Permit Application Status

PRRES20240726


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20240726
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE. FINISHED BASEMENT. WALKOUT BASEMENT. COVERED DECK.
02/20/2024
03/05/2024
08/28/2024
12/02/2024
Locations
Contacts
WALKER CUSTOM HOMES, LLC, Address:PO BOX 3194, Phone:(913) 208-2026  
Jason walker, Address:PO Box 247, Phone:(913) 208-2026  
5 STAR HEATING & COOLING, Address:211 NW 12TH, Phone:(816) 517-3341  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
TRI-COUNTY PLUMBING LLC, Address:PO BOX 234, Phone:(816) 720-3222  
WALKERCUSTOMHOMESKC@GMAIL.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331401-Water Tap Fee $3,760.00 $3,760.00 Paid 03/05/2024
8350015-Water Meter Fee $680.46 $680.46 Paid 03/05/2024
8331507-Sanitary Sewer Development Fee $2,159.00 $2,159.00 Paid 03/05/2024
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 03/05/2024
7232302-Residential License Tax Fee $1,022.72 $1,022.72 Paid 03/05/2024
9110078-Valuation Fee New Single Family $2,518.02 $2,518.02 Paid 03/05/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 3/25/2024 03/25/2024
Sewer Service Inspection - R Passed 3/26/2024 03/26/2024
Water Service Inspection - R Partial 3/27/2024 03/26/2024
Misc
Informational
03/26/2024
Pex ran roughly 15’ from foundation
Underslab Plumbing Inspection - Residential Passed 3/27/2024 3/27/2024 03/27/2024
Water Service Inspection - R Passed 3/27/2024 03/27/2024
Misc
Resolved
03/27/2024
Pex ran roughly 15’ from foundation
Electrical Service Inspection Passed 7/2/2024 7/2/2024 07/02/2024
Gas Service Inspection - Residential Failed 7/2/2024 7/2/2024 07/02/2024
Misc
Corrective Action Required
07/02/2024
No pressure at gas gauge for inspection
All Rough Inspection - Residential Failed 7/2/2024 7/2/2024 07/02/2024
Misc
Corrective Action Required
07/02/2024
NO FURTHER INSPECTIONS UNTIL EROSION CONTROL IS IN COMPLIANCE -address anchor bolts for garage back wall sill plate -missing stud in stud pack each end of beam in garage -missing stud at short wall left of rear slider -complete bath fan duct in master bath -address rafter bearing throughout -no pressure at gauge for gas inspection
Erosion Control Inspection Residential Failed 7/2/2024 07/02/2024
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
07/02/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. Address overgrown vegetation
All Rough Inspection - Residential Failed 7/12/2024 7/12/2024 07/12/2024
Misc
Corrective Action Required
07/02/2024
NO FURTHER INSPECTIONS UNTIL EROSION CONTROL IS IN COMPLIANCE -address anchor bolts for garage back wall sill plate (seal holes made in bottom plate in this area) -missing stud at short wall left of rear slider(stud over notched) -address rafter bearing throughout (fix to engineer specifications nailing and decree used)
Gas Service Inspection - Residential Passed 7/12/2024 7/12/2024 07/12/2024
Misc
Resolved
07/12/2024
No pressure at gas gauge for inspection
All Rough Inspection - Residential Passed 7/15/2024 7/15/2024 07/15/2024
Misc
Resolved
07/15/2024
Driveway Inspection Partial 8/5/2024 8/5/2024 08/06/2024
Misc
Informational
08/06/2024
8-6-24 Dustin A, DW is formed to city specs and aggregate is compacted, approved to pour
Sidewalk Inspection Partial 8/5/2024 8/5/2024 08/06/2024
Misc
Informational
08/06/2024
8-6-24 Dustin A Sw is formed and contacted to city specs. Slopes are in compliance . Approved to pour
Driveway Inspection Passed 8/13/2024 8/13/2024 08/13/2024
Misc
Informational
08/06/2024
8-6-24 Dustin A, DW is formed to city specs and aggregate is compacted, approved to pour 8-13-24 Dustin A, Dw is poured to city specs and slopes are in compliance, Pass
Sidewalk Inspection Passed 8/13/2024 8/13/2024 08/13/2024
Misc
Informational
08/06/2024
8-6-24 Dustin A Sw is formed and contacted to city specs. Slopes are in compliance . Approved to pour 8-13-24 Dustin A, Sw is formed to city specs an slopes are in compliance. Passed
Plot Plan Inspection Passed 9/3/2024 09/03/2024
Occupancy Inspection - Codes Residential Failed 11/6/2024 11/6/2024 11/06/2024
Misc
Corrective Action Required
11/06/2024
Inspection denied -no erosion control -maintain overgrown vegetation
Erosion Control Inspection Residential Failed 11/6/2024 11/6/2024 11/06/2024
DCM3 ESC REQUIRED 2 DAY
Resolved
11/06/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. Address overgrown vegetation Address
DCM5 ESC INSP DENIED
Corrective Action Required
11/06/2024
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION.
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
11/06/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Erosion Control Inspection Residential Passed 11/25/2024 11/25/2024
DCM5 ESC INSP DENIED
Resolved
11/25/2024
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION.
DCM3 ESC REQUIRED 2 DAY
Resolved
11/25/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Occupancy Inspection - Codes Residential Failed 11/25/2024 11/25/2024 11/25/2024
Misc
Resolved
11/25/2024
Inspection denied -no erosion control -maintain overgrown vegetation
Miscellaneous Correction
Corrective Action Required
11/25/2024
-Front porch GFCI receptacle is not fully secured into the wall within the protective bubble -Remove dust cover from basement CO detector -Seal top of AC disconnect -Water meter height in pit could not be inspected because of water in the pit
Occupancy Inspection - Codes Residential Full C of O 12/2/2024 12/2/2024 12/02/2024
Miscellaneous Correction
Resolved
12/02/2024
-Front porch GFCI receptacle is not fully secured into the wall within the protective bubble -Remove dust cover from basement CO detector -Seal top of AC disconnect -Water meter height in pit could not be inspected because of water in the pit
Documents & Images
Date Uploaded File Type Document Name
02/22/2024 Permit Codes Residential Plan Review
03/01/2024 Plot Plan APPROVED PLOT PLAN
03/01/2024 Permit Codes Residential Plan Review
03/04/2024 Application Form APPLICATION
03/04/2024 Application Form APPROVED PLANS
03/04/2024 Permit Codes Residential Plan Review
03/05/2024 Excise tax page 1
03/05/2024 Excise tax page 2
03/05/2024 Excise tax page 3
03/05/2024 Excise tax page 4
03/05/2024 Permit DS Building Permit
03/05/2024 Receipt Receipt for transaction:2024-001327
03/23/2024 3RD Party Insp Report Wilmoth 2234 SW Crown Dr LSMO Hook Farms Lot 200 Footing Inspection Report 3-15-24
03/25/2024 Letter INSPECTION SUMMARY
03/26/2024 Letter INSPECTION SUMMARY
03/26/2024 Letter INSPECTION SUMMARY
03/27/2024 Letter INSPECTION SUMMARY
03/27/2024 Letter INSPECTION SUMMARY
04/15/2024 3RD Party Insp Report THIRD PARTY INSPECTION
04/16/2024 3RD Party Insp Report THIRD PARTY INSPECTION
07/02/2024 Letter INSPECTION SUMMARY
07/02/2024 Letter INSPECTION SUMMARY
07/02/2024 Letter INSPECTION SUMMARY
07/02/2024 Letter INSPECTION SUMMARY
07/09/2024 3RD Party Insp Report THIRD PARTY FRAMING INSPECTION
07/12/2024 Letter INSPECTION SUMMARY
07/12/2024 Letter INSPECTION SUMMARY
08/06/2024 Letter INSPECTION SUMMARY
08/06/2024 Letter INSPECTION SUMMARY
08/13/2024 Letter INSPECTION SUMMARY
08/13/2024 Letter INSPECTION SUMMARY
08/30/2024 Plot Plan APPROVED AS BUILT PLOT PLAN
09/03/2024 Letter INSPECTION SUMMARY
09/03/2024 Letter INSPECTION SUMMARY
11/06/2024 Letter INSPECTION SUMMARY
11/06/2024 Letter INSPECTION SUMMARY
11/25/2024 Letter INSPECTION SUMMARY
11/25/2024 Letter INSPECTION SUMMARY
12/02/2024 Letter Field Certificate of Occupancy
12/02/2024 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home