Permit Application Status

PRRES20203671


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20203671
Building Permit - Residential
Certificate of Occupancy
SUMMIT VIEW FARMS DEVELOPMENT GROUP LLC
NEW SINGLE FAMILY
NEW HOUSE - UNFINSHED BAEMENT - COVERED DECK
10/12/2020
11/06/2020
02/28/2024
Locations
Contacts
SUMMIT VIEW FARMS DEVELOPMENT GROUP LLC, Address:13450 E STATE ROUTE 150  
SPELLERBERG ENTERPRISES LLC, Address:613 NE VIEWPARK DR, Phone:(816) 550-5535  
SPELLERBERGENTERPRISES@GMAIL.COM  
AFC HEATING AND COOLING, Address:824 NW MAIN ST , Phone:(816) 347-8388  
NEW HEIGHTS ELECTRIC LLC, Address:P O BOX 163, Phone:(816) 625-9504  
TRI-COUNTY PLUMBING LLC, Address:PO BOX 234, Phone:(816) 720-3222  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 10/14/2020 10/15/2020
Dylan Eppert
Signed and sealed
Corrective Action Required
10/14/2020

Plot plan must drawn, signed, and sealed by a licensed surveyor or engineer.
Legal description
Corrective Action Required
10/14/2020

The legal description, including plat or phase number and lot number, and street address must be provided on the plot plan. missing address
Right-of-way
Corrective Action Required
10/14/2020

The right-of-way with dimensions must be provided on the plot plan. SW KLINE IS A 60' ROW NOT 50'
Miscellaneous Correction
Corrective Action Required
10/14/2020

PLEASE CONFIRM IF THIS WILL BE A NORMAL WALK OUT OR WILL THIS BE A WALKOUT WALK UP?
Residential Plan Review Rejected 10/14/2020 10/14/2020
Dylan Eppert
07 Identify emergency escape openings from bedrooms
Corrective Action Required
10/14/2020

Identify emergency escape openings from bedrooms and basement(s). (IRC Section R310 as amended per Ordinance) label egress for bedroom on main floor
08 Designate locations of smoke detectors and carbon monoxide detectors
Corrective Action Required
10/14/2020

Designate locations of smoke detectors and carbon monoxide detectors. (IRC Section R314 and R315) missing detectors for bedroom on main floor.
Miscellaneous Correction
Corrective Action Required
10/14/2020

PLEASE CLARIFY IF THIS WILL BE A WALKOUT OR WALKOUT WALK UP. THEN REVISE PLANS TO MATCH THE PLOT PLAN.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,368.34 $1,368.34 Paid 11/06/2020
8331507-Sewer Connection Fee $600.00 $600.00 Paid 11/06/2020
8331401-Water Tap Fee $3,581.00 $3,581.00 Paid 11/06/2020
8350015-Water Meter Fee $455.54 $455.54 Paid 11/06/2020
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 11/06/2020
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 11/06/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 11/13/2020 (3:30) 11/13/2020 11/13/2020
Underslab Plumbing Inspection - Residential Passed 12/17/2020 12/17/2020 12/17/2020
Piers/Caissons Inspection - Residential Passed 1/21/2021 (10:15) 1/21/2021 01/21/2021
Misc
Informational
01/21/2021
(7) 24 X 40 COVERED DECK PIERS
Sewer Service Inspection - R Partial 3/22/2021 (2:00) 3/22/2021 03/22/2021
Misc
Informational
03/22/2021
partial sewer approval from connection at structure to approximately 10' shy of sewer stub
Sewer Service Inspection - R Passed 3/23/2021 (10:45) 3/23/2021 03/23/2021
Misc
Resolved
03/23/2021
partial sewer approval from connection at structure to approximately 10' shy of sewer stub
Water Service Inspection - R Partial 3/23/2021 3/23/2021 03/23/2021
Misc
Informational
03/23/2021
-PARTIAL INSPECTION FROM COPPER AT MAIN TAP 5' TOWARDS HOUSE, OK TO COVER AREA INSPECTED
Water Service Inspection - R Passed 3/23/2021 (1:00) 3/23/2021 03/23/2021
Misc
Resolved
03/23/2021
-PARTIAL INSPECTION FROM COPPER AT MAIN TAP 5' TOWARDS HOUSE, OK TO COVER AREA INSPECTED
Erosion Control Inspection Residential Failed 04/02/2021
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
04/02/2021
*4-2-21 EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
All Rough Inspection - Residential Failed 4/2/2021 4/2/2021 04/02/2021
Miscellaneous Correction
Corrective Action Required
04/02/2021
*4-2-21 INSPECTION DENIED DUE TO LACK OF EROSION CONTROL. PROVIDE SILT FENCE OR OTHER ACCEPTED MEANS AT PERIMETER OF LOT BEFORE ANY FURTHER INSPECTIONS
Electrical Service Inspection Passed 4/6/2021 4/6/2021 04/06/2021
Gas Service Inspection - Residential Passed 4/6/2021 4/6/2021 04/06/2021
All Rough Inspection - Residential Failed 4/6/2021 4/6/2021 04/06/2021
Miscellaneous Correction
Corrective Action Required
04/02/2021
-3” nailing grid pattern at sheathing to header garage portal PFH, see detail on D3 and R602.10.6.2 -Garage PFH CS16 straps start above header and end 12” below header on garage jack studs, see plan detail D3 and R602.10.6.2 -Garage portal PFH anchor bolts 1/2” with 2” x 2” x 3/16” flat washer, see plans D3 and R602.10.6.2 -support ridge at garage -joist hanger required at tail joist to attic access header in garage and 2nd floor laundry, over 4’ -Fireblock vertical to horizontal at furred down in garage -seal all top and bottom plate penetrations- see panty bottom plate, top plate above front entry -stud shoe at DWV kitchen exterior wall -Nail protection plates at all NM (romex) within 1 1/4” end of stud throughout - Fireblock DWV chase at great room windows -LIB bracing all locations per plans 2nd floor -All bath exhaust fans shall vent direct to exterior per plans, see exhaust note page D2 -2x6 ceiling joists at covered deck per plans, unable to inspect all covered deck framing due to siding lid cover -fireblock at covered deck fireplace -Install fireplace and complete gas line at deck fireplace -(2) through bolts at all post/beam connection per code at deck -Solid block between joists at deck fireplace cantilever -Nail all exterior sheathing per plans, 6” edge, 12” field
All Rough Inspection - Residential Failed 4/9/2021 4/9/2021 04/09/2021
Miscellaneous Correction
Corrective Action Required
04/06/2021
-3” nailing grid pattern at sheathing to header garage portal PFH, see detail on D3 and R602.10.6.2 -Install fireplace and complete gas line at deck fireplace -(2) through bolts at all post/beam connection per code at deck -Solid block between joists at deck fireplace cantilever -Nail all exterior sheathing per plans, 6” edge, 12” field **OK TO INSULATE**
Driveway Inspection Partial 4/12/2021 4/12/2021 04/12/2021
Misc
Informational
04/12/2021
4/12/21 Monday Driveway - forms and materials passed pre-inspection.
Driveway Inspection Passed 4/14/2021 4/14/2021 04/14/2021
Misc
Informational
04/12/2021
4/12/21 Monday Driveway - forms and materials passed pre-inspection.
Misc
Informational
04/14/2021
4/14/21 Wednesday Driveway - passed final inspection.
All Rough Inspection - Residential Passed 4/19/2021 4/19/2021 04/19/2021
Miscellaneous Correction
Resolved
04/19/2021
Erosion Control Inspection Residential Failed 5/25/2021 5/25/2021 05/25/2021
DCM3 ESC REQUIRED 2 DAY
Resolved
05/25/2021
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
05/25/2021
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. -MAINTAIN EROSION CONTROL AT REAR OF LOT, NEIGHBORING LOT AT REAR EXPERIENCING SILT RUNOFF ONTO PROPERTY
Sidewalk Inspection Passed 6/17/2021 6/17/2021 06/17/2021
Retaining Wall Inspection Partial 7/6/2021 07/06/2021
Misc
Informational
07/06/2021
A retaining wall of approximately 3ft. high will be built on Kline in the ROW by the Buildier/Homeowner. We are working out the details. Temorary Occupancy should not be held up for this.
Occupancy Inspection - Codes Residential Failed 7/7/2021 07/07/2021
Misc
Corrective Action Required
07/07/2021
-Contact Steve Robbins concerning retaining wall -Obtain lawn irrigation system permit -Final grade and sod -Splash blocks at all downspout and sump pump discharge locations, min 36” from foundation -GFCI protection required at duplex receptacle, dbl car garage bay -Breaker lockouts at all hardwired appliances
Sidewalk Inspection Partial 7/6/2021 7/6/2021 07/07/2021
Plot Plan Inspection Passed 7/13/2021 7/13/2021 07/13/2021
Erosion Control Inspection Residential Passed 07/13/2021
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
07/13/2021
Occupancy Inspection - Codes Residential Failed 7/13/2021 7/13/2021 07/13/2021
Misc
Corrective Action Required
07/07/2021
-Contact Steve Robbins concerning retaining wall -Obtain lawn irrigation system permit -Add splash block or extension to sump pump discharge, min 36" discharge from foundation -GFCI protection required at duplex receptacle, dbl car garage bay -Breaker lockouts at all hardwired appliances
Occupancy Inspection - Codes Residential Temporary C of O 7/15/2021 7/15/2021 07/15/2021
Misc
Corrective Action Required
07/13/2021
-Contact Steve Robbins concerning retaining wall **OK FOR TCO - TCO EXPIRES 8/13/21**
Occupancy Inspection - Codes Residential Full C of O 02/28/2024
Misc
Resolved
02/28/2024
-Contact Steve Robbins concerning retaining wall **OK FOR TCO - TCO EXPIRES 8/13/21**
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home