Summary
PRRES20211323
Building Permit - Residential
Certificate of Occupancy
SUMMIT VIEW FARMS DEVELOPMENT GROUP LLC
NEW SINGLE FAMILY
NEW HOUSE - UNFINISHED BASEMENT - COVERED PATIO
03/24/2021
03/25/2021
01/21/2022
05/09/2024
Locations
Contacts
SUMMIT VIEW FARMS DEVELOPMENT GROUP LLC, Address:13450 E STATE ROUTE 150  
BILL KENNEY & ASSOCIATES, Address:P O BOX 291, Phone:(816) 838-0552  
MIDWEST HEATING COOLING & PLUMBING, Address:13228 HOLMES RD, Phone:(816) 943-8513  
INHOME SYSTEMS LLC, Address:510 MISSION RD SW, Phone:(816) 372-0483  
A BRIGHT PLUMBING LLC, Address:18107 E 18TH TER N, Phone:(816) 215-0730  
BILLKENNEY9@GMAIL.COM  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 03/29/2021 03/25/2021
Kim Brennan
Residential Plan Review Approved 03/29/2021 03/25/2021
Kim Brennan
Misc
Corrective Action Required
03/25/2021

Electrical contractor does not have a valid business license
Plot Plan Review Approved 03/29/2021 03/25/2021
Kim Brennan
Residential Plan Review Rejected 03/29/2021 03/25/2021
Kim Brennan
Misc
Corrective Action Required
03/25/2021

Electrical contractor does not have a valid business license
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,402.16 $1,402.16 Paid 03/25/2021
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 03/25/2021
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 03/25/2021
8331507-Sewer Connection Fee $600.00 $600.00 Paid 03/25/2021
8331401-Water Tap Fee $3,581.00 $3,581.00 Paid 03/25/2021
8350015-Water Meter Fee $455.54 $455.54 Paid 03/25/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 10/31/2021
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 10/24/2022
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 04/20/2023
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 09/18/2023
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Erosion Control Inspection Residential Failed 5/25/2021 5/25/2021 05/25/2021
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
05/25/2021
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Erosion Control Inspection Residential Failed 6/25/2021 6/25/2021 06/25/2021
DCM2 ESC DEFICIENT INSTALLATION
Resolved
06/25/2021
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
06/25/2021
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Erosion Control Inspection Residential Failed 7/2/2021 7/2/2021 07/02/2021
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
06/25/2021
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Piers/Caissons Inspection - Residential Failed 9/13/2021 (10:00) 9/13/2021 09/13/2021
Misc
Corrective Action Required
09/13/2021
(2) 24" WIDE PIERS AT COVERED PATIO PER APPROVED ENGINEER PLANS
Sewer Service Inspection - R Passed 9/28/2021 (1:00) 9/28/2021 09/28/2021
Water Service Inspection - R Passed 9/29/2021 (8:30) 9/29/2021 09/29/2021
Underslab Plumbing Inspection - Residential Failed 9/30/2021 9/30/2021 09/30/2021
Misc
Corrective Action Required
09/30/2021
9/30/21 - INSPECTED DYE TEST FOR UNDERSLAB PLUMBING WASTE PERFORMED BY PLUMBING CONTRACTOR, DYE TEST ACCEPTABLE, NO VISUAL INSPECTION OF UNDERSLAB PLUMBING PERFORMED, UNDERSLAB WAS POURED WITHOUT INSPECTION SUBMIT LETTERS FROM BUILDER, PLUMBER, AND INTERIOR DRAIN TILE CONTRACTORS AS REQUESTED BY INSPECTION MANAGER MARK HARDING
All Rough Inspection - Residential Not Ready 10/28/2021 10/28/2021 10/28/2021
Misc
Corrective Action Required
10/28/2021
INSPECTION DENIED -ADDRESS EROSION CONTROL ON LOT. MAINTAIN SILT FENCE ON LOT -ADDRESS COVERED PATIO PIERS THAT HAVE BEEN POURED WITHOUT REINSPECTION, SEE FAILED PIER INSPECTION REPORT FROM 9/13/21, (2) 24" WIDE PIERS AT COVERED PATIO PER APPROVED PLANS
All Rough Inspection - Residential Failed 11/1/2021 11/1/2021 11/01/2021
Misc
Corrective Action Required
10/28/2021
-ADDRESS COVERED PATIO PIERS THAT HAVE BEEN POURED WITHOUT REINSPECTION, SEE FAILED PIER INSPECTION REPORT FROM 9/13/21, (2) 24" WIDE PIERS AT COVERED PATIO PER APPROVED PLANS (RESOLVE PIERS BEFORE SCHEDULING ALL ROUGH REINSPECTION) -Fir down at HVAC garage ceiling to allow for insulation -Address overnotched floor joist for DWV at garage -Anchor bolts required within 12” of plate break at garage -Joist hanger at ceiling joist to header, south side garage -Fireblock between top plates at dbl wall shower 1st floor -seal all top plate penetrations -1st floor bath, 2nd floor north bed closet -stud shoes, DWV stud penetration at kitchen exterior wall -seal all penetrations through air returns, studs and floor joist cavities -Fireblock vertical to horizontal at great room plumbing chase -protect pex against recessed can light great room -Fireblock between top plates at dbl wall fridge kitchen, seal low volt floor penetration -12” oc nailing at all abutting in and intersecting wall corners (braced walls) -Install front door -ceiling joist rafter connection , west bed exterior wall 2nd floor, 2nd floor master bed -seal low volt bottom plate penetration, 2nd floor bedroom west -Dbl top plate requires min 24” offset between plate breaks - see master bed 2nd floor west exterior wall -Secure all vertical DWV 2” or less at mid point - see 2nd floor -Protection plates at top and bottom plate DWV laundry, fireblock at top plate to attic space -Protect NM (romex) within 6’ of attic entrance -2nd floor b vent requires 1” clearance from combustibles -rafter collar ties every 48” o.c. -2nd floor brace purlin at load bearing wall and not box vault at master bedroom -Complete electrical at service panel -Tighten panel bonding screw -Secure SEC cable above service panel -Not approved use of ground clamps to connect multiple pieces of rebar at UFER, UFER needs to remain accessible at finish -rear covered patio covered without inspection -Nail all exterior sheathing per plans
Gas Service Inspection - Residential Failed 11/1/2021 11/1/2021 11/01/2021
Misc
Corrective Action Required
11/01/2021
-SEE ELECTRICAL SERVICE INSPECTION FOR CORRECTIONS AT UFER BEFORE RELEASE OF GAS SERVICE -GAS PRESSURE OK
Electrical Service Inspection Failed 11/1/2021 11/1/2021 11/01/2021
Misc
Corrective Action Required
11/01/2021
-Complete electrical at service panel -Tighten panel bonding screw -Not approved use of ground clamps to connect multiple pieces of rebar at UFER, UFER needs to remain accessible at finish
Footing Inspection - Residential Passed 11/1/2021 11/1/2021 11/01/2021
Misc
Informational
11/01/2021
APPROVED PER DAVID P AINSWORT 4/14/21
Piers/Caissons Inspection - Residential Passed 11/17/2021 11/17/2021
Misc
Resolved
11/17/2021
(2) 24" WIDE PIERS AT COVERED PATIO PER APPROVED ENGINEER PLANS
Misc
Informational
11/17/2021
Engineer submitted alternate plan
Gas Service Inspection - Residential Passed 11/17/2021 11/17/2021 11/17/2021
Misc
Resolved
11/17/2021
-SEE ELECTRICAL SERVICE INSPECTION FOR CORRECTIONS AT UFER BEFORE RELEASE OF GAS SERVICE -GAS PRESSURE OK
Electrical Service Inspection Passed 11/17/2021 11/17/2021 11/17/2021
Misc
Resolved
11/17/2021
-Complete electrical at service panel -Tighten panel bonding screw -Not approved use of ground clamps to connect multiple pieces of rebar at UFER, UFER needs to remain accessible at finish
All Rough Inspection - Residential Failed 11/17/2021 11/17/2021 11/17/2021
Misc
Corrective Action Required
11/01/2021
-seal all top plate penetrations -1st floor bath, 2nd floor north bed closet -seal all penetrations through air returns, studs and floor joist cavities -Dbl top plate requires min 24” offset between plate breaks - see master bed 2nd floor west exterior wall -Protect NM (romex) within 6’ of attic entrance (see above hall)
All Rough Inspection - Residential Passed 11/23/2021 11/23/2021 11/23/2021
Misc
Resolved
11/23/2021
Erosion Control Inspection Residential Failed 3/16/2022 03/16/2022
DCM3 ESC REQUIRED 2 DAY
Resolved
03/16/2022
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
03/16/2022
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Driveway Inspection Partial 3/16/2022 3/16/2022 03/16/2022
Misc
Informational
03/16/2022
On 3.16.2022 I performed a driveway inspection and pass the subgrade to pour concrete
Driveway Inspection Passed 8/23/2022 08/23/2022
Misc
Informational
03/16/2022
On 3.16.2022 I performed a driveway inspection and pass the subgrade to pour concrete 8-28-22 RH. Driveway meets LS standard.
Sidewalk Inspection Partial 8/23/2022 08/23/2022
Misc
Informational
08/23/2022
8-28-22 RH. Sidewalk was formed up and aggregate was placed and compacted.
Sidewalk Inspection Passed 8/30/2022 8/30/2022 08/30/2022
Misc
Informational
08/23/2022
8-28-22 RH. Sidewalk was formed up and aggregate was placed and compacted. 8-30-33 RH. Sidewalk meets LS and ADA Specification.
Underslab Plumbing Inspection - Residential Passed 9/16/2022 09/16/2022
Misc
Resolved
09/16/2022
9/30/21 - INSPECTED DYE TEST FOR UNDERSLAB PLUMBING WASTE PERFORMED BY PLUMBING CONTRACTOR, DYE TEST ACCEPTABLE, NO VISUAL INSPECTION OF UNDERSLAB PLUMBING PERFORMED, UNDERSLAB WAS POURED WITHOUT INSPECTION SUBMIT LETTERS FROM BUILDER, PLUMBER, AND INTERIOR DRAIN TILE CONTRACTORS AS REQUESTED BY INSPECTION MANAGER MARK HARDING
Occupancy Inspection - Codes Residential Failed 9/16/2022 9/16/2022 09/16/2022
Misc
Corrective Action Required
09/16/2022
inspection denied no address posted.
Plot Plan Inspection Passed 9/19/2022 09/19/2022
Occupancy Inspection - Codes Residential Failed 9/19/2022 9/19/2022 09/19/2022
Misc
Resolved
09/19/2022
inspection denied no address posted.
Misc
Corrective Action Required
09/19/2022
-obtain lawn irrigation permit -sod -splash blocks and sump pump discharge to extend 36” from foundation -uncover water meter and bring meter pit ring and lid to grade -check meter depth in pit at time of sod -garage to be checked when converted back from sales office -handrail required at stairs in garage -garage door to be self closing and latching -stairs at rear patio door -label all non GFCI outlets in unfinished spaces
Occupancy Inspection - Codes Residential Failed 10/4/2022 10/4/2022 10/04/2022
Misc
Corrective Action Required
09/19/2022
-garage to be checked when converted back from sales office -address open electrical near A/c -garage door to be self closing AND LACTCHING -handrail required at stairs in garage handrail to meet code requirements 34-38” from nosing of tread to handrail
Erosion Control Inspection Residential Passed 10/24/2022 10/24/2022
DCM3 ESC REQUIRED 2 DAY
Resolved
10/24/2022
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Occupancy Inspection - Codes Residential Ready for Temp CO 10/24/2022 10/24/2022 10/24/2022
Misc
Corrective Action Required
09/19/2022
-obtain lawn irrigation permit (permit issued still needs paid for) -garage to be checked when converted back from sales office -tco will be issued for 6 months house used for sales office
Occupancy Inspection - Codes Residential Temporary C of O 10/24/2022 10/24/2022
Misc
Corrective Action Required
10/24/2022
-obtain lawn irrigation permit (permit issued still needs paid for) -garage to be checked when converted back from sales office -tco for 6 months house used for sales office
Occupancy Inspection - Codes Residential Ready for Temp CO 4/24/2023 04/20/2023
Misc
Corrective Action Required
10/24/2022
-obtain lawn irrigation permit (permit issued still needs paid for) -garage to be checked when converted back from sales office -tco for 6 months house used for sales office
Occupancy Inspection - Codes Residential Ready for Temp CO 9/18/2023 09/18/2023
Misc
Corrective Action Required
04/20/2023
-obtain lawn irrigation permit (permit issued still needs paid for) -garage to be checked when converted back from sales office -tco for 6 months house used for sales office
Occupancy Inspection - Codes Residential Failed 3/18/2024 3/15/2024 03/15/2024
Misc
Corrective Action Required
09/18/2023
Submit TCO extension letter. TCO expires 03/15/24 -obtain lawn irrigation permit -repair hole in exterior wall from previous heat pump -handrail and garage to be code compliant see R311.7.8.5 Grip size
Occupancy Inspection - Codes Residential Full C of O 5/9/2024 5/9/2024 05/09/2024
Misc
Resolved
05/09/2024
Submit TCO extension letter. TCO expires 03/15/24 -obtain lawn irrigation permit -repair hole in exterior wall from previous heat pump -handrail and garage to be code compliant see R311.7.8.5 Grip size
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.