Planning Application Status

PL2025130




 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PL2025130
Club Carwash - Oldham Village
Commercial Final Development Plan
Commercial Final Development Plan
In Plan Review
05/29/2025
OLDHAM INVESTORS LLC
Drive-thru carwash with 25 vacuum stations on lot 9 of Oldham Village. Building is 5,164 sqft.
Locations
Property
61500036400000000

Structure
# *

Address
1031 SW JEFFERSON ST, LEES SUMMIT, MO 64081

1021 Jefferson Crossing
Contacts
OLDHAM INVESTORS LLC, Address:7200 W 132ND ST STE 150  
Club Carwash Operating, LLC, Address:1591 E. Prathersville Rd, Phone:(573) 999-5178  
Cochran Engineering, Address:Att: Eric Kirchner, Phone:(636) 332-4574  
Keith Farrell, Cochran Engineering, Address:8 E. Main St, Phone:(636) 332-4574  
Reviews
Review Type Outcome Est. Completion Date Completed
Planning Review Corrections 06/12/2025 06/12/2025
Hector Soto Jr.
Corrective Action Required
06/12/2025

LOT INFORMATION. 1) The total site acreage listed on Sheet C1 shows 47,045 sq. ft., but the most recent draft version of the associated minor plat shows a site/lot area of 47,242 sq. ft. Revise to match the plat. 2) The labeled lot line dimensions for the east property line and the two long boundary segments on the north and south sides of the lot do not match the most recent draft version of the associated plat. Revise to match the plat. 3) The curve radius listed for the east property line (Curve C1) does not match the most recent draft version of the associated plat, nor do the seconds for the bearing listed for Line Segment L1. Revise.
Corrective Action Required
06/12/2025

Corrective Action Required
06/12/2025

STREETS. SW Jefferson Crossing is labeled as a public roadway with 60' of right-of-way throughout the plan set. SW Jefferson Crossing is actually a private street within a 60' private common area tract, so it is neither a public street nor is it located within public right-of-way. Revise.
Corrective Action Required
06/12/2025

SIDEWALKS. Label the 5' sidewalk along SW Jefferson Crossing on Sheet C3.
Corrective Action Required
06/12/2025

OIL AND GAS WELLS. Add a note to the plans regarding the presence of any active, inactive or capped oil and/or gas wells on the property. Cite the source of information used to make this determination. MoDNR maintains an online well database that can be sourced and cited for this information.
Corrective Action Required
06/12/2025

BUILDING ELEVATIONS. No architectural building elevations were included in the application submittal for review. Submit color elevations that includes a material and color schedule for all exterior building materials.
Corrective Action Required
06/12/2025

MECHANICAL SCREENING. Show the location of all RTUs and ground-mounted equipment on the building elevations or site plan as appropriate. RTUs shall be fully screened from view by extending parapet walls to a height at least equal to the height of the units being screened. Ground-mounted equipment shall be fully screened from view up the height of the units by using evergreen landscaping or masonry walls.
Corrective Action Required
06/12/2025

SITE DATA TABLE. For centralized and easy reference, add the lot area and proposed building area information to the list of development information provided at the bottom right corner of Sheet C3.
Corrective Action Required
06/12/2025

TRASH ENCLOSURE. The dumpster enclosure detail on Sheet C12 shows the enclosure gates to be vinyl. City ordinance requires the gates to be either a solid steel opaque gate painted to be compatible with the color of the masonry or steel walls and building it is to serve, or a steel framed semi-opaque gate with a screen mesh material approved by the Director that provides an appropriate visual barrier. The proposed vinyl gates do not comply with the enclosure design requirements.
Corrective Action Required
06/12/2025

PARKING LOT BOUNDARY. Temporary asphalt curbing shall be provided where the parking lot drive will be extended in the future when the abutting lot to the south is developed. Curb blocks/wheel stops or the like cannot be used to satisfy this temporary curbing requirement.
Corrective Action Required
06/12/2025

ADA ACCESSIBLE ROUTE. Show the accessible path from the ADA space to the building entrance. Label the slopes and cross-slopes of said accessible path.
Corrective Action Required
06/12/2025

PLAT. The final plat for the Oldham Village development has yet to be recorded. No building permit shall be issued until such time as the approved final plat has been recorded with the County and the requisite number of recorded copies have been submitted to the City.
Engineering Review Corrections 06/12/2025 06/12/2025
Gene Williams, P.E.
Corrective Action Required
06/12/2025

Sheet C3: a. site-specific design for the new ADA-accessible ramps and ADA-accessible route across the commercial entrance is required. It is not sufficient to call-out a standard detail. At a minimum, elevations and slope callouts shall be provided for the site specific ramp and accessible route design across the commercial entrance. b. eliminate the "wings" on the ADA-accessible ramp if possible, and grade to provide the needed transition.
Corrective Action Required
06/12/2025

Sheet C4: a. private domestic water line from the public main to the meter shall be copper. Copper line shall also be required a minimum of 10 feet beyond the meter.
Corrective Action Required
06/12/2025

Profile View Sheets of Stormwater Pipes: HGL is called-out without the design storm. Provide the design storm callout, otherwise "HGL" by itself is meaningless.
Corrective Action Required
06/12/2025

Sheet C13: a. revise the ADA-accessible route and ramps to include slope callouts in addition to elevations.
Corrective Action Required
06/12/2025

A cost estimate is required prior to formal approval.
Building Codes Review Corrections 06/12/2025 06/11/2025
Joe Frogge
Miscellaneous Correction
Corrective Action Required
06/11/2025

Specify type of water tap at main.
Miscellaneous Correction
Corrective Action Required
06/11/2025

Water piping from main to meter and from meter to 10' towards building must be 2" copper.
Fire Review Corrections 06/12/2025 06/10/2025
Jim Eden
Code Statement
Informational
06/10/2025

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
Hydrants
Corrective Action Required
06/10/2025

IFC 507.5.1 - Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official. The building exceeds 300 feet from a hydrant as measured around the building.
Imposed Loads
Corrective Action Required
06/10/2025

IFC 503.2.3 - Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities. The drive lane along the north side of the building shall be capable of supporting the weight of a fire apparatus (75,000-pounds).Confirm construction.
Traffic Review No Comments 06/12/2025 06/02/2025
Erin Ralovo
Fees
Paid Fees Amount Paid Owing Date Paid
9110077-Final Development Plan fee $725.00 $725.00 Paid 05/29/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Hearings
Title Location Date Time
Documents & Images
Date Uploaded File Type Document Name
05/29/2025 Application Form Application form cover sheet_signed_PL2025130
05/29/2025 Plans Plan set_Rev 0_PL2025130
05/29/2025 Application Form FDP Checklist_PL2025130
05/29/2025 Activity Document Legal Description_PL2025130
05/29/2025 Application Form Ownership Affidavit_PL2025130
05/29/2025 Engineer Report/Study Storm Report_Rev 0_PL2025130
05/29/2025 Receipt Receipt_PL2025130
06/12/2025 Letter Applicant Letter - FDP (DFDP)
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home