Permit Application Status

PRRES20204762


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20204762
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - UNFINISHED BASEMENT - COVERED DECK TILE ROOF
12/14/2020
12/22/2020
06/13/2021
11/10/2021
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
MIKE@SUMMITHOMESKC.COM  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 12/28/2020 12/22/2020
Kim Brennan
Easements
Corrective Action Required
12/22/2020

All easements with dimensions must be provided on the plot plan.
As-graded plot plan
Corrective Action Required
12/22/2020

A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy.
Residential Plan Review Approved 12/28/2020 12/22/2020
Kim Brennan
Residential Plan Review Approved 12/17/2020 12/21/2020
Kim Brennan
08 Designate locations of smoke detectors and carbon monoxide detectors
Corrective Action Required
12/15/2020

Designate locations of smoke detectors and carbon monoxide detectors. (IRC Section R314 and R315) Not shown in the unfinished basement
Plot Plan Review Rejected 12/17/2020 12/15/2020
Kim Brennan
Easements
Corrective Action Required
12/15/2020

All easements with dimensions must be provided on the plot plan.
As-graded plot plan
Corrective Action Required
12/15/2020

A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $955.67 $955.67 Paid 12/22/2020
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 12/22/2020
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 12/22/2020
8331507-Sewer Connection Fee $360.00 $360.00 Paid 12/22/2020
8331401-Water Tap Fee $3,581.00 $3,581.00 Paid 12/22/2020
8350015-Water Meter Fee $455.54 $455.54 Paid 12/22/2020
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 10/13/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 10/13/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 10/13/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 10/13/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 10/13/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 10/13/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Sewer Service Inspection - R Passed 2/5/2021 (9:15) 2/5/2021 02/05/2021
Footing Inspection - Residential Failed 2/24/2021 02/24/2021
Misc
Corrective Action Required
02/24/2021
- NO FOOTING INSPECTION ON RECORD SUBMIT 3RD PARTY INSPECTIONS WITHIN 48 HOURS OF POUR -
Water Service Inspection - R Passed 2/24/2021 (1:00) 2/24/2021 02/24/2021
Footing Inspection - Residential Passed 2/22/2021 03/10/2021
Misc
Resolved
03/10/2021
- 3RD PARTY FOOTING BY DEREK PEREZ @ RES SIGNED & SEALED BY BRADLEY HUXOL
Underslab Plumbing Inspection - Residential Failed 3/10/2021 3/10/2021 03/10/2021
R506.2.5 Interior Underslab Drains
Corrective Action Required
03/10/2021
- CONNECT INTERIOR DRAIN TILE TO SUMP PUMP - CONCRETE FLOORS (ON GROUND). ADDED 7-927. Where foundations retain earth and enclose habitable or usable space located below grade, drains shall be provided below the floor slab. Drainage tiles, perforated pipe or other approved systems or materials shall be installed at or below the area(s) to be protected; shall be placed with positive or neutral slope to minimize the accumulation of deposits in the drainage system; and shall discharge by gravity or mechanical means to an approved storm water drainage system. The underslab drainage system shall be installed around the inner perimeter of the area(s) to be protected, or, in a manner that will provide adequate drainage for all area(s) to be protected and is approved by the building official. Interior underslab drains installed on uncompacted fill material shall be supported by mechanical means which are adequately tied into the concrete slab to ensure proper drainage throughout the underslab drain(s).
Underslab Plumbing Inspection - Residential Not Ready 3/11/2021 3/11/2021 03/11/2021
R506.2.5 Interior Underslab Drains
Corrective Action Required
03/10/2021
- CONNECT INTERIOR DRAIN TILE TO SUMP PUMP - ( SAME AS YESTERDAY )Michael Harkins 03/11/2021 9:09 AM CONCRETE FLOORS (ON GROUND). ADDED 7-927. Where foundations retain earth and enclose habitable or usable space located below grade, drains shall be provided below the floor slab. Drainage tiles, perforated pipe or other approved systems or materials shall be installed at or below the area(s) to be protected; shall be placed with positive or neutral slope to minimize the accumulation of deposits in the drainage system; and shall discharge by gravity or mechanical means to an approved storm water drainage system. The underslab drainage system shall be installed around the inner perimeter of the area(s) to be protected, or, in a manner that will provide adequate drainage for all area(s) to be protected and is approved by the building official. Interior underslab drains installed on uncompacted fill material shall be supported by mechanical means which are adequately tied into the concrete slab to ensure proper drainage throughout the underslab drain(s).
Underslab Plumbing Inspection - Residential Passed 3/12/2021 3/12/2021 03/12/2021
R506.2.5 Interior Underslab Drains
Resolved
03/12/2021
All Rough Inspection - Residential Failed 5/19/2021 5/19/2021 05/19/2021
Miscellaneous Correction
Corrective Action Required
05/19/2021
-Tape nail holes at PFH -Unable to verify nailing pattern at CS-PF, CS-WSP or EC1 braced walls -Address sheathing stapled in place of nails throughout -Address fire resistance rating of exterior walls and openings at West entry and East garage less than 5' separation to property line- walls to be 1 hour fire rated per IRC R302.1(1) -Truss screws/ H2.5s missing or not installed properly in multiple locations -Nail corners and intersecting studs per code -Provide anchor bolts at the end of plates in back garage wall and return walls at 2 car bay -Missing nuts and washers at anchor bolts at back garage wall and return walls at 2 car bay -Provide anchor bolts at plate breaks in garage -Missing LIB throughout -Missing nails in hanger at A8 truss in garage -Set nails in hanger at J18 truss in garage -Replace or sister stud to overnotched studs in garage -Provide min. (4) 2x4 studs at all girder truss bearing locations -Address exterior wall connections at front entry/ foyer, front entry/ bed 2, Southwest corner of dining room, and dining room/ covered porch- Provide engineered corrections -Add stud under truss at exterior bearing wall at front entry/ foyer where no double top plate exists -Seal floor penetration under bathtub in bed 2 bath -Nail sheathing to studs at bed 2 -Support header at ends in bed 2 -Seal bottom plate penetrations in bath 2 by closet and by stairs -Expose trusses, beams, posts and all connections for inspection at covered deck -Seal floor penetration at gas line in fireplace -Seal gap in flooring in closet bed 2 -Tighten anchor bolts throughout basements -Provide anchor bolts at plate breaks throughout basement -Missing nuts and washer at bolts under windows -Sister studs to over notched studs throughout basement -Provide anchor bolts at end of plates by slider -Address exterior corners not framed with 3 studs, no double top plates, no bottom plate, no proper corner connection at basement walls-Provide engineered corrections -Sheathing not nailed to top or bottom plate in exterior corners -Provide solid blocking 48" OC under island per plan -Address 6x6 posts at deck not full height -Provide (2) 1/2" through bolts at each beam to post connection -Provide lag bolts at ledger -Provide hanger at end joists to ledger connection -Gas and electrical ok
All Rough Inspection - Residential Not Ready 5/28/2021 5/28/2021 05/28/2021
Miscellaneous Correction
Corrective Action Required
05/19/2021
5/28/21 11:00 am LIBs, GT bearing points Provide 4 studs per plan NOT DONE NOT READY -Tape nail holes at PFH -Unable to verify nailing pattern at CS-PF, CS-WSP or EC1 braced walls -Address sheathing stapled in place of nails throughout -Address fire resistance rating of exterior walls and openings at West entry and East garage less than 5' separation to property line- walls to be 1 hour fire rated per IRC R302.1(1) -Truss screws/ H2.5s missing or not installed properly in multiple locations -Nail corners and intersecting studs per code -Provide anchor bolts at the end of plates in back garage wall and return walls at 2 car bay -Missing nuts and washers at anchor bolts at back garage wall and return walls at 2 car bay -Provide anchor bolts at plate breaks in garage -Missing LIB throughout -Missing nails in hanger at A8 truss in garage -Set nails in hanger at J18 truss in garage -Replace or sister stud to overnotched studs in garage -Provide min. (4) 2x4 studs at all girder truss bearing locations -Address exterior wall connections at front entry/ foyer, front entry/ bed 2, Southwest corner of dining room, and dining room/ covered porch- Provide engineered corrections -Add stud under truss at exterior bearing wall at front entry/ foyer where no double top plate exists -Nail sheathing to studs at bed 2 -Support header at ends in bed 2 -Seal bottom plate penetrations in bath 2 by closet and by stairs -Expose trusses, beams, posts and all connections for inspection at covered deck -Seal floor penetration at gas line in fireplace -Seal gap in flooring in closet bed 2 -Tighten anchor bolts throughout basements -Provide anchor bolts at plate breaks throughout basement -Missing nuts and washer at bolts under windows -Sister studs to over notched studs throughout basement -Provide anchor bolts at end of plates by slider -Address exterior corners not framed with 3 studs, no double top plates, no bottom plate, no proper corner connection at basement walls-Provide engineered corrections -Sheathing not nailed to top or bottom plate in exterior corners -Provide solid blocking 48" OC under island per plan -Address 6x6 posts at deck not full height -Provide (2) 1/2" through bolts at each beam to post connection -Provide lag bolts at ledger -Provide hanger at end joists to ledger connection -Gas and electrical ok
Electrical Service Inspection Passed 6/8/2021 6/8/2021 06/08/2021
Gas Service Inspection - Residential Passed 6/8/2021 6/8/2021 06/08/2021
All Rough Inspection - Residential Not Ready 6/8/2021 6/8/2021 06/08/2021
Miscellaneous Correction
Corrective Action Required
05/28/2021
6/8 - LIBs, FIre rated construction of East wall, GT bearing points-Nail all studs together tight to form stud pack and Provide 4 studs per plan NOT DONE NOT READY- -Unable to verify nailing pattern at CS-PF, CS-WSP or EC1 braced walls -Address sheathing stapled in place of nails throughout -Address fire resistance rating of exterior walls and openings at West entry and East garage less than 5' separation to property line- walls to be 1 hour fire rated per IRC R302.1(1) -Truss screws/ H2.5s missing or not installed properly in multiple locations -Nail corners and intersecting studs per code -Provide anchor bolts at the end of plates in back garage wall and return walls at 2 car bay -Missing nuts and washers at anchor bolts at back garage wall and return walls at 2 car bay -Provide anchor bolts at plate breaks in garage -Missing LIB throughout -Missing nails in hanger at A8 truss in garage -Set nails in hanger at J18 truss in garage -Replace or sister stud to overnotched studs in garage -Provide min. (4) 2x4 studs at all girder truss bearing locations -Address exterior wall connections at front entry/ foyer, front entry/ bed 2, Southwest corner of dining room, and dining room/ covered porch- Provide engineered corrections -Add stud under truss at exterior bearing wall at front entry/ foyer where no double top plate exists -Nail sheathing to studs at bed 2 -Support header at ends in bed 2 -Seal bottom plate penetrations in bath 2 by closet and by stairs -Expose trusses, beams, posts and all connections for inspection at covered deck -Seal floor penetration at gas line in fireplace -Seal gap in flooring in closet bed 2 -Tighten anchor bolts throughout basements -Provide anchor bolts at plate breaks throughout basement -Missing nuts and washer at bolts under windows -Sister studs to over notched studs throughout basement -Provide anchor bolts at end of plates by slider -Address exterior corners not framed with 3 studs, no double top plates, no bottom plate, no proper corner connection at basement walls-Provide engineered corrections -Sheathing not nailed to top or bottom plate in exterior corners -Provide solid blocking 48" OC under island per plan -Address 6x6 posts at deck not full height -Provide (2) 1/2" through bolts at each beam to post connection -Provide lag bolts at ledger -Provide hanger at end joists to ledger connection
All Rough Inspection - Residential Not Ready 6/23/2021 6/23/2021 06/23/2021
Miscellaneous Correction
Corrective Action Required
06/08/2021
6/8 - LIBs, FIre rated construction of East wall, GT bearing points-Nail all studs together tight to form stud pack and Provide 4 studs per plan NOT DONE NOT READY- - Tyvek tape nail penetrations south & east sides -Unable to verify nailing pattern at CS-PF, CS-WSP or EC1 braced walls -Address fire resistance rating of exterior walls and openings at West entry and East garage less than 5' separation to property line- walls to be 1 hour fire rated per IRC R302.1(1) -Truss screws/ H2.5s missing or not installed properly in multiple locations -Provide anchor bolts at the return walls at 2 car bay -Missing nuts and washers at anchor bolts return walls at 2 car bay ( Square washer on top of 2nd bottom plate per plan ) -Missing LIB (BED #2 CLOSET) -Set nails in hanger at J18 truss in garage -Provide min. (4) 2x4 studs at all girder truss bearing locations ( A-7 GARAGE) -Address exterior wall connections at front entry/ foyer, front entry/ bed 2, Southwest corner of dining room, and dining room/ covered porch- Provide engineered corrections -Seal bottom plate penetrations in bath 2 by closet and by stairs -Expose trusses, beams, posts and all connections for inspection at covered deck ( Provide 2 stud pack end of LVLs covered deck) -Tighten anchor bolts throughout basements(!NEAR SERVICE PANEL) -Address exterior corners not framed with 3 studs, no double top plates, no bottom plate, ( Anchor bolts) no proper corner connection at basement walls-Provide engineered corrections -Sheathing not nailed to top or bottom plate in exterior corners -Provide solid blocking 48" OC under island per plan ( West end of island) -Address 6x6 posts at deck not full height -Provide (2) 1/2" through bolts at each beam to post connection -Provide hanger at end joists to ledger connection
All Rough Inspection - Residential Not Ready 7/1/2021 7/1/2021 07/01/2021
Miscellaneous Correction
Corrective Action Required
06/23/2021
-Address fire resistance rating of exterior walls and openings at West entry and East garage less than 5' separation to property line- walls to be 1 hour fire rated per IRC R302.1(1) ( OSB IN SE CORNER NOT PYRO GUARD ) -Truss screws/ H2.5s missing or not installed properly in multiple locations ( MASTER BED SE CORNER ) -Provide anchor bolts at the return walls at 2 car bay -Missing nuts and washers at anchor bolts return walls at 2 car bay ( Square washer on top of 2nd bottom plate per plan ) -Address exterior wall connections at front entry/ foyer, front entry/ bed 2, Southwest corner of dining room, and dining room/ covered porch- Provide engineered corrections ( NO ENGINEERS LETTER ) -Address exterior corners not framed with 3 studs, no double top plates, no bottom plate, ( Anchor bolts) no proper corner connection at basement walls-Provide engineered corrections ( NO ENGINEERS LETTER ) -Provide (2) 1/2" through bolts at each beam to post connection -Provide hanger at end joists to ledger connection
All Rough Inspection - Residential Passed 7/9/2021 7/12/2021 07/12/2021
Miscellaneous Correction
Resolved
07/12/2021
Driveway Inspection Partial 8/5/2021 8/5/2021 08/05/2021
Misc
Informational
08/05/2021
Forms were placed and aggregate was present and compacted. RP 8-5-21
Driveway Inspection Passed 8/13/2021 8/13/2021 08/13/2021
Misc
Informational
08/05/2021
Forms were placed and aggregate was present and compacted. RP 8-5-21
Misc
Informational
08/13/2021
Finished driveway meets LS and ADA specs. RP 8-13-21
Sidewalk Inspection Not Ready 9/16/2021 9/16/2021 09/16/2021
Misc
Corrective Action Required
09/16/2021
No aggregate in place.
Sidewalk Inspection Partial 9/17/2021 9/17/2021 09/17/2021
Misc
Corrective Action Required
09/16/2021
No aggregate in place.
Misc
Informational
09/17/2021
Forms were placed and aggregate was present and compacted. RP 9-17-21
Sidewalk Inspection Passed 9/24/2021 9/24/2021 09/24/2021
Misc
Corrective Action Required
09/17/2021
No aggregate in place.
Misc
Informational
09/17/2021
Forms were placed and aggregate was present and compacted. RP 9-17-21
Misc
Informational
09/24/2021
9-24-21 11:36 sidewalk meets ADA spec 1.5% or less
Occupancy Inspection - Codes Residential Failed 10/13/2021 10/13/2021 10/13/2021
Misc
Corrective Action Required
10/13/2021
-pay all re-inspection fees. - submit as-graded plot plan. - check all exterior items, water meter etc, sod , splashblocks - uncover manhole front east side. - deck stairs over 7 3/4" -missing light master ceiling - sheetrock shelf platform garage. -support pex piping at water heater. -install anti-siphon on hose bib basement. - provide engineers report on continous deck post. - secure AC whip
Plot Plan Inspection Passed 10/21/2021 10/21/2021
Occupancy Inspection - Codes Residential Full C of O 11/10/2021 11/10/2021 11/10/2021
Misc
Resolved
11/10/2021
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.