Planning Application Status

PL2022025




 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PL2022025
Chase Bank - Public water line relocation
Engineering Plan Review
Engineering Plan Review
Approved
01/26/2022
JPMORGAN CHASE BANK NATIONAL ASSOCIATION
Locations
Contacts
JPMORGAN CHASE BANK NATIONAL ASSOCIATION, Address:1111 POLARIS PKWY STE 1J OH1-0241  
STATE PERMITS INC, Address:319 ELAINES COURT, Phone:(608) 407-9078  
Reviews
Review Type Outcome Est. Completion Date Completed
Engineering Review Approved with Conditions 03/11/2022 03/10/2022
Loic Nguinguiri, E.I.
Miscellaneous Correction
Corrective Action Required
03/10/2022

Stargrip joint restraint, shown in the submitted shop drawings, needs to have the Starbond polyester coating.
Miscellaneous Correction
Corrective Action Required
03/10/2022

Bedding aggregate is to be placed from a level 6 inches (minimum) below the bottom of the pipe to a level 12 inches (minimum) above the top of the pipe.
Miscellaneous Correction
Corrective Action Required
03/11/2022

Please submit a Missouri DNR permit.
Engineering Review Corrections 02/10/2022 02/08/2022
Loic Nguinguiri, E.I.
Miscellaneous Correction
Corrective Action Required
02/03/2022

Obtain an approved project cost estimate from Water Utilities, and re-upload to the CityView online portal.
Miscellaneous Correction
Corrective Action Required
02/03/2022

Please submit a Missouri DNR permit.
Engineering Review Corrections 02/02/2022 01/28/2022
Kent Monter
Miscellaneous Correction
Corrective Action Required
01/30/2022

From Water Utilities: Stargrip joint restraint, shown in the submitted shop drawings, needs to have the Starbond polyester coating.
Miscellaneous Correction
Corrective Action Required
01/30/2022

It is the design engineer’s responsibility to ensure that the proposed materials and components shown in the submitted shop drawings meet the specifications listed in Section 3900 of the City’s Design and Construction Manual.
Miscellaneous Correction
Corrective Action Required
01/30/2022

Construction plans are approvable, as long as bedding aggregate is to be placed from a level 6 inches (minimum) below the bottom of the pipe to a level 12 inches (minimum) above the top of the pipe.
Miscellaneous Correction
Corrective Action Required
01/30/2022

Please provide an Engineer’s Opinion of Probable Construction Cost (EOOPCC) sheet.
Miscellaneous Correction
Corrective Action Required
02/01/2022

Please submit a Missouri DNR permit.
Hearings

There are no hearings for this planning application.

Documents & Images
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home