Permit Application Status

PRRES20211547


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20211547
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - ROOF TRUSSES - UNFINISHED BASEMENT - COVERED DECK
04/05/2021
04/07/2021
10/04/2021
10/14/2022
Locations
Contacts
ROESER HOMES LLC, Address:11415 STRANG LINE RD, Phone:(913) 220-7477  
MELISSA@ROESERHOMES.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ELECTRICAL INVESTMENTS, Address:8014 REEDER ST, Phone:(816) 210-1597  
MILLER PLUMBING CO, Address:PO BOX 393 , Phone:(913) 851-1333  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 04/09/2021 04/07/2021
Brandon Kalwei
Side yard dimensions
Corrective Action Required
04/07/2021

The side yard dimensions must be provided on the plot plan. side yard on the south side needs to be minimum of 7.5'
Deck location
Corrective Action Required
04/07/2021

Deck location, with dimensions to property lines must be provided on the plot plan. dimensions from covered patio must be identified
Residential Plan Review Approved 04/09/2021 04/07/2021
Brandon Kalwei
Plot Plan Review Rejected 04/07/2021 04/05/2021
Brandon Kalwei
Side yard dimensions
Corrective Action Required
04/05/2021

The side yard dimensions must be provided on the plot plan. side yard on the south side needs to be minimum of 7.5'
Deck location
Corrective Action Required
04/05/2021

Deck location, with dimensions to property lines must be provided on the plot plan. dimensions from covered patio must be identified
Residential Plan Review Approved 04/07/2021 04/05/2021
Brandon Kalwei
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,604.25 $1,604.25 Paid 04/07/2021
8331507-Sewer Connection Fee $660.00 $660.00 Paid 04/07/2021
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 04/07/2021
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 04/07/2021
8331401-Water Tap Fee $3,581.00 $3,581.00 Paid 04/07/2021
8350015-Water Meter Fee $455.54 $455.54 Paid 04/07/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 10/10/2022
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 10/10/2022
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 10/10/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Erosion Control Inspection Residential Failed 12/16/2021 04/28/2021
Misc
Corrective Action Required
04/28/2021
-Establish erosion control within 48 hours -immediate street cleanup required -Remove debris from storm water inlet -no further inspections until issues are resolved
Miscellaneous Inspection Failed 04/28/2021
Misc
Corrective Action Required
04/28/2021
Post site address, no further inspections until resolved
Footing Inspection - Residential Passed 4/28/2021 (10:00) 4/28/2021 04/28/2021
Erosion Control Inspection Residential Failed 05/17/2021
Misc
Corrective Action Required
04/28/2021
-Establish erosion control within 48 hours -Remove debris from storm water inlet -no further inspections until issues are resolved
Miscellaneous Inspection Passed 05/17/2021
Misc
Resolved
05/17/2021
Post site address, no further inspections until resolved
Underslab Plumbing Inspection - Residential Failed 5/17/2021 5/17/2021 05/17/2021
Misc
Corrective Action Required
05/17/2021
Inspection denied due to noncompliance of erosion control inspection reports.
Water Service Inspection - R Passed 5/25/2021 (1:00) 5/25/2021 05/25/2021
Sewer Service Inspection - R Passed 5/25/2021 (1:00) 5/25/2021 05/25/2021
Underslab Plumbing Inspection - Residential Passed 6/4/2021 06/04/2021
Misc
Resolved
06/04/2021
All Rough Inspection - Residential Failed 7/27/2021 07/27/2021
Miscellaneous Correction
Corrective Action Required
07/27/2021
7-27-21 Portal Frame and Inspection: OK to cover exterior at PFH -Uncover front porch trusses for inspection -Remove siding and properly install truss screws or H2.5s at covered patio-do not cover
All Rough Inspection - Residential Failed 8/6/2021 8/6/2021 08/06/2021
Miscellaneous Correction
Corrective Action Required
07/27/2021
7-27-21 Portal Frame Inspection: OK to cover exterior at PFH -Uncover front porch trusses for inspection**incomplete covered. *rear covered patio truss ok.
All Rough Inspection - Residential Partial 9/24/2021 9/24/2021 09/24/2021
Miscellaneous Correction
Corrective Action Required
08/06/2021
7-27-21 Portal Frame Inspection: OK to cover exterior at PFH *rear covered patio truss ok. front ok
All Rough Inspection - Residential Not Ready 11/12/2021 11/12/2021 11/12/2021
Miscellaneous Correction
Corrective Action Required
09/24/2021
7-27-21 Portal Frame Inspection: OK to cover exterior at PFH *rear covered patio truss ok. front ok
Misc
Corrective Action Required
11/12/2021
NO INSPECTION PERFORMED - NOT READY NO CITY APPROVED PLANS ON SITE AT TIME OF INSPECTION
Gas Service Inspection - Residential Passed 11/16/2021 11/16/2021 11/16/2021
All Rough Inspection - Residential Not Ready 11/16/2021 11/16/2021 11/16/2021
Miscellaneous Correction
Corrective Action Required
11/12/2021
7-27-21 Portal Frame Inspection: OK to cover exterior at PFH *rear covered patio truss ok. front ok
Misc
Corrective Action Required
11/12/2021
-NO INSPECTION PERFORMED - NOT READY -NO CITY APPROVED PLANS ON SITE
Electrical Service Inspection Passed 11/16/2021 11/16/2021 11/16/2021
All Rough Inspection - Residential Not Ready 11/17/2021 11/17/2021 11/17/2021
Miscellaneous Correction
Corrective Action Required
11/16/2021
7-27-21 Portal Frame Inspection: OK to cover exterior at PFH *rear covered patio truss ok. front ok
Misc
Corrective Action Required
11/16/2021
- REVERSE LAYOUT AND NOT CITY STAMPED -NO INSPECTION PERFORMED - NOT READY -NO CITY APPROVED PLANS ON SITE
All Rough Inspection - Residential Failed 12/16/2021 12/16/2021 12/16/2021
Miscellaneous Correction
Informational
12/16/2021
7-27-21 Portal Frame Inspection: OK to cover exterior at PFH *rear covered patio truss ok. front ok
Misc
Corrective Action Required
11/17/2021
- Address vent penetration through roof at laundry - Nail off hangers in laundry - Install can light in hall by laundry - Nail truss hangers office - Nail truss hanger A5 upstairs front bedroom - Nail truss hanger B6, D1, B17 upstairs loft and back bedroom - Provide corrections for cut joist in basement behind furnace at dwv - Block out cantilever in basement - Nail joist hanger basement above bottom riser - Basement column C should be 3 1/2” not 3” - Install TJC37 at CJ14 per plan
All Rough Inspection - Residential Failed 12/16/2021 12/16/2021
Miscellaneous Correction
Informational
12/16/2021
7-27-21 Portal Frame Inspection: OK to cover exterior at PFH *rear covered patio truss ok. front ok
Misc
Corrective Action Required
12/16/2021
-Fire stop 3” dwv at front office rear wall , at ceiling height. -Missing truss hanger nails over door into front office -terminate Romex north office exterior wall -Fire stop hole through top plate left of dryer vent. - nail Dbl truss over stairs as loft. - support dwv 48” O.c. basement, mstr shower. -Aluminum bonding clamp on steel gas line with copper ground basement north wall. -support ducts in basement 10’o.c. (Office) -fire stop tub traps 1st floor south over kitchen . - fire stop flue chase 1st floor from joist space . See front ot 1/2 bath. - fire stop heat chase to joist space , see left side of closet 1st floor. - provide eng fix on truss over garage supported by blocking. - - Address vent penetration through roof at laundry - Nail off hangers in laundry - Install can light in hall by laundry - Nail truss hangers office - Nail truss hanger A5 upstairs front bedroom - Nail truss hanger B6, D1, B17 upstairs loft and back bedroom - Provide corrections for cut joist in basement behind furnace at dwv - Block out cantilever in basement - Nail joist hanger basement above bottom riser - Basement column C should be 3 1/2” not 3” - Install TJC37 at CJ14 per plan
All Rough Inspection - Residential Failed 1/25/2022 1/25/2022 01/25/2022
Miscellaneous Correction
Informational
12/16/2021
7-27-21 Portal Frame Inspection: OK to cover exterior at PFH *rear covered patio truss ok. front ok
Misc
Corrective Action Required
12/16/2021
-terminate Romex north office exterior wall - provide eng fix on truss over garage supported by blocking. -Provide corrections for cut joist in basement behind furnace at DWV
All Rough Inspection - Residential Failed 2/1/2022 02/01/2022
Miscellaneous Correction
Resolved
02/01/2022
7-27-21 Portal Frame Inspection: OK to cover exterior at PFH *rear covered patio truss ok. front ok
Misc
Corrective Action Required
01/25/2022
- provide fix on truss over garage supported by blocking.
All Rough Inspection - Residential Passed 2/4/2022 2/4/2022 02/04/2022
Misc
Resolved
02/04/2022
Erosion Control Inspection Residential Failed 2/22/2022 02/22/2022
Miscellaneous Correction
Corrective Action Required
02/22/2022
Repair silt fence Remove debris from street Clean storm inlet
Driveway Inspection Partial 4/8/2022 4/8/2022 04/08/2022
Misc
Informational
04/08/2022
Driveway is 34.5 feet wide. Forms were placed and aggregate was present and compacted. RP 4-8-22
Erosion Control Inspection Residential Failed 04/15/2022
Misc
Corrective Action Required
05/17/2021
-Establish erosion control within 48 hours -Remove debris from storm water inlet -no further inspections until issues are resolved
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
04/15/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Driveway Inspection Passed 4/22/2022 4/22/2022 04/22/2022
Misc
Informational
04/08/2022
Driveway is 34.5 feet wide. Forms were placed and aggregate was present and compacted. RP 4-8-22
Misc
Informational
04/22/2022
Finished driveway meets LS specs. RP 4-22-22
Occupancy Inspection - Codes Residential Failed 8/10/2022 08/10/2022
Misc
Corrective Action Required
08/10/2022
• pay all fees • Obtain irrigation permit and submit back flow certification • Final grading and sod • Splash blocks • Seal exterior penetrations • Sump discharge minimum of 36” from foundation • Address patio to grade, change grading or provide steps • Handrail on garage entry • Install garage entry door make self closing • Complete spindles on stairs to upstairs • Handrail must be continuous • Complete upstairs thermostat • Label non gfci outlet at sump pump • Provide lockouts for electrical panel • Add gravel to Egress window well
Erosion Control Inspection Residential Passed 10/07/2022
Miscellaneous Correction
Resolved
10/07/2022
Plot Plan Inspection Passed 10/07/2022
Occupancy Inspection - Codes Residential Failed 10/7/2022 10/7/2022 10/07/2022
Misc
Corrective Action Required
08/10/2022
• pay all fees • Submit back flow certification
Occupancy Inspection - Codes Residential Full C of O 10/14/2022
Misc
Resolved
10/14/2022
Documents & Images
Date Uploaded File Type Document Name
04/05/2021 Application Form APPLICATION
04/05/2021 Application Form License_Tax_Application
04/05/2021 Final Plot Plan - Lot 1487 WV
04/05/2021 Engineered Plan - Lot 1487 WV
04/05/2021 Approved Plans APPROVED PLANS
04/06/2021 Letter Codes Residential Plan Review
04/07/2021 Revised Final Plot Plan - Lot 1487 WV
04/07/2021 Plot Plan APPROVED PLOT PLAN
04/07/2021 Receipt Receipt for transaction:2021-001799
04/07/2021 Letter DS Building Permit
04/23/2021 Engineered Layout - Lot 1487 WV
04/23/2021 Sealed Truss Package - Lot 1487 WV
04/23/2021 Engineered TRUSS Plan - Lot 1487 WV
04/23/2021 Approved Plans APPROVED TRUSS DRAWINGS
04/23/2021 Approved Plans APPROVED TRUSS LAYOUT
04/28/2021 Letter INSPECTION SUMMARY
04/28/2021 Letter INSPECTION SUMMARY
04/28/2021 Letter INSPECTION SUMMARY
05/17/2021 Letter INSPECTION SUMMARY
05/17/2021 Letter INSPECTION SUMMARY
05/17/2021 Letter INSPECTION SUMMARY
05/25/2021 Letter INSPECTION SUMMARY
05/25/2021 Letter INSPECTION SUMMARY
06/04/2021 Letter INSPECTION SUMMARY
06/16/2021 3073 NW Thoreau Ln_ALL SLAB INSP_2021-06-10
07/27/2021 Letter INSPECTION SUMMARY
08/06/2021 Letter INSPECTION SUMMARY
09/24/2021 Letter INSPECTION SUMMARY
11/12/2021 Letter INSPECTION SUMMARY
11/16/2021 Letter INSPECTION SUMMARY
11/16/2021 Letter INSPECTION SUMMARY
11/16/2021 Letter INSPECTION SUMMARY
11/17/2021 Letter INSPECTION SUMMARY
12/16/2021 Letter INSPECTION SUMMARY
01/25/2022 Letter INSPECTION SUMMARY
02/01/2022 Letter INSPECTION SUMMARY
02/04/2022 Letter INSPECTION SUMMARY
02/22/2022 Letter INSPECTION SUMMARY
04/08/2022 Letter INSPECTION SUMMARY
04/15/2022 Letter INSPECTION SUMMARY
04/22/2022 Letter INSPECTION SUMMARY
08/10/2022 Letter INSPECTION SUMMARY
10/07/2022 Letter INSPECTION SUMMARY
10/07/2022 Letter INSPECTION SUMMARY
10/07/2022 Letter INSPECTION SUMMARY
10/10/2022 Receipt Receipt for transaction:2022-008138
10/14/2022 Extension Request Form copy 2
10/14/2022 Letter Codes Final Certificate of Occupancy
10/14/2022 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home