Review Type |
Outcome |
Est. Completion Date |
Completed |
Engineering Review
|
Approved with Conditions
|
05/31/2023
|
05/31/2023
|
|
Mike Weisenborn
|
|
Corrective Action Required
Please revise the estimate to include a breakdown that includes quantity, units, unit price, and total for each line item. Only site related items should be included. The estimate shall be signed/sealed by the engineer.
|
|
Corrective Action Required
Relocate the backflow vault to be outside of the public utility easement as required by Design and Construction Manual Section 6901.H.3.a.
|
|
Corrective Action Required
The method of draining the backflow vault sump shall be shown. We have seen the following methods used in the past: 1) daylighting with a small diameter pipe, 2) connection to a storm box, or 3) construction of an infiltration gallery in the form of a 2 foot diameter hole lined with permeable geotextile and filled with clean 3/4 inch rock. In lieu of the above, a sump pump could be installed. Please evaluate and revise as appropriate.
|
|
Corrective Action Required
Please revise to provide adequate drop across structures as required by Design and Construction Manual Section 5604.5.
|
|
|
Planning Review
|
No Comments
|
05/31/2023
|
05/31/2023
|
|
Mike Weisenborn
|
|
|
Fire Review
|
Approved with Conditions
|
05/31/2023
|
05/29/2023
|
|
Jim Eden
|
|
Code Statement
Corrective Action Required
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
|
|
|
Building Codes Review
|
No Comments
|
06/01/2023
|
05/24/2023
|
|
Mike Weisenborn
|
|
|
Traffic Review
|
No Comments
|
06/01/2023
|
05/24/2023
|
|
Mike Weisenborn
|
|
|
Building Codes Review
|
No Comments
|
05/01/2023
|
05/01/2023
|
|
Joe Frogge
|
|
|
Traffic Review
|
No Comments
|
05/01/2023
|
05/01/2023
|
|
Mike Weisenborn
|
|
|
Engineering Review
|
Corrections
|
05/01/2023
|
05/01/2023
|
|
Susan Nelson, P.E.
|
|
Corrective Action Required
General
- Please provide Engineer’s Estimate of Probable Costs.
- Please provide MDNR Land Disturbance Permit.
- Please provide SWPPP.
- Add more information to the Stormwater Management Memo indicating that the proposed increase in parking area in this project was already included in the previous stormwater study.
|
|
Corrective Action Required
C00 Overview Sheet
- Please specifically state the “City of Lee’s Summit’” Design and Construction Manual.
- Verify that oil – gas wells are not within the property and add a note regarding the specific study used as reference.
- Please show and label right-of-way limits and utility easements here and throughout plan set.
- Existing sidewalk and ramps not consistently shown. Arrows appear to be floating.
- Proposed monument sign cannot be located within the utility easement. Please relocate.
|
|
Corrective Action Required
C05/06 Erosion Control Details
- Sheets appear blurry.
|
|
Corrective Action Required
C10 Utility Plan
- Install new 8” tee with 2 – 8” gate valves at fire line connection to water main.
- Install backflow device vault for fire line.
- Please label material for domestic line and the fire line.
- Use new 2” tap and meter for the domestic water - Install cut-in wye for sanitary sewer connection.
- Keynote 5 points to two unrelated locations.
|
|
Corrective Action Required
C12 Storm Sewer Profiles
- Please add HGL.
- FL in and out of each drain basin is needed.
|
|
Corrective Action Required
C14/15 Details
- Sheets appear blurry.
- Add detail WAT-12 Vault for Double Check Detector Check.
- Add details for pipe trench and backfill.
|
|
Corrective Action Required
C16 Details
- On pavement sections, please show that the gravel base extends 1’ min. behind back of curb.
|
|
|
Planning Review
|
Corrections
|
05/01/2023
|
05/01/2023
|
|
Jalen Ford
|
|
Corrective Action Required
Is there any visual representation of the monument sign?
|
|
Corrective Action Required
(C00) Please mention that oil and gas wells were looked into. Also provide citation for the findings as well.
|
|
|
Fire Review
|
Corrections
|
05/01/2023
|
04/26/2023
|
|
Jim Eden
|
|
Code Statement
Corrective Action Required
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
|
|
Miscellaneous Correction
Corrective Action Required
The scale is incorrect on drawing C10
|
|
FDC
Corrective Action Required
IFC 903.3.7 - Fire department connections. The location of fire department connections shall be approved by the fire code official. Connections shall be a 4 inch Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the code official.
Action required- Show the location of the FDC and a hydrant within 100 feet.
|
|
|