Permit Application Status

PRRES20253205


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20253205
Building Permit - Residential
Issued
NEW DUPLEX
NEW DUPLEX. UNFINISHED BASEMENT. Permitted under PRRES20244002 previously Andrea Sessler 07/30/2025 11:48 AM
07/30/2025
09/05/2025
Locations
Contacts
Site360 LLC, Address:1813 SW Fountain Drive  
JGKELLEY2@GMAIL.COM  
COMFORT SYSTEMS HTG/CLG, Address:128 W Markey Rd, Phone:(816) 322-1013  
ELECTRICAL CONNECTIONS, Address:20112 HOPS CREEK DR, Phone:(816) 838-6946  
A BRIGHT PLUMBING LLC, Address:201 NE WOODBURY DR, Phone:(816) 867-4540  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
Additional Permit Fee $1,908.00 $1,908.00 Paid 09/05/2025
$1,858.00
Not Ready Inspection Fee $75.00 $75.00 Paid 09/22/2025
Outstanding Fees Amount Paid Owing Date Paid
Not Ready Inspection Fee $75.00 $0.00 $75.00 Not Paid


$75.00    Add Fees to My Cart
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Plot Plan Inspection Pending
Footing Inspection - Residential Pending
Foundation Inspection - Commercial Pending
Underslab Plumbing Inspection - Residential Pending
Underslab Electrical Inspection - Residential Pending
Occupancy Inspection - Codes Residential Pending
Erosion Control Inspection Residential Pending
All Rough Inspection - Residential Not Ready 9/17/2025 9/17/2025 09/17/2025
Misc
Corrective Action Required
09/17/2025
Not ready -Post address -Complete nailing pattern at CS-WSP panels, PFH and CS-PF -Horizontal seams must occur in middle 24" of portal legs
All Rough Inspection - Residential Failed 9/25/2025 9/25/2025 09/25/2025
Misc
Corrective Action Required
09/17/2025
Exterior sheathing ok to cover
Erosion Control Inspection Residential Failed 09/25/2025
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
09/25/2025
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. -Provide gravel filter of min 6" lift of min 3/4" gravel at drive. -Clean silt from street
Piers/Caissons Inspection - Residential Failed 10/14/2025 10/14/2025 10/14/2025
Misc
Corrective Action Required
10/14/2025
-Piers to be 36" depth min -Remove loose gravel from bottom of pier
Piers/Caissons Inspection - Residential Passed 10/15/2025 10/15/2025 10/15/2025
Misc
Resolved
10/15/2025
Gas Service Inspection - Residential Passed 10/27/2025 10/27/2025 10/27/2025
All Rough Inspection - Residential Failed 10/27/2025 10/27/2025 10/27/2025
Misc
Corrective Action Required
09/25/2025
Exterior sheathing ok to cover Attic framing ok to cover
Erosion Control Inspection Residential Failed 10/27/2025
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
09/25/2025
10/27/25 EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. -Provide gravel filter of min 6" lift of min 3/4" gravel at drive.
Electrical Service Inspection Failed 10/27/2025 10/27/2025 10/27/2025
Misc
Corrective Action Required
10/27/2025
-Unable to open exterior disconnect for inspection -GEC must connect to service neutral at first point of disconnect -Panels downstream from exterior disconnect require equipment grounding conductor and all grounds and neutrals to be separated -Close any openings in exterior panel
Rated Assembly Inspection Partial 10/29/2025 10/29/2025 10/29/2025
Misc
Informational
10/29/2025
Above ceiling attic screw pattern is good, behind furnace ductwork screw pattern is good mud and tape good , ok to set ductwork.
Electrical Service Inspection Passed 10/29/2025 10/29/2025 10/29/2025
Misc
Resolved
10/29/2025
Erosion Control Inspection Residential Partial 10/29/2025 10/29/2025 10/29/2025
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
10/29/2025
10/27/25 EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. -Provide gravel filter of min 6" lift of min 3/4" gravel at drive.
Sewer Service Inspection - R Partial 10/30/2025 10/30/2025 10/30/2025
Misc
Informational
10/30/2025
219 inspected only
Sewer Service Inspection - R Passed 11/3/2025 11/3/2025 11/03/2025
Misc
Resolved
11/03/2025
219 inspected only
Water Service Inspection - R Partial 11/5/2025 11/5/2025 11/05/2025
Misc
Corrective Action Required
11/05/2025
Unit 229 only
Water Service Inspection - R Passed 11/14/2025 11/14/2025 11/14/2025
Misc
Resolved
11/14/2025
Water for both units
Rated Assembly Inspection Partial 11/25/2025 11/25/2025 11/25/2025
Misc
Informational
10/29/2025
Above ceiling attic screw pattern is good, behind furnace ductwork screw pattern is good mud and tape good , ok to set ductwork.
All Rough Inspection - Residential Failed 11/25/2025 11/25/2025 11/25/2025
Misc
Corrective Action Required
10/27/2025
BOTH UNITS -Anchor bolts to be in middle third of plate at garage -Seal penetrations at joist space of hvac chase -Joist over bored for dwv at entry -Install bonding screw and jumper at metallic ceiling box at entry -Install security blocking at hinge and strike locations at entry doors -Protect electrical min 6” Above floor at island -Holes bored closer than 2” together at powder room joists -Fireblock dead space at dwv chase -Support dwv max 48” oc at powder room joists -Protect dryer duct 2” below plate line -Cripple walls shorter than 14” require plywood on at least one face at front bathroom exterior wall -solid block or provide lateral restraint above load bearing walls -Provide proper slope at vents in attic space -Seal gaps in vertical fireblocking at double walls (bottom plates) -Seal gaps at ceiling line fireblocking at basement fur out wall -Complete fireblocking at soffit lines in basement -Provide receptacle at wall space greater than 24” at basement bed entry 217 -Provide stud shoe at stud over bored for Se cable -Install stud shoe at over bored stud in exterior kitchen wall -protect electrical closer than 1.25” to face of framing at bottom plates 219 -missing receptacle at shower wall in master bed -Nail exterior corners
All Rough Inspection - Residential Failed 12/17/2025 12/17/2025 12/17/2025
Misc
Corrective Action Required
11/25/2025
BOTH UNITS -Anchor bolts to be in middle third of plate at garage-NOT DONE -Seal penetrations at joist space of hvac chase -SEE AT JOIST SPACES -Install security blocking at hinge and strike locations at entry doors-NOT DONE AT 217 -Fireblock dead space at dwv chase-NOT DONE THIS IS BY GARAGE ENTRY/FRONT DOOR CLOSET 104 -Cripple walls shorter than 14” require plywood on at least one face at front bathroom exterior wall-NOT DONE IN 219 -Provide proper slope at vents in attic space-NOT DONE IN 219 217 -Provide stud shoe at stud over bored for Se cable-FASTEN PER MANUFACTURER 219 -Nail exterior corners-NAIL 12”’ OC MIN
Rated Assembly Inspection Partial 12/17/2025 12/17/2025 12/17/2025
Misc
Informational
11/25/2025
Above ceiling attic screw pattern is good, behind furnace ductwork screw pattern is good mud and tape good , ok to set ductwork.
All Rough Inspection - Residential Passed 12/22/2025 12/22/2025 12/22/2025
Misc
Resolved
12/22/2025
BOTH UNITS -Anchor bolts to be in middle third of plate at garage-NOT DONE -Seal penetrations at joist space of hvac chase -SEE AT JOIST SPACES -Install security blocking at hinge and strike locations at entry doors-NOT DONE AT 217 -Fireblock dead space at dwv chase-NOT DONE THIS IS BY GARAGE ENTRY/FRONT DOOR CLOSET 104 -Cripple walls shorter than 14” require plywood on at least one face at front bathroom exterior wall-NOT DONE IN 219 -Provide proper slope at vents in attic space-NOT DONE IN 219 217 -Provide stud shoe at stud over bored for Se cable-FASTEN PER MANUFACTURER 219 -Nail exterior corners-NAIL 12”’ OC MIN
Driveway Inspection Partial 2/19/2026 2/19/2026 02/19/2026
Misc
Informational
02/19/2026
02/19/26 Thursday JMJ Driveway - forms and materials passed pre-inspection.
Rated Assembly Inspection Not Ready 2/18/2026 2/24/2026 02/24/2026
Misc
Informational
12/17/2025
Above ceiling attic screw pattern is good, behind furnace ductwork screw pattern is good mud and tape good , ok to set ductwork.
Misc
Corrective Action Required
02/24/2026
2/24/26 NOT READY 217 -Missing rock at stairwell landing -Complete screw pattern at patch by stairwell in kitchen -Complete rock at top plates in garage-REMOVE INSULATION FOR INSPECTION -Rock joist space in basement -Tape seam at ceiling line second floor -Add rock at bottom plate second floor 219 -Remove insulation in garage and complete rock at top plate -Remove rock in kitchen for inspection -Install rock at joist space in basement -Seal gap in between joist and mechanical chase second floor -Seal gap above top plates second floor above stairwell -Seal penetration in back bedroom -Tape seam at ceiling line second floor
Rated Assembly Inspection Passed 2/27/2026 2/27/2026 02/27/2026
Misc
Resolved
02/27/2026
Above ceiling attic screw pattern is good, behind furnace ductwork screw pattern is good mud and tape good , ok to set ductwork.
Misc
Resolved
02/27/2026
2/24/26 NOT READY 217 -Missing rock at stairwell landing -Complete screw pattern at patch by stairwell in kitchen -Complete rock at top plates in garage-REMOVE INSULATION FOR INSPECTION -Rock joist space in basement -Tape seam at ceiling line second floor -Add rock at bottom plate second floor 219 -Remove insulation in garage and complete rock at top plate -Remove rock in kitchen for inspection -Install rock at joist space in basement -Seal gap in between joist and mechanical chase second floor -Seal gap above top plates second floor above stairwell -Seal penetration in back bedroom -Tape seam at ceiling line second floor
Driveway Inspection Passed 3/2/2026 3/2/2026 03/02/2026
Misc
Informational
02/19/2026
02/19/26 Thursday JMJ Driveway - forms and materials passed pre-inspection.
Misc
Informational
03/02/2026
03/02/26 Monday JMJ Driveway - Passed inspection.
Documents & Images
Date Uploaded File Type Document Name
07/30/2025 Application Form APPLICATION
09/04/2025 Letter LETTER FOR PLANS TO BE USED BY NEW OWNER
09/04/2025 Approved Plans APPROVED PLANS 1
09/05/2025 Letter OWNERSHIP DOC
09/05/2025 Permit Codes Residential Plan Review
09/05/2025 Permit DS Building Permit
09/05/2025 Receipt Receipt for transaction: 2025-006936
09/05/2025 Plot Plan APPROVED PLOT PLAN
09/11/2025 Approved Plans APPROVED PLANS
09/17/2025 Letter INSPECTION SUMMARY
09/22/2025 Receipt Receipt for transaction:2025-007269
09/25/2025 Letter INSPECTION SUMMARY
09/25/2025 Letter INSPECTION SUMMARY
10/14/2025 Letter INSPECTION SUMMARY
10/15/2025 Letter INSPECTION SUMMARY
10/27/2025 Letter INSPECTION SUMMARY
10/27/2025 Letter INSPECTION SUMMARY
10/27/2025 Letter INSPECTION SUMMARY
10/27/2025 Letter INSPECTION SUMMARY
10/29/2025 Letter INSPECTION SUMMARY
10/29/2025 Letter INSPECTION SUMMARY
10/29/2025 Letter INSPECTION SUMMARY
10/29/2025 Letter INSPECTION SUMMARY
10/30/2025 Letter INSPECTION SUMMARY
11/03/2025 Letter INSPECTION SUMMARY
11/05/2025 Letter INSPECTION SUMMARY
11/14/2025 Letter INSPECTION SUMMARY
11/25/2025 Letter INSPECTION SUMMARY
11/25/2025 Letter INSPECTION SUMMARY
12/15/2025 Engineer Report/Study Comment Response #3 & #7 REO Engineering
12/17/2025 Letter INSPECTION SUMMARY
12/17/2025 Letter INSPECTION SUMMARY
12/22/2025 Letter INSPECTION SUMMARY
02/19/2026 Letter INSPECTION SUMMARY
02/19/2026 Letter INSPECTION SUMMARY
02/24/2026 Letter INSPECTION SUMMARY
02/27/2026 Letter INSPECTION SUMMARY
03/02/2026 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home