Permit Application Status

PRCOM20130393


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20130393
Building Permit - Commercial
Certificate of Occupancy
DACUR INVESTMENT COMPANY INC
NEW COMMERCIAL
RESTAURANT
03/14/2013
06/11/2013
11/01/2014
05/01/2014
Locations
Contacts
ACCEL CONSTRUCTION LLC, Address:4015 N. WOODLAWN CT, SUITE 1, Phone:(316) 866-2885  
MCDANIEL FURNACE & SHEET METAL, Address:2905 S M 291 FRONTAGE RD, Phone:(816) 373-6370  
ELECTRI-TECH, Address:11828 E LEWIS CT, Phone:(316) 683-2841  
LADD PLUMBING, Address:19304 E 255TH ST, Phone:(816) 380-2698  
BRR ARCHITECTURE, Address:6700 ANTIOCH PLAZA SUITE 300, Phone:(913) 236-3385  
DACUR INVESTMENT COMPANY INC, Address:2700 KENDALLWOOD PKWY # 208  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 10/07/2013
Brian Austerman
Misc
Corrective Action Required
10/07/2013

Plans show FDC as single 2 1/2 connection. FDC shall be a single 4"Storts type, verified at inspection and testing
Installation acceptance testing
Corrective Action Required
10/07/2013

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule hydrostatic and flow testing
Alarm Plan Review Released for Construction 07/15/2013
Brian Austerman
Misc
Corrective Action Required
07/15/2013

Move outside horn strobe to over the fire department connection, this is on the corner by the utility room. Verified at inspection
Misc
Corrective Action Required
07/15/2013

Duct detection to shut down the unit and transmit a supervisory signal to the panel. Verified at testing
Misc
Corrective Action Required
07/15/2013

Manual pulls for the hood systems shall be no closer than 10' and no further than 20'. Location to be verified at testing
Installation acceptance testing
Corrective Action Required
07/15/2013

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule alarm testing in coordination with flow testing
Fire Plan Review Approved 04/24/2013 06/25/2013
Brian Austerman
Type I hood - Where required
Corrective Action Required
06/25/2013

2006 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Fryer #34 needs a type 1 protected hood, not shown on plans. Per a phone conversation with Bill (Hockenbergs Design) this hood is part of a 6 gallon shared system, both hoods are activated with the manual pull. Verified on inspection 4/23/2013- PROVIDE PLANS FOR BOTH TYPE 1 HOODS
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
06/25/2013

2006 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Place K class under the manual release for the hood systems along with instructions. Verified at inspection ADDRESSED IN RESUB
Knox box required
Corrective Action Required
06/25/2013

2006 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Call 816.969.1316 to obtain a knox box application. Knox box is to be located underneath the outside horn strobe ADDRESSED IN RESUB
Construction documents - Fire protection systems
Corrective Action Required
06/25/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval
Construction documents for fire alarm systems
Corrective Action Required
06/25/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval
Misc
Corrective Action Required
06/25/2013

904.11.1 Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area a minimum of 10 feet (3048 mm) and a maximum of 20 feet (6096 mm) from the kitchen exhaust system. The manual actuation device shall be installed not more than 48 inches (1200 mm) nor less than 42 inches (1067 mm) above the floor and shall clearly identify the hazard protected. The manual actuation shall require a maximum force of 40 pounds (178 N) and a maximum movement of 14 inches (356 mm) to actuate the fire suppression system. SHOW LOCATION FOR MANUAL PULL FOR KITCHEN HOODS. THIS IS A SHARED SYSTEM, LOCATE MANUAL PULL ACCORDING TO DISTANCE REQUIREMENTS LISTED ABOVE
Licensed Contractors Approved 06/28/2013 06/05/2013
Codes Admin
Business License
Corrective Action Required
04/02/2013

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required - Provide the name of the licensed general contractor for the project. A minimum of a Class B license is required. This information is required prior to permit approval.
License contractors
Corrective Action Required
04/02/2013

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the licensed mechanical, electrical and plumbing contractors for the project. This information is required for permit approval.
Final Development Plan Review Approved 05/31/2013 05/21/2013
Mike Weisenborn
Building Plan Review Approved with Conditions 04/24/2013 04/24/2013
Mike Weisenborn
Misc
Resolved
04/24/2013

Per the Lee's Summit Water Utilities Department, the existing water meter at this location is a one inch. I have included in the permit fee the cost of a new meter setup as they will not allow the existing setup to be reused. The tap fee is not being charged. The fittings provided are one inch and the service line coming out of the meter will need to one inch for a minimum of ten feet. At that time the service can transition to a larger size. Action required - This comment is for information purposes.
Plumb - Backflow general 608.3
Resolved
04/24/2013

2006 IPC 608.3 - Devices, appurtenances, appliances and apparatus. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to the water supply system, shall be provided with protection against backflow and contamination of the water supply system. Water pumps, filters, softeners, tanks and all other appliances and devices that handle or treat potable water shall be protected against contamination. Action required - Note 15 on Sheet P102 indicates a backflow preventer is to be installed on the tea brewer but not the ice machine. Make needed corrections.
Misc
Resolved
04/24/2013

The Lee's Summit Water Department requires a dougle check valve assembly on irrigation systems. Action required - Make needed corrections.
Fire Plan Review Approved with Conditions 04/24/2013 04/23/2013
Brian Austerman
Type I hood - Where required
Corrective Action Required
04/18/2013

2006 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Fryer #34 needs a type 1 protected hood, not shown on plans. Per a phone conversation with Bill (Hockenbergs Design) this hood is part of a 6 gallon shared system, both hoods are activated with the manual pull. Verified on inspection 4/23/2013- PROVIDE PLANS FOR BOTH TYPE 1 HOODS
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
04/18/2013

2006 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Place K class under the manual release for the hood systems along with instructions. Verified at inspection ADDRESSED IN RESUB
Knox box required
Corrective Action Required
04/18/2013

2006 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Call 816.969.1316 to obtain a knox box application. Knox box is to be located underneath the outside horn strobe ADDRESSED IN RESUB
Construction documents - Fire protection systems
Corrective Action Required
04/18/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval
Construction documents for fire alarm systems
Corrective Action Required
04/18/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval
Misc
Corrective Action Required
04/23/2013

904.11.1 Manual system operation. A manual actuation device shall be located at or near a means of egress from the cooking area a minimum of 10 feet (3048 mm) and a maximum of 20 feet (6096 mm) from the kitchen exhaust system. The manual actuation device shall be installed not more than 48 inches (1200 mm) nor less than 42 inches (1067 mm) above the floor and shall clearly identify the hazard protected. The manual actuation shall require a maximum force of 40 pounds (178 N) and a maximum movement of 14 inches (356 mm) to actuate the fire suppression system. SHOW LOCATION FOR MANUAL PULL FOR KITCHEN HOODS. THIS IS A SHARED SYSTEM, LOCATE MANUAL PULL ACCORDING TO DISTANCE REQUIREMENTS LISTED ABOVE
Building Plan Review Rejected 04/04/2013 04/04/2013
Mike Weisenborn
Misc
Corrective Action Required
04/02/2013

Per the Lee's Summit Water Utilities Department, the existing water meter at this location is a one inch. I have included in the permit fee the cost of a new meter setup as they will not allow the existing setup to be reused. The tap fee is not being charged. The fittings provided are one inch and the service line coming out of the meter will need to one inch for a minimum of ten feet. At that time the service can transition to a larger size. Action required - This comment is for information purposes.
Plumb - Backflow general 608.3
Corrective Action Required
04/04/2013

2006 IPC 608.3 - Devices, appurtenances, appliances and apparatus. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to the water supply system, shall be provided with protection against backflow and contamination of the water supply system. Water pumps, filters, softeners, tanks and all other appliances and devices that handle or treat potable water shall be protected against contamination. Action required - Note 15 on Sheet P102 indicates a backflow preventer is to be installed on the tea brewer but not the ice machine. Make needed corrections.
Misc
Corrective Action Required
04/04/2013

The Lee's Summit Water Department requires a dougle check valve assembly on irrigation systems. Action required - Make needed corrections.
Fire Plan Review Approved with Conditions 03/28/2013 03/21/2013
Brian Austerman
Type I hood - Where required
Corrective Action Required
03/21/2013

2006 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Fryer #34 needs a type 1 protected hood, not shown on plans. Per a phone conversation with Bill (Hockenbergs Design) this hood is part of a 6 gallon shared system, both hoods are activated with the manual pull. Verified on inspection
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
03/21/2013

2006 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Place K class under the manual release for the hood systems along with instructions. Verified at inspection
Knox box required
Corrective Action Required
03/21/2013

2006 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Call 816.969.1316 to obtain a knox box application. Knox box is to be located underneath the outside horn strobe
Construction documents - Fire protection systems
Corrective Action Required
03/21/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide sprinkler plans for approval
Construction documents for fire alarm systems
Corrective Action Required
03/21/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide alarm plans for approval
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $5,054.00 $5,054.00 Paid 06/11/2013
$5,054.00
8331507-Sewer Connection Fee $30.00 $30.00 Paid 06/11/2013
$30.00
8350015-Water Meter Fee $458.91 $458.91 Paid 06/11/2013
$458.91
9110079-After Hours Inspection (Building Codes)(Per Hour) $90.06 $90.06 Paid 07/22/2013
$90.06
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Not Ready 7/19/2013 (3:30) 7/19/2013 at 12:00 AM 07/19/2013
Footing Inspection - Commercial Partial 7/20/2013 at 12:00 AM 07/21/2013
Misc
Partial Correction
07/21/2013
OK TO POUR WHEN READY CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS
Underslab Plumbing Inspection - Commercial Partial 8/2/2013 at 12:00 AM 08/02/2013
Misc
Partial Correction
08/02/2013
PIPE SIZE FOR TWO F.D.'s AT WEST END NOT PER DRAWING.
Underslab Plumbing Inspection - Commercial Partial 8/2/2013 at 12:00 AM 08/02/2013
Misc
Partial Correction
08/02/2013
PIPE SIZE FOR TWO F.D.'s AT WEST END NOT PER DRAWING. SEE RED-CIRCILED ON PERMIT DRAWING.
Underslab Electrical Inspection - Commercial Passed 8/27/2013 8/27/2013 at 12:00 AM 08/27/2013
Underslab Plumbing Inspection - Commercial Passed 8/27/2013 8/27/2013 at 12:00 AM 08/27/2013
Misc
Resolved
08/27/2013
PIPE SIZE FOR TWO F.D.'s AT WEST END NOT PER DRAWING. SEE RED-CIRCILED ON PERMIT DRAWING.
Water Service Inspection Partial 8/27/2013 at 12:00 AM 08/27/2013
Misc
Partial Correction
08/27/2013
OK TO COVER WHEN READY DOMESTIC WATER SERVICE LINE FROM BUILDING ENTRY TO 15' WEST. COPPER OR PEX OK
Footing Inspection - Commercial Partial 8/30/2013 at 12:00 AM 08/30/2013
Misc
Partial Correction
08/21/2013
OK TO POUR WHEN READY CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS
Misc
Partial Correction
08/30/2013
OK TO POUR WHEN READY ISOLATED COLUMN FOOTING AT C/2.
Footing Inspection - Commercial Not Ready 9/11/2013 (1:45) 9/11/2013 at 12:00 AM 09/11/2013
Misc
Partial Correction
08/30/2013
OK TO POUR WHEN READY CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS
Misc
Partial Correction
08/30/2013
OK TO POUR WHEN READY ISOLATED COLUMN FOOTINGS AT: C/2; CANOPY FOOTINGS NOT READY FOR INSPECTION 9/11/13
Footing Inspection - Commercial Partial 9/12/2013 at 12:00 AM 09/12/2013
Misc
Partial Correction
09/11/2013
OK TO POUR WHEN READY CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS
Misc
Partial Correction
09/11/2013
OK TO POUR WHEN READY ISOLATED COLUMN FOOTINGS AT: C/2; TWO F4 CANOPY FOOTINGS OK TO POUR AFTER RE-BAR IS CHAIRED-UP FOR 3" CLEARANCE FROM BOTTOM OF EXCAVATION
Hood/Duct Inspection Partial 10/16/2013 (8:00 to 5:00) 10/16/2013 at 12:00 AM 10/16/2013
Misc
Partial Correction
10/16/2013
IMC 506 COMMERCIAL KITCHEN GREASE DUCT FABRICATION & INSTALLATION: LIGHT TEST OF SHOP WELDS APPROVED;
Hood/Duct Inspection Partial 10/17/2013 10/17/2013 at 12:00 AM 10/17/2013
Misc
Partial Correction
10/16/2013
IMC 506 COMMERCIAL KITCHEN GREASE DUCT FABRICATION & INSTALLATION: LIGHT TEST OF SHOP WELDS APPROVED; LIGHT TEST OF FIELD WELDS APPROVED. G.C. TO WITNESS INSTALLATION OF 1ST LAYER OF WRAP. 2ND WRAP SUBJECT TO APPROVAL AT OR BEFORE ABOVE-CEILING INSPECTION.
Misc
Corrective Action Required
10/17/2013
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBBS-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE; SMOKE CAPTURE TEST TO BE WITNESSED BY INSPECTOR BEFORE ANY OCCUPANCY IS APPROVED.
Rough Framing Inspection - Commercial Partial 10/17/2013 10/17/2013 at 12:00 AM 10/17/2013
Misc
Partial Correction
10/17/2013
FASTENER PATTERN ON SW1 SHEAR WALL SHEATHING APROVED.
Rough Framing Inspection - Commercial Partial 10/28/2013 10/28/2013 at 12:00 AM 10/28/2013
Misc
Partial Correction
10/17/2013
FASTENER PATTERN ON SW1 SHEAR WALL SHEATHING APROVED. -TIE DOWN ANCHORS INSTALLED FOR SHEAR WALLS
In-wall Inspection Partial 10/28/2013 10/28/2013 at 12:00 AM 10/28/2013
Misc
Partial Correction
01/10/2014
-FIREBLOCK ALL CONCEALED FURRED OUT WALL SPACES AROUND THE BUILDING PERIMETER AT CEILING LEVEL
Above Ceiling Inspection Partial 10/31/2013 at 12:00 AM 10/31/2013
Misc
Partial Correction
10/31/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: NE ROOM + RESTROOMS OK EXCEPT SPRINKLER DROPS YET TO BE PIPED
Above Ceiling Inspection Partial 11/1/2013 at 12:00 AM 11/01/2013
Misc
Partial Correction
10/31/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 100 VESTIBULE + 105 & 106 RESTROOMS OK EXCEPT SPRINKLER DROPS YET TO BE PIPED
Rough Framing Inspection - Commercial Partial 11/5/2013 11/5/2013 at 12:00 AM 11/05/2013
Misc
Partial Correction
10/28/2013
FASTENER PATTERN ON SW1 SHEAR WALL SHEATHING APROVED. -TIE DOWN ANCHORS INSTALLED FOR SHEAR WALLS - HOOD WALL CHANGED TO METAL STUDS OK TO COVER
Gas Piping Inspection - Commercial Not Ready 11/11/2013 11/11/2013 at 12:00 AM 11/11/2013
Misc
Corrective Action Required
11/11/2013
IFGC 407; 415: 8' PROTECTION OF ROOF MEMBRANE UNDER WOODEN PIPING SUPPORT BLOCKS FOR GAS PIPING: COMPLY WITH MAXIMUM SUPPORT SPACING PER IFGC. USE WEATHER-RESISTANT BLOCKING MATERIAL PROVIDING SOLID SUPPORT UNDER PIPE. LOOSE-CLAMP BLOCKS TO PIPE. APPLY SPECIFIED / APPROVED, ROOF-COMPATIBLE SLIP SHEET TO UNDERSIDE OF BLOCKS WITH METAL FASTENERS AT SIDES OF BLOCKS.
Misc
Corrective Action Required
11/11/2013
IFGC 404.8: EXPOSED METALLIC PIPING MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS.
Misc
Corrective Action Required
11/11/2013
PIPING INSIDE BUILDING NOT YET COMPLETED. SUBSEQUENT INSPECTION AND PRESSURE TEST WILL BE REQUIRED WHEN PIPING IS COMPLETED.
Gas Service Inspection - Commercial Passed 11/11/2013 11/11/2013 at 12:00 AM 11/11/2013
Underground Plumbing Inspection - Commercial Partial 8/2/2013 11/13/2013 at 12:00 AM 11/13/2013
Misc
Partial Correction
11/13/2013
GREASE INTERCEPTOR INSTALLED. PIPING IN PROGRESS. NO ISSUES TO DATE.
Underground Plumbing Inspection - Commercial Passed 11/14/2013 11/14/2013 at 12:00 AM 11/14/2013
Misc
Resolved
11/14/2013
GREASE INTERCEPTOR INSTALLED. PIPING IN PROGRESS. NO ISSUES TO DATE.
Electrical Service Inspection Passed 11/14/2013 11/14/2013 at 12:00 AM 11/14/2013
Sewer Service Inspection Passed 11/15/2013 (8:15) 11/15/2013 at 12:00 AM 11/15/2013
Footing Inspection - Commercial Partial 11/18/2013 at 12:00 AM 11/18/2013
Misc
Resolved
11/18/2013
OK TO POUR WHEN READY CONCRETE GRADE BEAM + INTEGRAL COLUMN FOOTINGS
Misc
Resolved
11/18/2013
OK TO POUR WHEN READY ISOLATED COLUMN FOOTINGS AT: C/2; TWO F4 CANOPY FOOTINGS OK TO POUR AFTER RE-BAR IS CHAIRED-UP FOR 3" CLEARANCE FROM BOTTOM OF EXCAVATION
Misc
Partial Correction
11/18/2013
OK TO POUR WHEN READY GRADE BEAMS AND INTEGRAL PIERS FOR TRASH ENCLOSURE.
Above Ceiling Inspection Failed 12/2/2013 12/2/2013 at 12:00 AM 12/02/2013
Misc
Partial Correction
11/01/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 100 VESTIBULE + 105 & 106 RESTROOMS OK EXCEPT SPRINKLER DROPS YET TO BE PIPED
Misc
Corrective Action Required
12/02/2013
ACT CEILING FRAMING AND ABOVE-CEILING SYSTEMS: SEE ISSUES BELOW>>>
Misc
Corrective Action Required
12/02/2013
CEILING SUPPORT WIRES ARE TO SUPPORT ONLY CEILING SYSTEM; REMOVE AND INDEPENDENTLY SUPPORT ALL OTHER SYSTEMS E.G. MC ELECTRICAL CABLE
Misc
Corrective Action Required
12/02/2013
TIE WIRES AT LAY-IN ELECTRICAL LIGHTING LUMINAIRES: PROVIDE TWO SLACK WIRE TIES PER FIXTURE FROM STRUCTURE TO TWO OPPOSITE DIAGONAL CORNERS. TIE BOTH ENDS WITH TWO FULL WRAPS MINIMUM.
Misc
Corrective Action Required
12/02/2013
COMPLETE ALL SPRINLER FIRE PROTECTION PIPING AND DROPS
Misc
Corrective Action Required
12/02/2013
MC ELECT CABLE: - ENSURE SUPPORT AT 6' MAX INTERVALS - ENSURE SECURED WITHIN 12" OF ENTRY TO BOXES
Misc
Corrective Action Required
12/02/2013
COMPLETE MAKE-UP AND CLOSE ALL ELECT J.B.'S
Misc
Corrective Action Required
12/02/2013
PEX WATER TUBING: - ENSURE SUPPORT AT 32" MAX HORIZONTAL - ENSURE SECURED AT CEILING ELEVATION VERTICAL - WET PIPING MAY NOT RUN ABOVE ELECTRICAL PANELS
Above Ceiling Inspection Partial 12/4/2013 12/4/2013 at 12:00 AM 12/04/2013
Misc
Partial Correction
12/02/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 100 VESTIBULE + 105 & 106 RESTROOMS OK EXCEPT SPRINKLER DROPS YET TO BE PIPED
Misc
Corrective Action Required
12/02/2013
ACT CEILING FRAMING AND ABOVE-CEILING SYSTEMS: SEE ISSUES BELOW>>> OK TO INSTALL BORDERS ONLY AT FOLLOWING LOCATIONS: 107; 108; 109; 110; 114 E AND N ONLY
Misc
Corrective Action Required
12/02/2013
CEILING SUPPORT WIRES ARE TO SUPPORT ONLY CEILING SYSTEM; REMOVE AND INDEPENDENTLY SUPPORT ALL OTHER SYSTEMS E.G. MC ELECTRICAL CABLE
Misc
Corrective Action Required
12/02/2013
TIE WIRES AT LAY-IN ELECTRICAL LIGHTING LUMINAIRES: PROVIDE TWO SLACK WIRE TIES PER FIXTURE FROM STRUCTURE TO TWO OPPOSITE DIAGONAL CORNERS. TIE BOTH ENDS WITH TWO FULL WRAPS MINIMUM.
Misc
Corrective Action Required
12/02/2013
COMPLETE ALL SPRINLER FIRE PROTECTION PIPING AND DROPS
Misc
Corrective Action Required
12/02/2013
MC ELECT CABLE: - ENSURE SUPPORT AT 6' MAX INTERVALS - ENSURE SECURED WITHIN 12" OF ENTRY TO BOXES
Misc
Corrective Action Required
12/02/2013
COMPLETE MAKE-UP AND CLOSE ALL ELECT J.B.'S
Misc
Corrective Action Required
12/02/2013
PEX WATER TUBING: - ENSURE SUPPORT AT 32" MAX HORIZONTAL - ENSURE SECURED AT CEILING ELEVATION VERTICAL - WET PIPING MAY NOT RUN ABOVE ELECTRICAL PANELS
Above Ceiling Inspection Passed 12/5/2013 at 12:00 AM 12/05/2013
Misc
Resolved
12/05/2013
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 100 VESTIBULE + 105 & 106 RESTROOMS OK EXCEPT SPRINKLER DROPS YET TO BE PIPED
Misc
Resolved
12/05/2013
AFTER VERTICAL PEX TUBING RUNS ARE SECURE ABOVE CEILING OK TO COVER WHEN READY ACT CEILING FRAMING AND ABOVE-CEILING SYSTEMS
Misc
Resolved
12/05/2013
CEILING SUPPORT WIRES ARE TO SUPPORT ONLY CEILING SYSTEM; REMOVE AND INDEPENDENTLY SUPPORT ALL OTHER SYSTEMS E.G. MC ELECTRICAL CABLE
Misc
Resolved
12/05/2013
TIE WIRES AT LAY-IN ELECTRICAL LIGHTING LUMINAIRES: PROVIDE TWO SLACK WIRE TIES PER FIXTURE FROM STRUCTURE TO TWO OPPOSITE DIAGONAL CORNERS. TIE BOTH ENDS WITH TWO FULL WRAPS MINIMUM.
Misc
Resolved
12/05/2013
COMPLETE ALL SPRINLER FIRE PROTECTION PIPING AND DROPS
Misc
Resolved
12/05/2013
MC ELECT CABLE: - ENSURE SUPPORT AT 6' MAX INTERVALS - ENSURE SECURED WITHIN 12" OF ENTRY TO BOXES
Misc
Resolved
12/05/2013
COMPLETE MAKE-UP AND CLOSE ALL ELECT J.B.'S
Misc
Resolved
12/05/2013
PEX WATER TUBING: - ENSURE SUPPORT AT 32" MAX HORIZONTAL - ENSURE SECURED AT CEILING ELEVATION VERTICAL - WET PIPING MAY NOT RUN ABOVE ELECTRICAL PANELS
Sprinkler - Hydrostatic Test Passed 12/16/2013 at 9:00 AM 12/16/2013
Underground Electrical Inspection - Commercial Partial 12/20/2013 12/20/2013 at 12:00 AM 12/20/2013
Misc
Partial Correction
12/20/2013
OK TO COVER WHEN READY INSTALLATION OF BURIED ELECTRICAL CONDUIT FOLLOWING SEGMENTS: FROM NE CORNER OF BLDG TO J.B. AND TWO GROUND LUMINAIRES; FROM PRE-MENU BOARD TO TWO MENU BOARD LOCATIONS (SUBSTANTIALLY COVERED BUT TO BE PARTIALLY EXPOSED LATER WHEN MENU BOARDS ARE CONSTRUCTED)
Occupancy Inspection - Codes Commercial Not Ready 12/27/2013 12/27/2013 at 12:00 AM 12/27/2013
Misc
Corrective Action Required
12/27/2013
EXTERIOR OF BUILDING AND SITEWORK EXCLUDED FROM CURRENT FINAL INSPECTION. NOT READY FOR INSPECTION.
Misc
Corrective Action Required
12/27/2013
ROOFTOP SCUPPER AT SW CORNER OF BLDG DUMPING WATER ON ELECTRICAL SERVICE GEAR. MUST BE DIVERTED IMMEDIATELY.
Misc
Corrective Action Required
12/27/2013
RESOLVE FIRE DEPT ISSUES.
Misc
Corrective Action Required
12/27/2013
OBTAIN WATER DEPARTMENT APPROVAL.
Misc
Corrective Action Required
12/27/2013
OBTAIN PUBLIC WORKS DEPT APPROVAL.
Misc
Corrective Action Required
12/27/2013
OBTAIN PLANNING & DEVELOPMENT DEPT APPROVAL.
Misc
Corrective Action Required
12/27/2013
AFFIX "NO SMOKING" SIGN AT PUBLIC ENTRANCE(S).
Misc
Corrective Action Required
12/27/2013
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Misc
Corrective Action Required
12/27/2013
UNTERMINATED LIQUID-TIGHT ELECTRICAL CONDUCTORS HANGING AT EXTERIOR EAST & SOUTHEAST WALLS.
Misc
Corrective Action Required
12/27/2013
RESTROOMS NOT FULLY COMPLETED FOR FINAL INSPECTION. ENSURE ALL DIMENSIONS ARE PER ADA/ANSI.
Misc
Corrective Action Required
12/27/2013
IPC 608: BACKFLOW PREVENTION DEVICE REQUIRED AT POTABLE WATER-FED EQUIPMENT. AT CARBONATED BEVERAGE DISPENSING EQUIPMENT USE ASSE 1022 LISTED DEVICE.
Misc
Corrective Action Required
12/27/2013
VACUUM BREAKER REQUIRED AT THREADED HOSE CONNECTIONS.
Misc
Corrective Action Required
12/27/2013
NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES. SEE AT DINING AREA
Misc
Corrective Action Required
12/27/2013
APPARENT HOT/NEUTRAL REVERSE AT ELECT RECEPT LEFT OF CARBONATED BEVERAGE DISPENSER.
Misc
Corrective Action Required
12/27/2013
ENSURE FLOOR SINK IS COMPLETELY SEALED TO WALL.
Misc
Corrective Action Required
12/27/2013
ROOFTOP: > GAS PIPE MUST BE PAINTED > USE MIN 4" HIGH LABELS TO IDENTIFY ALL ELECTRICAL-POWERED EQUPMENT AT ROOFTOP (RTU'S, EF'S, MUA..) AND REFLECT DESIGNATION IN ELECT PANEL SCHEDULES. > ONE GAS PIPE SUPPORT BLOCK IS NOT COMPLETED. > 4x4 SUPPORTS FOR REFRIGERATION EQUIPMENT DO NOT HAVE SLIP SHEETS TO PROTECT ROOF MEMBRANE. > INSULATION IS INCOMPLETE ON REFRIGERATION TUBING. > ELECT RECEPTS @ RTU'S REQUIRE IN-USE COVERS > CLEAR/CLEAN ENTIRE ROOF OF EXCESS MATERIAL & DEBRIS
Misc
Corrective Action Required
12/27/2013
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PUBLIC NOR CUSTOMERS PRIOR TO APPROVAL.
Piers/Caissons Inspection - Commercial Partial 1/3/2014 at 12:00 AM 01/03/2014
Misc
Partial Correction
01/03/2014
IF LAYOUT IS CORRECT FOR CONCENTRIC LOADING OK TO POUR WHEN READY 4 MENU BOARD PIERS PER 8-1/2" X 11" DRAWINGS ON SITE. ENSURE 3" RE-BAR COVERAGE AT BOTTOMS AND BANKS AND ANCHOR BOLT PLACEMENT PER DRAWINGS.
Alarm Test Passed 12/27/2013 at 12:00 AM 01/10/2014
Alternate Protection Systems Inspection Passed 12/27/2013 at 12:00 AM 01/10/2014
Sprinkler - Flow Test Passed 12/27/2013 at 12:00 AM 01/10/2014
Rough Framing Inspection - Commercial Passed 11/5/2013 at 12:00 AM 01/10/2014
Misc
Resolved
01/10/2014
FASTENER PATTERN ON SW1 SHEAR WALL SHEATHING APROVED. -TIE DOWN ANCHORS INSTALLED FOR SHEAR WALLS - HOOD WALL CHANGED TO METAL STUDS OK TO COVER
Hood/Duct Inspection Passed 1/10/2014 at 12:00 AM 01/10/2014
Misc
Resolved
01/10/2014
IMC 506 COMMERCIAL KITCHEN GREASE DUCT FABRICATION & INSTALLATION: LIGHT TEST OF SHOP WELDS APPROVED; LIGHT TEST OF FIELD WELDS APPROVED. G.C. TO WITNESS INSTALLATION OF 1ST LAYER OF WRAP. 2ND WRAP SUBJECT TO APPROVAL AT OR BEFORE ABOVE-CEILING INSPECTION.
Misc
Resolved
01/10/2014
IMC 507.16 COMMERCIAL KITCHEN GREASE HOOD PERFORMANCE TEST: NEBBS-CERTIFIED REPORT REQUIRED TO BE SUBMITTED TO INSPECTOR WHEN EQUIPMENT IS OPERATIONAL AND BEFORE COMMERCIAL USE; SMOKE CAPTURE TEST TO BE WITNESSED BY INSPECTOR BEFORE ANY OCCUPANCY IS APPROVED.
In-wall Inspection Passed 1/10/2014 at 12:00 AM 01/10/2014
Misc
Resolved
01/10/2014
-FIREBLOCK ALL CONCEALED FURRED OUT WALL SPACES AROUND THE BUILDING PERIMETER AT CEILING LEVEL
Fire Line Construction Inspection Passed 8/27/2013 at 1:00 AM 01/13/2014
Occupancy Inspection - Engineering Passed 1/13/2014 at 12:00 AM 01/13/2014
Occupancy Inspection - Fire Passed 1/13/2014 at 12:00 AM 01/13/2014
Occupancy Inspection - Codes Commercial Temporary C of O 1/13/2014 1/13/2014 at 12:00 AM 01/13/2014
Misc
Resolved
01/13/2014
EXTERIOR OF BUILDING AND SITEWORK EXCLUDED FROM CURRENT FINAL INSPECTION. NOT READY FOR INSPECTION.
Misc
Resolved
01/13/2014
ROOFTOP SCUPPER AT SW CORNER OF BLDG DUMPING WATER ON ELECTRICAL SERVICE GEAR. MUST BE DIVERTED IMMEDIATELY.
Misc
Resolved
01/13/2014
RESOLVE FIRE DEPT ISSUES.
Misc
Resolved
01/13/2014
OBTAIN WATER DEPARTMENT APPROVAL.
Misc
Resolved
01/13/2014
OBTAIN PUBLIC WORKS DEPT APPROVAL.
Misc
Corrective Action Required
12/27/2013
OBTAIN PLANNING & DEVELOPMENT DEPT APPROVAL.
Misc
Resolved
01/13/2014
AFFIX "NO SMOKING" SIGN AT PUBLIC ENTRANCE(S).
Misc
Corrective Action Required
12/27/2013
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): CHECK, COMPLETE AND CORRECT PANEL SCHEDULES AS DISCUSSED.
Misc
Resolved
01/13/2014
UNTERMINATED LIQUID-TIGHT ELECTRICAL CONDUCTORS HANGING AT EXTERIOR EAST & SOUTHEAST WALLS.
Misc
Corrective Action Required
12/27/2013
ENSURE ALL DIMENSIONS AT RESTROOMS ARE PER ADA/ANSI. SEE 18" GRAB BARS.
Misc
Resolved
01/13/2014
IPC 608: BACKFLOW PREVENTION DEVICE REQUIRED AT POTABLE WATER-FED EQUIPMENT. AT CARBONATED BEVERAGE DISPENSING EQUIPMENT USE ASSE 1022 LISTED DEVICE.
Misc
Corrective Action Required
12/27/2013
VACUUM BREAKER REQUIRED AT THREADED HOSE CONNECTIONS.
Misc
Resolved
01/13/2014
NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES. SEE AT DINING AREA
Misc
Resolved
01/13/2014
APPARENT HOT/NEUTRAL REVERSE AT ELECT RECEPT LEFT OF CARBONATED BEVERAGE DISPENSER.
Misc
Resolved
01/13/2014
ENSURE FLOOR SINK IS COMPLETELY SEALED TO WALL.
Misc
Corrective Action Required
12/27/2013
ROOFTOP: > TOP OF GREASE DUCT AT EXHAUST FAN CURB: ELIMINATE PROTRUSIONS AND FILL GAPS AS DISCUSSED. > INSULATION IS INCOMPLETE ON REFRIGERATION TUBING. > CLEAR/CLEAN ENTIRE ROOF OF EXCESS MATERIAL & DEBRIS
Misc
Resolved
01/13/2014
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PUBLIC NOR CUSTOMERS PRIOR TO APPROVAL.
Misc
Corrective Action Required
01/13/2014
GAS PIPE AT WATER HEATER NOT SECURED TO RESIST LATERAL LOADS.
Misc
Corrective Action Required
01/13/2014
SEAL ALL PENETRATIONS OF EXTERIOR WALL.
Footing Inspection - Commercial Passed 1/3/2014 (11:00) 11/18/2013 at 12:00 AM 01/13/2014
Misc
Resolved
01/13/2014
OK TO POUR WHEN READY GRADE BEAMS AND INTEGRAL PIERS FOR TRASH ENCLOSURE.
Gas Piping Inspection - Commercial Passed 1/13/2014 at 12:00 AM 01/13/2014
Misc
Resolved
01/13/2014
IFGC 407; 415: 8' PROTECTION OF ROOF MEMBRANE UNDER WOODEN PIPING SUPPORT BLOCKS FOR GAS PIPING: COMPLY WITH MAXIMUM SUPPORT SPACING PER IFGC. USE WEATHER-RESISTANT BLOCKING MATERIAL PROVIDING SOLID SUPPORT UNDER PIPE. LOOSE-CLAMP BLOCKS TO PIPE. APPLY SPECIFIED / APPROVED, ROOF-COMPATIBLE SLIP SHEET TO UNDERSIDE OF BLOCKS WITH METAL FASTENERS AT SIDES OF BLOCKS.
Misc
Resolved
01/13/2014
IFGC 404.8: EXPOSED METALLIC PIPING MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS.
Misc
Resolved
01/10/2014
PIPING INSIDE BUILDING NOT YET COMPLETED. SUBSEQUENT INSPECTION AND PRESSURE TEST WILL BE REQUIRED WHEN PIPING IS COMPLETED.
Piers/Caissons Inspection - Commercial Passed 1/3/2014 at 12:00 AM 01/13/2014
Misc
Resolved
01/13/2014
IF LAYOUT IS CORRECT FOR CONCENTRIC LOADING OK TO POUR WHEN READY 4 MENU BOARD PIERS PER 8-1/2" X 11" DRAWINGS ON SITE. ENSURE 3" RE-BAR COVERAGE AT BOTTOMS AND BANKS AND ANCHOR BOLT PLACEMENT PER DRAWINGS.
Underground Electrical Inspection - Commercial Passed 12/20/2013 at 12:00 AM 01/13/2014
Misc
Resolved
01/13/2014
OK TO COVER WHEN READY INSTALLATION OF BURIED ELECTRICAL CONDUIT FOLLOWING SEGMENTS: FROM NE CORNER OF BLDG TO J.B. AND TWO GROUND LUMINAIRES; FROM PRE-MENU BOARD TO TWO MENU BOARD LOCATIONS (SUBSTANTIALLY COVERED BUT TO BE PARTIALLY EXPOSED LATER WHEN MENU BOARDS ARE CONSTRUCTED)
Water Service Inspection Passed 8/27/2013 at 12:00 AM 01/13/2014
Misc
Resolved
01/13/2014
OK TO COVER WHEN READY DOMESTIC WATER SERVICE LINE FROM BUILDING ENTRY TO 15' WEST. COPPER OR PEX OK
Occupancy Inspection - Planning Temporary C of O 1/13/2014 at 12:00 AM 01/14/2014
Corrective Action Required
01/14/2014
TRASH ENCLOSURE. Install solid steel gates per the approved plan.
Corrective Action Required
01/14/2014
LANDSCAPING. Complete landscaping per the approved plan.
Piers/Caissons Inspection - Commercial Passed 1/14/2014 (10:30) 1/14/2014 at 12:00 AM 01/14/2014
Occupancy Inspection - Codes Commercial Failed 1/23/2014 at 12:00 AM 01/23/2014
Misc
Corrective Action Required
01/13/2014
OBTAIN PLANNING & DEVELOPMENT DEPT APPROVAL. ANITICIPATE LATE MARCH COMPLETION.
Misc
Resolved
01/23/2014
NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): CHECK, COMPLETE AND CORRECT PANEL SCHEDULES AS DISCUSSED.
Misc
Corrective Action Required
01/13/2014
ENSURE ALL DIMENSIONS AT RESTROOMS ARE PER ADA/ANSI. SEE 18" GRAB BARS.
Misc
Resolved
01/23/2014
VACUUM BREAKER REQUIRED AT THREADED HOSE CONNECTIONS.
Misc
Corrective Action Required
01/13/2014
ROOFTOP: > INSULATION ON REFRIGERATION TUBING NEEDS TO BE REPLACED. > CLEAR/CLEAN ENTIRE ROOF OF EXCESS MATERIAL & DEBRIS
Misc
Resolved
01/23/2014
GAS PIPE AT WATER HEATER NOT SECURED TO RESIST LATERAL LOADS.
Misc
Resolved
01/23/2014
SEAL ALL PENETRATIONS OF EXTERIOR WALL.
Occupancy Inspection - Codes Commercial Failed 1/23/2014 at 12:00 AM 01/23/2014
Misc
Corrective Action Required
01/23/2014
OBTAIN PLANNING & DEVELOPMENT DEPT APPROVAL. ANITICIPATE LATE MARCH COMPLETION.
Misc
Corrective Action Required
01/23/2014
ENSURE ALL DIMENSIONS AT RESTROOMS ARE PER ADA/ANSI. SEE 18" GRAB BARS. TO BE READY FOR RE-INSPECTION 1/24/14.
Misc
Corrective Action Required
01/23/2014
ROOFTOP: > INSULATION ON REFRIGERATION TUBING NEEDS TO BE REPLACED. > CLEAR/CLEAN ENTIRE ROOF OF EXCESS MATERIAL & DEBRIS TO BE READY FOR RE-INSPECTION 1/24/14.
Occupancy Inspection - Codes Commercial Temporary C of O 1/24/2014 at 12:00 AM 01/24/2014
Misc
Corrective Action Required
01/23/2014
FINISH SITEWORK PENDING CONDUCIVE WEATHER. ANITICIPATE LATE MARCH COMPLETION. CALL TO REQUEST RE-INSPECTION WHEN READY.
Misc
Resolved
01/24/2014
ENSURE ALL DIMENSIONS AT RESTROOMS ARE PER ADA/ANSI. SEE 18" GRAB BARS. TO BE READY FOR RE-INSPECTION 1/24/14.
Misc
Resolved
01/24/2014
ROOFTOP: > INSULATION ON REFRIGERATION TUBING NEEDS TO BE REPLACED. > CLEAR/CLEAN ENTIRE ROOF OF EXCESS MATERIAL & DEBRIS TO BE READY FOR RE-INSPECTION 1/24/14.
Misc
Corrective Action Required
01/24/2014
SECURE ROOFTOP WALKWAY RUNNERS TO PREVENT OBSTRUCTION OF ROOF DRAINS.
Occupancy Inspection - Codes Commercial Temporary C of O 4/21/2014 4/21/2014 at 12:00 AM 04/21/2014
Misc
Corrective Action Required
01/24/2014
LOWER WATER METER WELL COVER TO BE FLUSH WITH FINISH GRADE
Misc
Resolved
04/21/2014
SECURE ROOFTOP WALKWAY RUNNERS TO PREVENT OBSTRUCTION OF ROOF DRAINS.
Misc
Corrective Action Required
04/21/2014
RESOLVE PLANNING DEPARTMENT ISSUES
Occupancy Inspection - Planning Temporary C of O 4/21/2014 at 12:00 AM 04/21/2014
Corrective Action Required
04/21/2014
LANDSCAPING. Install one additional tree and add mulch to island along the exterior (west) side of the drive-through lanes.
Miscellaneous Inspection Passed 4/21/2014 at 12:00 AM 04/21/2014
Occupancy Inspection - Water Utilities Passed 04/24/2014
Occupancy Inspection - Codes Commercial Partial 4/25/2014 at 12:00 AM 04/25/2014
Misc
Resolved
04/25/2014
LOWER WATER METER WELL COVER TO BE FLUSH WITH FINISH GRADE
Misc
Corrective Action Required
04/21/2014
RESOLVE PLANNING DEPARTMENT ISSUES
Occupancy Inspection - Codes Commercial Full C of O 5/1/2014 at 12:00 AM 05/01/2014
Misc
Resolved
05/01/2014
RESOLVE PLANNING DEPARTMENT ISSUES
Occupancy Inspection - Planning Passed 5/1/2014 at 12:00 AM 05/02/2014
Documents & Images
Date Uploaded File Type Document Name
04/02/2013 PRCOM20130393wateremail.pdf
04/04/2013 Letter Plan Review Conditions
06/05/2013 Letter Plan Review Conditions
06/11/2013 Letter Building Permit
06/25/2013 Letter Fire Building Plan Review
06/27/2013 Letter Fire Building Plan Review
06/27/2013 Letter Fire Building Plan Review
07/18/2013 Letter Fire (Alarm) Plan Review Notice
08/02/2013 Letter Inspection Summary
08/27/2013 Letter Inspection Summary
08/27/2013 Letter Inspection Summary
08/30/2013 Letter Inspection Summary
09/12/2013 Letter Inspection Summary
10/07/2013 Letter Fire (Sprinkler) Plan Review
10/16/2013 Letter Inspection Summary
10/17/2013 Letter Inspection Summary
10/28/2013 Letter Inspection Summary
10/31/2013 Letter Inspection Summary
11/05/2013 Letter Inspection Summary
11/11/2013 Letter Inspection Summary
11/13/2013 Letter Inspection Summary
11/14/2013 Letter Inspection Summary
11/15/2013 Letter Inspection Summary
11/18/2013 Letter Inspection Summary
12/02/2013 Letter Inspection Summary
12/04/2013 Letter Inspection Summary
12/05/2013 Letter Inspection Summary
12/09/2013 Letter DOC120913-002.pdf
12/20/2013 Letter Inspection Summary
12/27/2013 Letter Inspection Summary
01/03/2014 Letter Inspection Summary
01/13/2014 Letter Codes Temporary Certificate of Occupancy
01/14/2014 Letter Inspection Summary
01/23/2014 Letter Inspection Summary
01/24/2014 Letter Codes Temporary Certificate of Occupancy
03/27/2014 Letter Codes 10 Day Letter
04/21/2014 Letter Codes Temporary Certificate of Occupancy
05/01/2014 Letter Field Certificate of Occupancy
05/06/2014 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home