INSPECTED FRAMING OF FRONT EXTERIOR WALL. ANCHOR OF BOTTOM TRACK NOT ANCHORED W/ 1/2" BOLT EMBEDDED MIN 3". THE REST FRAMED PER PLAN
In-wall Inspection Failed 7/19/2019 7/19/2019 at 1:50 PM 07/19/2019
Misc
Corrective Action Required
07/19/2019
IN-WALL PLUMBING NOT READY FOR INSPECTION. JB PROVIDED COURTESY OBSERVATIONS SOUTH & EAST OF DEMISING WALL - BUT NO FORMAL INSPECTION PRESENTLY.
In-wall Inspection Passed 7/23/2019 7/23/2019 at 3:00 PM 07/23/2019
Misc
Resolved
07/23/2019
IN-WALL PLUMBING NOT READY FOR INSPECTION. JB PROVIDED COURTESY OBSERVATIONS SOUTH & EAST OF DEMISING WALL - BUT NO FORMAL INSPECTION PRESENTLY.
Electrical Service Inspection Passed 7/31/2019 7/31/2019 at 4:25 PM 07/31/2019
Above Ceiling Inspection Partial 8/27/2019 8/27/2019 at 3:00 PM 08/27/2019
Misc
Partial Correction
08/27/2019
ABOVE-CEILING-OK TO COVER: -LIGHT SOFFIT ABOVE RECEPTION
Above Ceiling Inspection Passed 9/6/2019 9/6/2019 at 2:15 PM 09/06/2019
Misc
Partial Correction
08/27/2019
ABOVE-CEILING-OK TO COVER: -LIGHT SOFFIT ABOVE RECEPTION
Underground Electrical Inspection - Commercial Failed 9/10/2019 9/10/2019 at 8:30 AM 09/10/2019
Misc
Corrective Action Required
09/10/2019
POLE BASE HOLE DUG TOO SMALL FOR RE-BAR CAGE. 3" MINIMUM CLEARANCE NOT PROVIDED.
Underground Electrical Inspection - Commercial Failed 9/10/2019 9/10/2019 at 10:35 AM 09/10/2019
Misc
Corrective Action Required
09/10/2019
POLE BASE HOLE DUG 5' DEEP; DRAWING CALLS FOR 6'
Occupancy Inspection - Fire Partial 9/11/2019 9/11/2019 09/11/2019
Alarm Test Partial 9/11/2019 09/11/2019
Rough Framing Inspection - Commercial Passed 09/11/2019
Misc
Resolved
09/11/2019
-INSPECTED FRAMING OF FRONT EXTERIOR WALL. ANCHOR OF BOTTOM TRACK NOT ANCHORED W/ 1/2" BOLT EMBEDDED MIN 3". THE REST FRAMED PER PLAN
Occupancy Inspection - Codes Commercial Failed 9/11/2019 9/11/2019 at 2:05 PM 09/11/2019
Informational
09/11/2019
-NOT READY FOR INSPECTION. GAS PIPING, MECHANICAL NOT COMPLETED. -WALKED THROUGH THE BUILDING. BUILDING IS OK TO STOCK ITEMS BUT DO NOT OCCUPY.
Occupancy Inspection - Engineering Temporary C of O 9/20/2019 09/13/2019
Gas Service Inspection - Commercial Passed 9/13/2019 9/13/2019 at 1:20 PM 09/13/2019
Gas Piping Inspection - Commercial Passed 9/13/2019 09/13/2019
Occupancy Inspection - Water Utilities Passed 9/20/2019 09/20/2019
Underground Electrical Inspection - Commercial Passed 09/20/2019
Misc
Resolved
09/20/2019
POLE BASE HOLE DUG 5' DEEP; DRAWING CALLS FOR 6'
Occupancy Inspection - Codes Commercial Temporary C of O 9/20/2019 at 1:25 PM 09/20/2019
Misc
Corrective Action Required
09/20/2019
-APPROVAL REQUIRED FROM: FIELD SERVICE AND FIRE -FUEL TANK AND DISPENSER NOT DONE -SUBMIT SPECIAL INSPECTION REPORT
Occupancy Inspection - Planning Passed 9/20/2019 09/20/2019
Occupancy Inspection - Fire Temporary C of O 9/20/2019 09/20/2019
Alarm Test Passed 9/20/2019 09/20/2019
Occupancy Inspection - Fire Passed 10/22/2019 10/22/2019
Occupancy Inspection - Codes Commercial Temporary C of O 10/22/2019 at 2:35 PM 10/22/2019
Misc
Corrective Action Required
09/20/2019
-FUEL TANK AND DISPENSER- SUPPORT RMC RACEWAY -SUBMIT SPECIAL INSPECTION REPORT
Occupancy Inspection - Engineering Temporary C of O 9/20/2019 9/20/2019 10/22/2019
Occupancy Inspection - Engineering Passed 11/04/2019
Occupancy Inspection - Codes Commercial Full C of O 11/27/2019 11/27/2019
Misc
Resolved
11/27/2019
-FUEL TANK AND DISPENSER- SUPPORT RMC RACEWAY -SUBMIT SPECIAL INSPECTION REPORT
Documents & Images
Date Uploaded File Type Document Name
11/02/2018 Letter Fire Building Plan Review
11/02/2018 Letter Codes P/R Corrections Document
11/08/2018 Special Inspection Intent Letter
11/12/2018 Letter Fire Building Plan Review
11/28/2018 Receipt Receipt for transaction: 2018-007374
12/04/2018 Letter Codes Plan Review Conditions
12/04/2018 Letter Codes Building Permit
01/10/2019 faa 7460 approval
04/03/2019 Letter INSPECTION SUMMARY
04/03/2019 Letter INSPECTION SUMMARY
04/05/2019 Letter INSPECTION SUMMARY
04/08/2019 Letter INSPECTION SUMMARY
04/09/2019 Letter Fire (Alarm) Plan Review Notice
04/11/2019 Letter INSPECTION SUMMARY
04/11/2019 Letter INSPECTION SUMMARY
05/06/2019 Letter Fire Building Plan Review
06/21/2019 Letter INSPECTION SUMMARY
07/19/2019 Letter INSPECTION SUMMARY
07/23/2019 Letter INSPECTION SUMMARY
07/31/2019 Letter INSPECTION SUMMARY
08/27/2019 Letter INSPECTION SUMMARY
09/06/2019 Letter INSPECTION SUMMARY
09/11/2019 Letter INSPECTION SUMMARY
09/11/2019 Letter INSPECTION SUMMARY
09/13/2019 Letter INSPECTION SUMMARY
09/13/2019 Letter INSPECTION SUMMARY
09/20/2019 Letter INSPECTION SUMMARY
09/20/2019 Letter Codes Temporary Certificate of Occupancy
10/22/2019 Letter Codes Temporary Certificate of Occupancy
11/27/2019 special inspections letter
11/27/2019 Letter Codes Final Certificate of Occupancy
11/27/2019 Letter Field Certificate of Occupancy
12/02/2019 Letter Codes Final Certificate of Occupancy
12/02/2019 Engineer Report/Study FINAL 3RD PARTY INSPECTION LETTER
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home