Planning Application Status

PL2019297




 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PL2019297
PUBLIC WATER MAIN EXTENSION - KANSAS CITY SURGICAL & DENTAL OFFICE
Engineering Plan Review
Engineering Plan Review
Approved
09/06/2019
Locations
Contacts
CROCKETT ENGINEERING CONSULTANTS , Address:1000 W NIFONG BLVD, SUITE 207 , Phone:(573) 447-0292  
Reviews
Review Type Outcome Est. Completion Date Completed
Record Drawings Review No Comments 11/18/2022 11/11/2022
Sue Pyles, P.E.
Engineering Review No Comments 10/02/2019 09/25/2019
Gene Williams, P.E.
Engineering Review Corrections 09/20/2019 09/13/2019
Gene Williams, P.E.
Corrective Action Required
09/13/2019

What is the plan for future pavement near the south fire hydrant (i.e., listed as note D on Sheet CE1)? Is this the final location of the fire hydrant, or will it be moved in the future? If it will be moved in the future, please change the configuration of this fire hydrant to an "inline" temporary fire hydrant, with a valve just prior to the fire hydrant assembly.
Corrective Action Required
09/13/2019

Please see comments related to the "future domestic water service line" in the Final Development Plan. Sheet CE1 should be changed to remove this connection. No connection can be made at this time.
Corrective Action Required
09/13/2019

Sheet CE2 shows a profile view with stationing, but the plan view does not show any stationing. In addition, the scale is 1 inch to 50 feet. The standard is 1 inch to 20 feet. Please consider placing both the plan view and the profile view on one (1) sheet, perhaps with a 1 inch to 30 foot scale, along with stationing for both the profile and plan view.
Corrective Action Required
09/13/2019

Cover Sheet: There are numerous references to the City of Lee's Summit standards for street, stormwater, and sanitary sewer shown in the notes. However, there are no such notes for water lines. Tracer wire is not addressed, and fittings (i.e., bends, tees, etc.) should be specifically called-out as being ductile iron with epoxy-coating as per City of Lee's Summit standards.
Corrective Action Required
09/13/2019

It did not appear that any elevation call-outs were provided for the pipe in the profile view.
Hearings

There are no hearings for this planning application.

Documents & Images
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home