Permit Application Status

PRRES20222104


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20222104
Building Permit - Residential
Certificate of Occupancy
WHISPERING WOODS LAND LLC
NEW SINGLE FAMILY
NEW HOUSE. UNFINISHED BASEMENT. COVERED DECK.
05/17/2022
05/24/2022
11/14/2022
08/29/2023
Locations
Contacts
NEW MARK HOMES - KC LLC, Address:5207 NW CROOKED ROAD, Phone:(816) 969-9010  
WHISPERING WOODS LAND LLC, Address:803 PCA ROAD  
Ashley Kirby, Address:5207 NW Crooked Rd, Phone:(816) 969-9010  
HARRINGTON BROTHERS HEATING & COOLING, Address:15630 S KEELER ST, Phone:(913) 422-5444  
PREMIER ELECTRIC & LIGHTING DESIGN, Address:PO BOX 1311, Phone:(816) 564-7660  
R & R PLUMBING INC, Address:2001 GASLIGHT DR, Phone:(816) 772-5431  
CBRUNING@NEWMARKHOMESKC.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sewer Connection Fee $570.00 $570.00 Paid 05/24/2022
8331401-Water Tap Fee $3,655.00 $3,655.00 Paid 05/24/2022
8350015-Water Meter Fee $479.24 $479.24 Paid 05/24/2022
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 05/24/2022
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 05/24/2022
9110078-Valuation Fee New Single Family $1,440.05 $1,440.05 Paid 05/24/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 6/30/2022 06/30/2022
Sewer Service Inspection - R Passed 8/10/2022 (8:45) 8/10/2022 08/10/2022
Water Service Inspection - R Partial 8/15/2022 08/15/2022
Water Service Inspection - R Passed 8/16/2022 08/16/2022
Underslab Plumbing Inspection - Residential Passed 8/24/2022 8/24/2022 08/24/2022
Gas Service Inspection - Residential Failed 2/1/2023 2/1/2023 02/01/2023
Misc
Corrective Action Required
02/01/2023
Pressure ok Bond gas line
Electrical Service Inspection Passed 2/1/2023 2/1/2023 02/01/2023
All Rough Inspection - Residential Failed 2/1/2023 2/1/2023 02/01/2023
Misc
Corrective Action Required
02/01/2023
-missing hanger on triple lvl above garage -fire block furr out wall in garage to ceiling space -address over notched wall stud for anchor bolt garage E wall -fire block garage N wall into furr down -provide weld certificate for beams welded together -furr out for pex in dining -fire block dining room E wall to ceiling space -address holes drilled closer than 2” to one another above dining room -address penetration in top plate above laundry -stud packs above fire place for 2nd story -stud pack in bed 4 closet -collar ties for ridge above 2nd story hall -address cut joist above basement mechanical area -bond gas line -solid block 48” OC in basement per plans -address holes drilled closer than 2” to each other in double for pex NE basement
All Rough Inspection - Residential Passed 2/10/2023 2/10/2023 02/10/2023
Misc
Resolved
02/10/2023
-missing hanger on triple lvl above garage -fire block furr out wall in garage to ceiling space -address over notched wall stud for anchor bolt garage E wall -fire block garage N wall into furr down -provide weld certificate for beams welded together -furr out for pex in dining -fire block dining room E wall to ceiling space -address holes drilled closer than 2” to one another above dining room -address penetration in top plate above laundry -stud packs above fire place for 2nd story -stud pack in bed 4 closet -collar ties for ridge above 2nd story hall -address cut joist above basement mechanical area -bond gas line -solid block 48” OC in basement per plans -address holes drilled closer than 2” to each other in double for pex NE basement
Gas Service Inspection - Residential Passed 2/10/2023 2/10/2023 02/10/2023
Misc
Resolved
02/10/2023
Pressure ok Bond gas line
Driveway Inspection Partial 3/7/2023 3/7/2023 03/07/2023
Misc
Informational
03/07/2023
3-7-23 RH. Driveway is formed up and aggregate is placed and compacted. Approved to pour.
Erosion Control Inspection Residential Failed 3/17/2023 3/17/2023 03/17/2023
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
03/17/2023
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
03/17/2023
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Erosion Control Inspection Residential Failed 04/28/2023
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
04/28/2023
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
DCM2 ESC DEFICIENT INSTALLATION
Resolved
04/28/2023
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
04/28/2023
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Erosion Control Inspection Residential Failed 07/20/2023
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
04/28/2023
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. Maintain silt fence and overgrown vegetation
Piers/Caissons Inspection - Residential Passed 08/10/2023
Occupancy Inspection - Codes Residential Failed 8/10/2023 8/10/2023 08/10/2023
Misc
Corrective Action Required
08/10/2023
-Address pending driveway inspection -Provide as graded plot plan -secure A/c whip within 12” of disconnect -splash blocks to extend 36” from foundation -identify sewer tracer wire. -address deck post to beam connections and deck post to be continuous per plans.
Driveway Inspection Passed 8/10/2023 8/10/2023 08/10/2023
Misc
Informational
03/07/2023
3-7-23 RH. Driveway is formed up and aggregate is placed and compacted. Approved to pour. 8-10-23 PS Driveway approach meets LS specifications
Plot Plan Inspection Passed 8/14/2023 08/14/2023
Erosion Control Inspection Residential Passed 08/29/2023
DCM3 ESC REQUIRED 2 DAY
Resolved
08/29/2023
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. Maintain silt fence and overgrown vegetation
Occupancy Inspection - Codes Residential Full C of O 8/29/2023 8/29/2023 08/29/2023
Misc
Resolved
08/29/2023
-Address pending driveway inspection -Provide as graded plot plan -secure A/c whip within 12” of disconnect -splash blocks to extend 36” from foundation
Documents & Images
Date Uploaded File Type Document Name
05/17/2022 1940_001
05/18/2022 Permit Codes Residential Plan Review
05/20/2022 Approved Plans APPROVED PLANS
05/20/2022 Plot Plan APPROVED PLOT PLAN
05/20/2022 Permit Codes Residential Plan Review
05/24/2022 Permit DS Building Permit
05/24/2022 Receipt Receipt for transaction:2022-003874
06/30/2022 Letter INSPECTION SUMMARY
08/10/2022 Letter INSPECTION SUMMARY
08/15/2022 Letter INSPECTION SUMMARY
08/24/2022 Letter INSPECTION SUMMARY
08/31/2022 1608 SW 27th St_DECK PIER INSP_2022-08-26
11/08/2022 Final_2022_10_25_PortalFrame_LSMO_New Mark Homes
01/11/2023 Letter Codes 140 Day Letter
02/01/2023 Letter INSPECTION SUMMARY
02/01/2023 Letter INSPECTION SUMMARY
02/01/2023 Letter INSPECTION SUMMARY
02/01/2023 Letter INSPECTION SUMMARY
02/08/2023 2023_02_07_Lot 47 whispering woods_Compliance Letter(1)
02/08/2023 New Mark WW47 Weld Cert
02/10/2023 Letter INSPECTION SUMMARY
02/10/2023 Letter INSPECTION SUMMARY
03/07/2023 Letter INSPECTION SUMMARY
03/17/2023 Letter INSPECTION SUMMARY
04/28/2023 Letter INSPECTION SUMMARY
07/20/2023 Letter INSPECTION SUMMARY
08/10/2023 Letter INSPECTION SUMMARY
08/10/2023 Letter INSPECTION SUMMARY
08/10/2023 Letter INSPECTION SUMMARY
08/10/2023 Letter INSPECTION SUMMARY
08/11/2023 Plot Plan APPROVED AS BUILT PLOT PLAN
08/14/2023 Letter INSPECTION SUMMARY
08/29/2023 Letter INSPECTION SUMMARY
08/29/2023 Letter Field Certificate of Occupancy
08/29/2023 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home