Permit Application Status

PRRES20210696


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20210696
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - PARTIAL FINISHED BASEMENT - UNCOVERED DECK TILE ROOF
02/22/2021
02/25/2021
08/21/2021
01/18/2022
Locations
Contacts
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
MIKE@SUMMITHOMESKC.COM  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 03/01/2021 02/25/2021
Kim Brennan
Property boundary
Corrective Action Required
02/25/2021

Property boundary distances and bearings, as shown on the recorded plat, must be provided on the plot plan. Rear property line should be 62.61.
Deck location
Corrective Action Required
02/25/2021

Deck location, with dimensions to property lines must be provided on the plot plan. Construction drawings show a covered deck
Misc
Corrective Action Required
02/25/2021

Retaining walls 4' and over require engineered drawings
Basement opening elevations
Corrective Action Required
02/25/2021

Minimum Building Opening Elevation (MBOE) and location on structure must be provided on the plot plan. The revised MDP does not show MLO's on the front, only in the rear
As-graded plot plan
Corrective Action Required
02/25/2021

A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy.
Residential Plan Review Approved 03/01/2021 02/25/2021
Kim Brennan
05 Provide square footage of living area, garage area, unfinished basement
Corrective Action Required
02/25/2021

Provide square footage of living area, garage area, unfinished basement area, etc (IRC Section R3) Says covered patio but the drawings show covered deck. Which one is correct?
Planning Review (RES) Approved 02/24/2021 02/22/2021
Kim Brennan
Plot Plan Review Rejected 02/24/2021 02/22/2021
Kim Brennan
Property boundary
Corrective Action Required
02/22/2021

Property boundary distances and bearings, as shown on the recorded plat, must be provided on the plot plan. Rear property line should be 62.61.
Deck location
Corrective Action Required
02/22/2021

Deck location, with dimensions to property lines must be provided on the plot plan. Construction drawings show a covered deck
Misc
Corrective Action Required
02/22/2021

Retaining walls 4' and over require engineered drawings
Basement opening elevations
Corrective Action Required
02/22/2021

Minimum Building Opening Elevation (MBOE) and location on structure must be provided on the plot plan. The revised MDP does not show MLO's on the front, only in the rear
As-graded plot plan
Corrective Action Required
02/22/2021

A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy.
Residential Plan Review Rejected 02/24/2021 02/22/2021
Kim Brennan
05 Provide square footage of living area, garage area, unfinished basement
Corrective Action Required
02/22/2021

Provide square footage of living area, garage area, unfinished basement area, etc (IRC Section R3) Says covered patio but the drawings show covered deck. Which one is correct?
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,030.79 $1,030.79 Paid 02/25/2021
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 02/25/2021
8331401-Water Tap Fee $3,581.00 $3,581.00 Paid 02/25/2021
8350015-Water Meter Fee $455.54 $455.54 Paid 02/25/2021
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 02/25/2021
8331507-Sewer Connection Fee $390.00 $390.00 Paid 02/25/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 09/24/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 09/24/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 09/24/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 09/24/2021
9110080-3rd and Subsequent Inspection Fee (Per Hour) $50.00 $50.00 Paid 09/24/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 4/9/2021 04/09/2021
Misc
Informational
04/09/2021
- 3RD PARTY FOOTING BY DEREK PEREZ @ RES SIGNED & SEALED BY BRADLEY HUXOL - - UFER LOCATED CENTER SOUTH REAR GARAGE FOUNDATION WALL -
Underslab Plumbing Inspection - Residential Failed 4/26/2021 4/26/2021 04/26/2021
Misc
Corrective Action Required
04/26/2021
Provide positive or neutral slope of interior underslab drain tile throughout
Underslab Plumbing Inspection - Residential Passed 4/28/2021 4/28/2021 04/28/2021
Misc
Resolved
04/28/2021
All Rough Inspection - Residential Partial 6/22/2021 6/22/2021 06/22/2021
Misc
Corrective Action Required
06/22/2021
GARAGE PORTAL FRAME 3" O.C. NAILING & HOLD DOWNS NAILED OFF OK TO COVER TRUSSES FRONT PORCH TRUSS LOCK SCREWS IN PLACE OK TO COVER CHECK BELOW ON ROUGH IN PROVIDE 4 STUD PACK AT GIRDER TRUSS BEARING POINTS PER ROOF PLAN G-1 TRUSS AT FRONT PORCH
Gas Service Inspection - Residential Failed 8/16/2021 8/16/2021 08/16/2021
Misc
Corrective Action Required
08/16/2021
-Provide min 10 psi pressure for testing
Electrical Service Inspection Passed 8/16/2021 8/16/2021 08/16/2021
All Rough Inspection - Residential Failed 8/16/2021 8/16/2021 08/16/2021
Misc
Corrective Action Required
06/22/2021
-Complete vapor barrier covering for the garage PHF walls -Provide full solid block between rafters or 1-hr fire rating under roof soffit -Walls with fire separation distance less than 5 ft shall be rated 1 hour on both sides -Provide a rear receptacle readily accessible from and within 6.5 ft of grade -Secure receptacle box in master bedroom behind fireplace -Nail together A10 girder truss per detail; tie down this GT at both ends. Use 2 straps instead of screws for big uplift; provide full support at front end -Protect DVW at bottom wall plate of closet/front bathroom wall -Strap top plates lapped less than 2 ft at front bathroom -Protect AC circuit at garage rear wall corner -Protect wiring within 6 ft of attic access -Protect dryer duct at top plate -Tie down A1 GT and truss above laundry rm. Use straps instead of screws for big uplift; nail together GT per detail -Strap top plates lapped less than 2 ft at master closet -Install HUS26 hanger at C8 connection to A1 GT -Provide combustion air openings per code -Fb gap at vertical fire blockings; fb openings at I beam web -Anchor sill plate within 12” of end at east unfinished basement wall -Install missing stud at wet bar wall -Solid block joists under kitchen island per plan **OK TO INSULATE
All Rough Inspection - Residential Not Ready 8/23/2021 8/23/2021 08/23/2021
Misc
Corrective Action Required
08/16/2021
-Complete vapor barrier covering for the garage PHF walls -Provide full solid block between rafters or 1-hr fire rating under roof soffit -Walls with fire separation distance less than 5 ft shall be rated 1 hour on both sides -Provide a rear receptacle readily accessible from and within 6.5 ft of grade -Secure receptacle box in master bedroom behind fireplace -Nail together A10 girder truss per detail; tie down this GT at both ends. Use 2 straps instead of screws for big uplift; provide full support at front end -Protect DVW at bottom wall plate of closet/front bathroom wall -Strap top plates lapped less than 2 ft at front bathroom -Protect AC circuit at garage rear wall corner -Protect wiring within 6 ft of attic access -Protect dryer duct at top plate -Tie down A1 GT and truss above laundry rm. Use straps instead of screws for big uplift; nail together GT per detail -Strap top plates lapped less than 2 ft at master closet -Install HUS26 hanger at C8 connection to A1 GT -Provide combustion air openings per code -Fb gap at vertical fire blockings; fb openings at I beam web -Anchor sill plate within 12” of end at east unfinished basement wall -Install missing stud at wet bar wall -Solid block joists under kitchen island per plan
All Rough Inspection - Residential Not Ready 8/31/2021 8/31/2021 08/31/2021
Misc
Corrective Action Required
08/23/2021
-Provide full solid block between rafters or 1-hr fire rating under roof soffit -Walls with fire separation distance less than 5 ft shall be rated 1 hour on both sides -Protect dryer duct at top plate ( fire block, seal upward penetration) -Tie down A1 GT and truss above laundry rm. Use straps instead of screws for big uplift; nail together GT per detail -Provide combustion air openings per code -Fb gap at vertical fire blockings; fb openings at I beam web : House is insulated unable to verify items complete : : exterior bracing WSP per plan 4'-0" panels at corners : : pyro-guard is stapled not nailed per code/per plan :
Sewer Service Inspection - R Passed 9/9/2021 09/09/2021
Water Service Inspection - R Passed 9/13/2021 (10:30) 9/13/2021 09/13/2021
All Rough Inspection - Residential Not Ready 9/10/2021 9/10/2021 09/13/2021
Misc
Corrective Action Required
08/31/2021
-Provide full solid block between rafters or 1-hr fire rating under roof soffit -Walls with fire separation distance less than 5 ft shall be rated 1 hour on both sides -Provide combustion air openings per code -Fb gap at vertical fire blockings; fb openings at I beam web : House is insulated unable to verify items complete : : exterior bracing WSP per plan 4'-0" panels at corners : : pyro-guard is stapled not nailed per code/per plan :
Gas Service Inspection - Residential Passed 9/15/2021 9/15/2021 09/15/2021
Misc
Resolved
09/15/2021
-Provide min 10 psi pressure for testing
All Rough Inspection - Residential Failed 9/15/2021 9/15/2021 09/15/2021
Misc
Corrective Action Required
09/10/2021
-Walls with fire separation distance less than 5 ft shall be rated 1 hour on both sides-PYRO GAURD REQUIRED TO BE TO TOP PLATE AND NAILED PER CODE
Driveway Inspection Partial 9/20/2021 9/20/2021 09/20/2021
Misc
Informational
09/20/2021
Forms are in place and rock is present and compacted. Right of way is in ADA spec.
All Rough Inspection - Residential Failed 9/22/2021 9/22/2021 09/22/2021
Misc
Corrective Action Required
09/22/2021
**9-22-21 Inspection denied due to lack of erosion control-Maintain gravel filter, silt fence at perimeter and clean trash and debris from site before further inspections -Walls with fire separation distance less than 5 ft shall be rated 1 hour on both sides-PYRO GAURD REQUIRED TO BE TO TOP PLATE AND NAILED PER CODE
Erosion Control Inspection Residential Failed 9/22/2021 9/22/2021 09/22/2021
DCM5 ESC INSP DENIED
Corrective Action Required
09/22/2021
**9-22-21 Inspection denied due to lack of erosion control-Maintain gravel filter, silt fence at perimeter and clean trash and debris from site before further inspections REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION.
All Rough Inspection - Residential Passed 9/24/2021 9/24/2021 09/24/2021
Misc
Resolved
09/24/2021
Driveway Inspection Passed 9/24/2021 9/24/2021 09/24/2021
Misc
Informational
09/20/2021
Forms are in place and rock is present and compacted. Right of way is in ADA spec.
Misc
Informational
09/24/2021
Driveway is good and meets ADA spec
Sidewalk Inspection Partial 10/7/2021 10/7/2021 10/07/2021
Misc
Informational
10/07/2021
10-7-21 10:48 AN Forms are in place and aggregate is present and compacted
Sidewalk Inspection Passed 10/15/2021 10/15/2021 10/12/2021
Misc
Informational
10/07/2021
10-7-21 10:48 AN Forms are in place and aggregate is present and compacted
Misc
Informational
10/12/2021
10-12-21 AN sidewalk looks good and meets ADA specs
Piers/Caissons Inspection - Residential Passed 12/3/2021 12/03/2021
Misc
Informational
12/03/2021
indicated checked in 3rd party footing inspection
Occupancy Inspection - Codes Residential Temporary C of O 12/3/2021 12/3/2021 12/03/2021
Misc
Corrective Action Required
12/03/2021
TCO UNTIL 02/03/22 -Final grade and sod -sump pump discharge and all drainage discharge to be 36" from foundation -check water metere at time of final grade and sod
Piers/Caissons Inspection - Residential Passed 1/18/2022 01/18/2022
Misc
Informational
01/18/2022
INCLUDED ON 3RD PARTY FOOTING BY RES
Plot Plan Inspection Passed 1/18/2022 01/18/2022
Occupancy Inspection - Codes Residential Full C of O 1/18/2022 1/18/2022 01/18/2022
Misc
Resolved
01/18/2022
Sidewalk Inspection Partial 05/12/2022
Misc
Informational
05/12/2022
5-12-22 AN forms are in place and aggregate is present and compacted
Sidewalk Inspection Passed 5/17/2022 5/17/2022 05/23/2022
Misc
Informational
05/12/2022
5-12-22 AN forms are in place and aggregate is present and compacted
Misc
Informational
05/23/2022
Sidewalk meets LS and ADA specs. 5/23/22 ES
Documents & Images
Date Uploaded File Type Document Name
02/22/2021 Application Form Permit Application and License Tax Form
02/22/2021 2629082 RF SEALS 02022021
02/22/2021 Letter Codes Residential Plan Review
02/25/2021 Approved Plans Approved Truss Layout
02/25/2021 Approved Plans Approved Truss Package
02/25/2021 W1 #21 - Permit App
02/25/2021 Plot Plan Approved Plot Plan
02/25/2021 Approved Plans Approved Drawings
02/25/2021 Receipt Receipt for transaction:2021-000929
02/25/2021 Letter DS Building Permit
04/09/2021 W1-21 Woodside Footing Inspection
04/09/2021 Letter INSPECTION SUMMARY
04/26/2021 Letter INSPECTION SUMMARY
04/28/2021 Letter INSPECTION SUMMARY
06/22/2021 Letter INSPECTION SUMMARY
08/16/2021 Letter INSPECTION SUMMARY
08/16/2021 Letter INSPECTION SUMMARY
08/16/2021 Letter INSPECTION SUMMARY
08/23/2021 Letter INSPECTION SUMMARY
08/31/2021 Letter INSPECTION SUMMARY
09/09/2021 Letter INSPECTION SUMMARY
09/10/2021 Letter INSPECTION SUMMARY
09/13/2021 Letter INSPECTION SUMMARY
09/13/2021 Letter INSPECTION SUMMARY
09/15/2021 Letter INSPECTION SUMMARY
09/15/2021 Letter INSPECTION SUMMARY
09/15/2021 Letter INSPECTION SUMMARY
09/20/2021 Letter INSPECTION SUMMARY
09/22/2021 Letter INSPECTION SUMMARY
09/22/2021 Letter INSPECTION SUMMARY
09/24/2021 Letter INSPECTION SUMMARY
09/24/2021 Letter INSPECTION SUMMARY
09/24/2021 Receipt Receipt for transaction:2021-007576
10/07/2021 Letter INSPECTION SUMMARY
10/12/2021 Letter INSPECTION SUMMARY
10/19/2021 Approved Plans APPROVED COVERED DECK PLAN
10/19/2021 Approved Plans APPROVED COVERED PORCH DETAILS
10/19/2021 Approved Plans APPROVED COVERED PORCH TRUSS LAYOUT
10/21/2021 Plot Plan APPROVED AS BUILT PLOT PLAN
12/03/2021 Letter INSPECTION SUMMARY
12/03/2021 Letter Codes Temporary Certificate of Occupancy
01/18/2022 Letter INSPECTION SUMMARY
01/18/2022 Letter INSPECTION SUMMARY
01/18/2022 Letter Field Certificate of Occupancy
01/18/2022 Letter Codes Final Certificate of Occupancy
05/12/2022 Letter INSPECTION SUMMARY
05/23/2022 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents