Review Type |
Outcome |
Est. Completion Date |
Completed |
Planning Review
|
Approved with Conditions
|
03/31/2020
|
03/30/2020
|
|
Hector Soto Jr.
|
|
Corrective Action Required
SPECIAL USE CONDITIONS. The automotive sales use shall be subject to the conditions listed under UDO Section 6.1050.A.
|
|
|
Traffic Review
|
No Comments
|
03/31/2020
|
03/26/2020
|
|
Michael Park
|
|
|
Fire Review
|
Approved with Conditions
|
03/31/2020
|
03/26/2020
|
|
Jim Eden
|
|
Code Statement
Corrective Action Required
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
|
|
Hydrants
IFC 507.5.1 - Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official.
Action required: Provide an additional accessible hydrant.
|
|
FDC
IFC 903.3.7 - Fire department connections. The location of fire department connections shall be approved by the fire code official. Connections shall be a 4 inch Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the code official.
Action required: Show the location of the FDC and hydrant within 100'.
|
|
Imposed Loads
IFC 503.2.3 - Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
|
|
|
Engineering Review
|
No Comments
|
03/31/2020
|
03/25/2020
|
|
Sue Pyles, P.E.
|
|
|
Planning Review
|
Corrections
|
03/06/2020
|
03/06/2020
|
|
Hector Soto Jr.
|
|
Corrective Action Required
USE NARRATIVE.
- The application lists "automotive detailing, cleaning, reconditioning interior and exterior" as the proposed description of use. It is staff's understanding that automotive sales will also be conducted on-site. Please confirm if this is the case. Will any automotive repair activities be conducted on-site? If so, please list the range of repair services offered.
- If auto sales and repair services will take place on-site, please respond to the conditions for each use found under UDO Section 6.1050 and Section 6.440. If no auto sales and/or repair services will take place on-site, then an SUP is not required for the proposed use.
|
|
Corrective Action Required
TIME PERIOD. There is no requested time period listed on the application or mentioned in the use narrative. For new construction facilities such as these, the City Council has historically granted SUPs for time periods ranging from 20-30 years.
|
|
|
Traffic Review
|
No Comments
|
03/06/2020
|
03/03/2020
|
|
Michael Park
|
|
|
Fire Review
|
Corrections
|
03/06/2020
|
03/02/2020
|
|
Jim Eden
|
|
Code Statement
Corrective Action Required
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
|
|
Hydrants
Corrective Action Required
IFC 507.5.1 - Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official.
Action required: Provide an additional accessible hydrant.
|
|
FDC
Corrective Action Required
IFC 903.3.7 - Fire department connections. The location of fire department connections shall be approved by the fire code official. Connections shall be a 4 inch Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the code official.
Action required: Show the location of the FDC and hydrant within 100'.
|
|
Imposed Loads
Corrective Action Required
IFC 503.2.3 - Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
|
|
|
Engineering Review
|
No Comments
|
03/06/2020
|
02/28/2020
|
|
Sue Pyles, P.E.
|
|
|