Permit Application Status

PRRES20243632


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20243632
Building Permit - Residential
Certificate of Occupancy
CMH PARKS INC
NEW SINGLE FAMILY
NEW HOUSE - UNFINISHED BASEMENT - ROOF TRUSSES STOP WORK ORDER generated on 08/22/2024 12:00 AM by username 'Mitchell Schwarz'. STOP WORK ORDER removed on 09/06/2024 12:00 AM by username 'Mitchell Schwarz'.
07/16/2024
07/25/2024
01/13/2025
10/02/2025
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:10450 Holmes Rd Suite 100, Phone:(816) 246-6700  
CMH PARKS INC, Address:5000 CLAYTON RD  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
BRUCER@SUMMITHOMESKC.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
Sanitary Sewer Development Fee $2,285.00 $2,285.00 Paid 07/25/2024
Right of Way Permit Fee $85.00 $85.00 Paid 07/25/2024
Residential Excise Tax Fee $1,022.72 $1,022.72 Paid 07/25/2024
Water Tap Fee $3,973.00 $3,973.00 Paid 07/25/2024
Water Meter Fee $748.03 $748.03 Paid 07/25/2024
Valuation Fee New Single Family $1,350.06 $1,350.06 Paid 07/25/2024
Not Ready Inspection Fee $75.00 $75.00 Paid 12/04/2024
Not Ready Inspection Fee $75.00 $75.00 Paid 12/04/2024
Temporary Occupancy Fee $50.00 $50.00 Paid 12/26/2024
Temporary Occupancy Fee $50.00 $50.00 Paid 01/16/2025
Temporary Occupancy Fee $50.00 $50.00 Paid 03/13/2025
Temporary Occupancy Fee $50.00 $50.00 Paid 03/13/2025
Temporary Occupancy Fee $50.00 $50.00 Paid 04/15/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Sewer Service Inspection - R Passed 8/21/2024 8/21/2024 08/21/2024
Water Service Inspection - R Passed 8/22/2024 8/22/2024 08/22/2024
Footing Inspection - Residential Failed - Stop Work 8/22/2024 08/22/2024
Misc
Corrective Action Required
08/22/2024
Footing poured without inspection
Footing Inspection - Residential Passed 9/6/2024 9/6/2024 09/06/2024
Misc
Resolved
09/06/2024
Footing poured without inspection
Underslab Plumbing Inspection - Residential Passed 9/9/2024 9/9/2024 09/09/2024
All Rough Inspection - Residential Failed 9/26/2024 9/26/2024 09/26/2024
Misc
Corrective Action Required
09/26/2024
- NAIL PATTERN OUTSIDE OK - HEADER TO JACK-STUD STRAP PER TABLE R602.10.6.4 ON BOTH SIDES OF OPENING OPPOSITE SIDE SHEATHING
All Rough Inspection - Residential Not Ready 10/18/2024 10/18/2024 10/18/2024
Misc
Corrective Action Required
09/26/2024
10/18/24- no city stamped plans on site inspection denied PORTAL FRAM INSPECTION ONLY - NAIL PATTERN OUTSIDE OK - HEADER TO JACK-STUD STRAP PER TABLE R602.10.6.4 ON BOTH SIDES OF OPENING OPPOSITE SIDE SHEATHING
All Rough Inspection - Residential Failed 10/22/2024 10/22/2024 10/22/2024
Misc
Resolved
10/22/2024
10/18/24- no city stamped plans on site inspection denied PORTAL FRAM INSPECTION ONLY - NAIL PATTERN OUTSIDE OK - HEADER TO JACK-STUD STRAP PER TABLE R602.10.6.4 ON BOTH SIDES OF OPENING OPPOSITE SIDE SHEATHING
Misc
Corrective Action Required
10/22/2024
-anchor bolts to be I. The middle 1/3 of sill plate. (See portal frame) -block all sheathing breaks in garage -address open electrical at front door -address bath vents above primary bath -provide blocking under kitchen island -anchor all steel columns in basement
All Rough Inspection - Residential Failed 10/25/2024 10/25/2024 10/25/2024
Misc
Corrective Action Required
10/22/2024
-anchor bolts to be I. The middle 1/3 of sill plate. (See portal frame)
All Rough Inspection - Residential Not Ready 10/28/2024 10/28/2024 10/28/2024
Misc
Corrective Action Required
10/25/2024
-anchor bolts to be In The middle 1/3 of sill plate. (See portal frame)
Piers/Caissons Inspection - Residential Passed 10/29/2024 10/29/2024 10/29/2024
All Rough Inspection - Residential Passed 10/30/2024 10/30/2024 10/30/2024
Misc
Resolved
10/30/2024
-anchor bolts to be I. The middle 1/3 of sill plate. (See portal frame)
Gas Service Inspection - Residential Passed 11/8/2024 11/8/2024 11/08/2024
Electrical Service Inspection Passed 11/8/2024 11/8/2024 11/08/2024
Driveway Inspection Partial 12/3/2024 12/3/2024 12/03/2024
Misc
Informational
12/03/2024
12-2-24 Dustin A, DW is formed and compacted. Slopes are in compliance. Approved to pour
Sidewalk Inspection Partial 12/3/2024 12/3/2024 12/03/2024
Misc
Informational
12/03/2024
12-2-24 Dustin A, SW is formed and compacted and slopes are in compliace. Approved to pour
Driveway Inspection Passed 12/10/2024 12/10/2024 12/10/2024
Misc
Informational
12/03/2024
12-2-24 Dustin A, DW is formed and compacted. Slopes are in compliance. Approved to pour 12-10-24 Dustin A, DW is poured to city specs and slopes are in compliance. Pass
Sidewalk Inspection Failed 12/10/2024 12/10/2024 12/10/2024
Misc
Informational
12/03/2024
12-2-24 Dustin A, SW is formed and compacted and slopes are in compliace. Approved to pour 12-10-24 Dustin A, SW is poured. Slopes are in compliance. One trip hazard on right side of approach. Cannot pass until that is fixed and forms pulled
Occupancy Inspection - Codes Residential Failed 12/23/2024 12/23/2024 12/23/2024
Misc
Corrective Action Required
12/23/2024
-provide as graded plot plan. -final grade and sod -obtain issued lawn irrigation permit -address pending sidewalk inspection -splash blocks and sump pump discharge to extend 36” from foundation -all outlets in garage to be gfci protected or single pull receptacle and labeled -
Occupancy Inspection - Codes Residential Ready for Temp CO 12/24/2024 12/24/2024 12/24/2024
Misc
Corrective Action Required
12/23/2024
-provide as graded plot plan. -final grade and sod -obtain issued lawn irrigation permit -address pending sidewalk inspection -splash blocks and sump pump discharge to extend 36” from foundation
Sidewalk Inspection Passed 12/27/2024
Misc
Informational
12/10/2024
12-2-24 Dustin A, SW is formed and compacted and slopes are in compliace. Approved to pour 12-10-24 Dustin A, SW is poured. Slopes are in compliance. One trip hazard on right side of approach. Cannot pass until that is fixed and forms pulled 12-27-24 Dustin A, SW has been corrected
Occupancy Inspection - Codes Residential Ready for Temp CO 1/16/2025 01/16/2025
Misc
Corrective Action Required
12/24/2024
TCO EXTENSION GRANTED FOR ANOTHER 30 DAYS. -provide as graded plot plan. -final grade and sod -obtain issued lawn irrigation permit -address pending sidewalk inspection -splash blocks and sump pump discharge to extend 36” from foundation
Plot Plan Inspection Failed 4/4/2025 04/04/2025
Misc
Corrective Action Required
04/04/2025
Inspection denied erosion control not in compliance
Erosion Control Inspection Residential Failed 04/04/2025
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
04/04/2025
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. EROSION CONTROL INSTALL IS NOT ADEQUATELY RETAILING SILT
Erosion Control Inspection Residential Passed 4/15/2025 4/15/2025 04/15/2025
DCM2 ESC DEFICIENT INSTALLATION
Resolved
04/15/2025
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. EROSION CONTROL INSTALL IS NOT ADEQUATELY RETAILING SILT
Occupancy Inspection - Codes Residential Ready for Temp CO 4/15/2025 04/15/2025
Misc
Corrective Action Required
01/16/2025
As graded plot plan submited, but needs 6' of fall on 3 sides of house and storn inlet cleaned. Can see that lot slopes back to house simply by looking at fence. TCO extended for 30 days
Occupancy Inspection - Codes Residential Failed 4/16/2025 4/16/2025 04/16/2025
Misc
Corrective Action Required
04/15/2025
As graded plot plan submited, but needs 6' of fall on 3 sides of house and storn inlet cleaned. Can see that lot slopes back to house simply by looking at fence. TCO extended for 30 days
Occupancy Inspection - Codes Residential Failed 5/15/2025 05/15/2025
Misc
Corrective Action Required
04/16/2025
As graded plot plan submited, but needs 6' of fall on 3 sides of house and storn inlet cleaned. Can see that lot slopes back to house simply by looking at fence. TCO extended for 30 days
Plot Plan Inspection Passed 10/2/2025 10/02/2025
Misc
Corrective Action Required
04/04/2025
Inspection denied erosion control not in compliance
Occupancy Inspection - Codes Residential Full C of O 10/2/2025 10/02/2025
Misc
Resolved
10/02/2025
As graded plot plan submited, but needs 6' of fall on 3 sides of house and storn inlet cleaned. Can see that lot slopes back to house simply by looking at fence. TCO extended for 30 days
Documents & Images
Date Uploaded File Type Document Name
07/16/2024 H3 #77 - ENGINEERED PLANS
07/16/2024 H3 #77 - PERMIT APP
07/16/2024 H3 #77 - PLOT PLAN
07/16/2024 H3 #77 - TRUSS DETAILS
07/16/2024 H3 #77 - TRUSS LAYOUT
07/17/2024 Permit Codes Residential Plan Review
07/17/2024 Approved Plans APPROVED PLANS
07/17/2024 Approved Plans APPROVED TRUSS LAYOUT
07/17/2024 Approved Plans APPROVED TRUSS PACKAGE
07/24/2024 LOT 77 CITY 7-24-24
07/24/2024 Plot Plan APPROVED PLOT PLAN
07/24/2024 Permit Codes Residential Plan Review
07/25/2024 Permit DS Building Permit
07/25/2024 Receipt Receipt for transaction:2024-006208
08/21/2024 Letter INSPECTION SUMMARY
08/22/2024 Letter INSPECTION SUMMARY
08/22/2024 Letter Stop Work Order
09/05/2024 M L Crose 1538 SW Arbor Falls Dr LSMO Hawthorn Ridge Lot 77 Permit 2024-3632 3rd Party Footing Inspection Report 8-14-24
09/06/2024 Letter INSPECTION SUMMARY
09/09/2024 Letter INSPECTION SUMMARY
09/26/2024 Letter INSPECTION SUMMARY
10/18/2024 Letter INSPECTION SUMMARY
10/22/2024 Letter INSPECTION SUMMARY
10/25/2024 Letter INSPECTION SUMMARY
10/28/2024 Letter INSPECTION SUMMARY
10/29/2024 Letter INSPECTION SUMMARY
10/29/2024 Letter INSPECTION SUMMARY
10/30/2024 Letter INSPECTION SUMMARY
11/08/2024 Letter INSPECTION SUMMARY
11/08/2024 Letter INSPECTION SUMMARY
12/03/2024 Letter INSPECTION SUMMARY
12/03/2024 Letter INSPECTION SUMMARY
12/04/2024 Receipt Receipt for transaction:2024-009332
12/10/2024 Letter INSPECTION SUMMARY
12/10/2024 Letter INSPECTION SUMMARY
12/10/2024 Letter INSPECTION SUMMARY
12/23/2024 Letter INSPECTION SUMMARY
12/24/2024 Letter INSPECTION SUMMARY
12/26/2024 Certificate/License Codes Temporary Certificate of Occupancy
12/26/2024 Receipt Receipt for transaction:2024-009658
12/27/2024 Letter INSPECTION SUMMARY
01/15/2025 Application Form HT #77 - TCO Extension App 1_15_25
01/16/2025 Letter INSPECTION SUMMARY
01/16/2025 Certificate/License Codes Temporary Certificate of Occupancy
01/16/2025 Receipt Receipt for transaction:2025-000268
02/05/2025 Application Form TCO EXTENSION APPLICATION
03/13/2025 Certificate/License Codes Temporary Certificate of Occupancy
03/13/2025 Certificate/License Codes Temporary Certificate of Occupancy
03/13/2025 Receipt Receipt for transaction:2025-001549
04/03/2025 LOT 77 ASBUILT 4-3-25
04/03/2025 Plot Plan APPROVED AS GRADED PLOT PLAN
04/04/2025 Letter INSPECTION SUMMARY
04/04/2025 Letter INSPECTION SUMMARY
04/15/2025 Certificate/License Codes Temporary Certificate of Occupancy
04/15/2025 Receipt Receipt for transaction:2025-002328
04/16/2025 Letter INSPECTION SUMMARY
04/16/2025 Letter INSPECTION SUMMARY
04/16/2025 Letter INSPECTION SUMMARY
05/06/2025 HT #77 - TCO Extension App 5_6_25
05/15/2025 Letter Permit Expired Notice
05/15/2025 Letter INSPECTION SUMMARY
10/02/2025 Letter INSPECTION SUMMARY
10/02/2025 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home