Review Type |
Outcome |
Est. Completion Date |
Completed |
Plot Plan Review
|
Approved
|
04/22/2021
|
04/20/2021
|
|
Kim Brennan
|
|
|
Residential Plan Review
|
Approved
|
04/22/2021
|
04/20/2021
|
|
Kim Brennan
|
|
03 Two (2) plot plans
Corrective Action Required
plot plan is missing
|
|
06 Designate use of each room or space
Corrective Action Required
Designate use of each room or space including but not limited to; basement storage, garages, and attic areas intended for storage space.
Not designated for the finished basement
|
|
05 Provide square footage of living area, garage area, unfinished basement
Corrective Action Required
Provide square footage of living area, garage area, unfinished basement area, etc (IRC Section R304)
Not shown for the unfinished basement or covered deck
|
|
07 Identify emergency escape openings from bedrooms
Corrective Action Required
Identify emergency escape openings from bedrooms and basement(s). (IRC Section R310 as amended per Ordinance)
Please show egress locations
|
|
09 Identify furnace and water heater locations
Corrective Action Required
Identify furnace and water heater location(s). (IRC Section G2406)
Please identify furnace location
|
|
10 Combustion air
Corrective Action Required
Provide combustion air calculations and specify transfer air grilles for fuel burning appliances located in confined space(s). (IRC Chapter 17 and Section G2407)
|
|
14 Identify roof covering material (IRC Section R905)
Corrective Action Required
Identify roof covering material (IRC Section R905)
|
|
|
Plot Plan Review
|
Approved
|
04/16/2021
|
04/15/2021
|
|
Kim Brennan
|
|
Deck location
Corrective Action Required
Deck location, with dimensions to property lines must be provided on the plot plan.
Please show this as a covered patio
|
|
Easements
Corrective Action Required
All easements with dimensions must be provided on the plot plan.
Rear shows a 7.5' side yard but I think it is supposed to be a 7.5' U/E
|
|
Basement opening elevations
Corrective Action Required
Minimum Building Opening Elevation (MBOE) and location on structure must be provided on the plot plan.
|
|
As-graded plot plan
Corrective Action Required
A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy.
|
|
|
Residential Plan Review
|
Rejected
|
04/16/2021
|
04/14/2021
|
|
Kim Brennan
|
|
03 Two (2) plot plans
Corrective Action Required
plot plan is missing
|
|
06 Designate use of each room or space
Corrective Action Required
Designate use of each room or space including but not limited to; basement storage, garages, and attic areas intended for storage space.
Not designated for the finished basement
|
|
05 Provide square footage of living area, garage area, unfinished basement
Corrective Action Required
Provide square footage of living area, garage area, unfinished basement area, etc (IRC Section R304)
Not shown for the unfinished basement or covered deck
|
|
07 Identify emergency escape openings from bedrooms
Corrective Action Required
Identify emergency escape openings from bedrooms and basement(s). (IRC Section R310 as amended per Ordinance)
Please show egress locations
|
|
09 Identify furnace and water heater locations
Corrective Action Required
Identify furnace and water heater location(s). (IRC Section G2406)
Please identify furnace location
|
|
10 Combustion air
Corrective Action Required
Provide combustion air calculations and specify transfer air grilles for fuel burning appliances located in confined space(s). (IRC Chapter 17 and Section G2407)
|
|
14 Identify roof covering material (IRC Section R905)
Corrective Action Required
Identify roof covering material (IRC Section R905)
|
|
|
Plot Plan Review
|
Rejected
|
04/15/2021
|
04/14/2021
|
|
Kim Brennan
|
|
|
Residential Plan Review
|
Rejected
|
04/15/2021
|
04/13/2021
|
|
Kim Brennan
|
|
03 Two (2) plot plans
Corrective Action Required
plot plan is missing
|
|
06 Designate use of each room or space
Corrective Action Required
Designate use of each room or space including but not limited to; basement storage, garages, and attic areas intended for storage space.
Not designated for the finished basement
|
|
05 Provide square footage of living area, garage area, unfinished basement
Corrective Action Required
Provide square footage of living area, garage area, unfinished basement area, etc (IRC Section R304)
Not shown for the unfinished basement or covered deck
|
|
07 Identify emergency escape openings from bedrooms
Corrective Action Required
Identify emergency escape openings from bedrooms and basement(s). (IRC Section R310 as amended per Ordinance)
Please show egress locations
|
|
09 Identify furnace and water heater locations
Corrective Action Required
Identify furnace and water heater location(s). (IRC Section G2406)
Please identify furnace location
|
|
10 Combustion air
Corrective Action Required
Provide combustion air calculations and specify transfer air grilles for fuel burning appliances located in confined space(s). (IRC Chapter 17 and Section G2407)
|
|
14 Identify roof covering material (IRC Section R905)
Corrective Action Required
Identify roof covering material (IRC Section R905)
|
|
|