Permit Application Status

PRRES20202812


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20202812
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - ENGINEERED FLOOR - ROOF TRUSS - FINISHED BASEMENT - COVERED DECK
09/03/2020
09/16/2020
05/10/2022
Locations
Contacts
CARDINAL CREST HOMES, Address:1539 SWIFT AVE, Phone:(816) 499-3156  
JAMES@CARDINALCRESTHOMES.COM  
MCDANIEL FURNACE & SHEET METAL, Address:2905 S M 291 FRONTAGE RD, Phone:(816) 373-6370  
JOE KILOWATT INC, Address:6506 ROYAL, Phone:(816) 792-4888  
HAMPTON PLUMBING INC, Address:P O BOX 552, Phone:(816) 628-5069  
Reviews
Review Type Outcome Est. Completion Date Completed
Residential Plan Review Approved 09/09/2020 09/16/2020
Dylan Eppert
02 One (1) complete license tax application
Corrective Action Required
09/09/2020

One (1) complete license tax application
18 Identify type of roof/truss package (if used) complete with layout, comp
Corrective Action Required
09/09/2020

Identify type of roof/truss package (if used) complete with layout, component design, fastening details, blocking and sheathing requirements. (IRC Section 802.10) DEFERRED
31 Identify type of joist package or floor truss package (if used)
Corrective Action Required
09/09/2020

Identify type of joist package or floor truss package (if used) complete with layouts, fastening details, blocking and bracing requirements and minimum sheathing. DEFERRED
Plot Plan Review Approved 09/09/2020 09/09/2020
Dylan Eppert
City infrustructure
Corrective Action Required
09/09/2020

Show all manholes, water valve boxes, fire hydrants, and stormwater structures. MISSING MANHOLE, SANITARY STUB LOCATION AND SNAITARY LINE.
Planning Review (RES) Approved 09/10/2020 09/08/2020
Victoria Nelson
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $1,077.17 $1,077.17 Paid 09/16/2020
8331507-Sewer Connection Fee $570.00 $570.00 Paid 09/16/2020
Water Tap Fee $3,581.00 $3,581.00 Paid 09/16/2020
Water Meter Fee $455.54 $455.54 Paid 09/16/2020
Right of Way Permit Fee $80.00 $80.00 Paid 09/16/2020
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 09/08/2020
$1,077.12
New Longview Road and Bridge Escrow $1,077.12 $1,077.12 Paid 09/16/2020
Not Ready Inspection Fee $50.00 $50.00 Paid 08/30/2021
Not Ready Inspection Fee $50.00 $50.00 Paid 08/30/2021
Not Ready Inspection Fee $50.00 $50.00 Paid 08/30/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Residential Passed 11/5/2020 11/5/2020 at 8:20 AM 11/05/2020
Misc
Corrective Action Required
11/05/2020
- PROVIDE 3RD PARTY FOOTING INSPECTION WITHIN 48 HOURS OF POUR -
Erosion Control Inspection Residential Failed 11/06/2020
Misc
Corrective Action Required
11/06/2020
-Deficient erosion control, methods require continuous maintenance. Reestablish erosion control at front and rear property lines within two days. -Immediate Street clean up required, front and rear -No further inspections until issues are resolved
Sewer Service Inspection - R Passed 11/12/2020 (1:15) 11/12/2020 11/12/2020
Water Service Inspection - R Passed 11/13/2020 (10:45) 11/13/2020 11/13/2020
Erosion Control Inspection Residential Failed 12/08/2020
Misc
Corrective Action Required
11/06/2020
-Deficient erosion control, methods require continuous maintenance. Reestablish erosion control at curb within two days. -Immediate Street clean up required, front and rear -No further inspections until issues are resolved
Gas Service Inspection - Residential Passed 1/25/2021 1/25/2021 01/25/2021
Gas Piping Inspection - Residential Passed 01/25/2021
Erosion Control Inspection Residential Failed 01/25/2021
Misc
Corrective Action Required
12/08/2020
-Erosion control requires continuous maintenance. Repair damaged sections within two business days -no further inspections until issues are resolved
Erosion Control Inspection Residential Failed 02/04/2021
Misc
Corrective Action Required
01/25/2021
-Erosion control requires continuous maintenance. Repair damaged sections within 48 hours -no further inspections until issues are resolved
Erosion Control Inspection Residential Failed 03/08/2021
Misc
Corrective Action Required
02/04/2021
-Erosion control requires continuous maintenance. Repair damaged sections within 48 hours -no further inspections until issues are resolved
All Rough Inspection - Residential Failed 3/8/2021 3/8/2021 03/08/2021
Misc
Corrective Action Required
03/08/2021
No access to interior, all doors are locked and no lockbox onsite. Provide access and reschedule inspection
All Rough Inspection - Residential Failed 03/08/2021
Misc
Corrective Action Required
03/08/2021
-Provide and make up all outlet boxes, mechanically fasten spliced equipment grounding conductors and ground all metallic outlet boxes -Complete exterior sheathing installation -Install flashing at roof penetrations -Maintain 1 inch minimum clearance of B vent to combustibles, bedroom 2 closet -Provide nail plate protection of conductor top plate Penetrations where edge of penetration is less than 1.25” from face of framing members, bed 2 -Provide hardwired and interconnected smoke alarm in bedroom two -Fireblock all through floor Penetrations -Fireblock bottom plate penetration main level bath -Fireblock penetration and wood fire block at DWV penetration, main level bath -Secure NM conductor within 12 inches of junction box, main level bath -first/second floor exterior wall and garage/dwelling separation wall bottom plate 12”oc fastening per plan -Fasten steel columns to wood floor per plan detail -Adequate fireblock of penetrations in wood fireblock at concealed space bottom of stairs main floor -Provide minimum 16g galvanized metal ties 1.5” wide at over bored top plates of interior load bearing walls. Fasten ties across and to the plate at each side of the opening with minimum 4-10dx1.5” at each side. The metal tie must extend a minimum of 6” past the opening. Garage/dwelling separation wall -Provide stud shoe at overbored exterior wall stud, clothes washer DWV -Nail plate protection at Conductor stud Penetrations. Bed 2, mudroom, master bed, dining, stairs to basement, great room, bed 4 & loft -Provide stud shoe at overbored exterior wall stud, gas piping penetration dining -Protect NM conductors from physical damage minimum 6” AFF at floor penetrations -Adequate fireblock top plate penetration, master bath -Nail plate protection at bottom plate penetration, Refrigerator water supply -Portal opening per PFG 2/S2.0, framing and fastening -12” oc fastening, stud to stud and abutting studs at intersecting braced walls -Fireblock vertical to horizontal second floor concealed space east of stairs -Repair damaged water distribution piping, unfinished basement area -Identify white insulated conductors to be used as current carrying conductors at both points of termination -Fireblock vertical to horizontal that soffit to walk connection, basement bathroom -Fireblock at soffit/wall connection, bed three & bed 4 -Complete bath exhaust duct installation, basement bath -Secure Supply air boot, basement bath -Single wall metal flue pipe is prohibited in attic space -DECK- -Ledger attachment to structure per code -Beam/post connections per code
Electrical Service Inspection Passed 3/8/2021 03/08/2021
Erosion Control Inspection Residential Failed 03/12/2021
Misc
Corrective Action Required
03/08/2021
-Erosion control requires continuous maintenance. Repair damaged sections within 48 hours -no further inspections until issues are resolved Second notice 03/12/2021
All Rough Inspection - Residential Failed 3/12/2021 3/12/2021 03/12/2021
Misc
Corrective Action Required
03/08/2021
-Provide and make up all outlet boxes, mechanically fasten spliced equipment grounding conductors and ground all metallic outlet boxes -Complete exterior sheathing installation -Install flashing at roof penetrations -Maintain 1 inch minimum clearance of B vent to combustibles, bedroom 2 closet -Provide nail plate protection of conductor top plate Penetrations where edge of penetration is less than 1.25” from face of framing members, bed 2 -Provide hardwired and interconnected smoke alarm in bedroom two -Fireblock all through floor Penetrations -Fireblock bottom plate penetration main level bath -Fireblock penetration and wood fire block at DWV penetration, main level bath -Secure NM conductor within 12 inches of junction box, main level bath -first/second floor exterior wall and garage/dwelling separation wall bottom plate 12”oc fastening per plan -Fasten steel columns to wood floor per plan detail -Adequate fireblock of penetrations in wood fireblock at concealed space bottom of stairs main floor -Provide minimum 16g galvanized metal ties 1.5” wide at over bored top plates of interior load bearing walls. Fasten ties across and to the plate at each side of the opening with minimum 4-10dx1.5” at each side. The metal tie must extend a minimum of 6” past the opening. Garage/dwelling separation wall -Provide stud shoe at overbored exterior wall stud, clothes washer DWV -Nail plate protection at Conductor stud Penetrations. Bed 2, mudroom, master bed, dining, stairs to basement, great room, bed 4 & loft -Provide stud shoe at overbored exterior wall stud, gas piping penetration dining -Protect NM conductors from physical damage minimum 6” AFF at floor penetrations -Adequate fireblock top plate penetration, master bath -Nail plate protection at bottom plate penetration, Refrigerator water supply -Portal opening per PFG 2/S2.0, framing and fastening -12” oc fastening, stud to stud and abutting studs at intersecting braced walls -Fireblock vertical to horizontal second floor concealed space east of stairs -Repair damaged water distribution piping, unfinished basement area -Identify white insulated conductors to be used as current carrying conductors at both points of termination -Fireblock vertical to horizontal that soffit to walk connection, basement bathroom -Fireblock at soffit/wall connection, bed three & bed 4 -Complete bath exhaust duct installation, basement bath -Secure Supply air boot, basement bath -Single wall metal flue pipe is prohibited in attic space -DECK- -Ledger attachment to structure per code -Beam/post connections per code
Misc
Corrective Action Required
03/12/2021
Inspection denied due to lack of compliance with recent erosion control inspection reports 03/12/2021
All Rough Inspection - Residential Failed 3/16/2021 3/16/2021 03/16/2021
Misc
Corrective Action Required
03/12/2021
-Fireblock all through floor Penetrations -first/second floor exterior wall and garage/dwelling separation wall bottom plate 12”oc fastening per plan -Fasten steel columns to wood floor per plan detail -Provide minimum 16g galvanized metal ties 1.5” wide at over bored top plates of interior load bearing walls. Fasten ties across and to the plate at each side of the opening with minimum 4-10dx1.5” at each side. The metal tie must extend a minimum of 6” past the opening. Garage/dwelling separation wall -Fireblock vertical to horizontal second floor concealed space east of stairs, Also properly Support removed Conductor per code in this area -Identify white insulated conductors to be used as current carrying conductors at both points of termination -Fireblock at soffit/wall connections, bed three & bed 4 -Secure Supply air boot, basement bath -Provide manufacturers installation instructions of gas flex vent in attic space -DECK- -Ledger attachment to structure per code -Beam/post connections per code
Misc
Resolved
03/16/2021
Inspection denied due to lack of compliance with recent erosion control inspection reports 03/12/2021
Erosion Control Inspection Residential Passed 03/16/2021
Misc
Resolved
03/16/2021
-Erosion control requires continuous maintenance. Repair damaged sections within 48 hours -no further inspections until issues are resolved Second notice 03/12/2021
Footing Inspection - Residential Passed 03/16/2021
All Rough Inspection - Residential Not Ready 3/23/2021 3/23/2021 03/23/2021
Misc
Corrective Action Required
03/16/2021
-Fireblock all through floor Penetrations -first/second floor exterior wall and garage/dwelling separation wall bottom plate 12”oc fastening per plan -Fasten steel columns to wood floor per plan detail -Provide minimum 16g galvanized metal ties 1.5” wide at over bored top plates of interior load bearing walls. Fasten ties across and to the plate at each side of the opening with minimum 4-10dx1.5” at each side. The metal tie must extend a minimum of 6” past the opening. Garage/dwelling separation wall -Fireblock vertical to horizontal second floor concealed space east of stairs, Also Support removed Conductor per code in this area -DECK- -Ledger attachment to structure per code -Beam/post connections per code
All Rough Inspection - Residential Not Ready 3/25/2021 3/25/2021 03/25/2021
Misc
Corrective Action Required
03/23/2021
-fireblock penetrations in wood fireblock, second story concealed space electrical & HVAC lineset penetrations -DECK- -Beam/post connections per code
All Rough Inspection - Residential Passed 3/30/2021 3/30/2021 03/30/2021
Misc
Resolved
03/30/2021
-fireblock penetrations in wood fireblock, second story concealed space electrical & HVAC lineset penetrations -DECK- -Beam/post connections per code
Sidewalk Inspection Partial 4/30/2021 4/30/2021 04/30/2021
Misc
Corrective Action Required
04/30/2021
Forms were placed and aggregate was present and compacted, but not 4 inches deep. Contractor is to remove excess subgrade and add correct amount of aggregate. RP 4-30-21
Sidewalk Inspection Failed 5/7/2021 5/7/2021 05/07/2021
Misc
Corrective Action Required
04/30/2021
Forms were placed and aggregate was present and compacted, but not 4 inches deep. Contractor is to remove excess subgrade and add correct amount of aggregate. RP 4-30-21
Misc
Corrective Action Required
05/07/2021
One panel is busted and needs to be replaced. The rest of the sidewalk looks good. RP 5-7-21
Occupancy Inspection - Codes Residential Not Ready 8/30/2021 8/30/2021 08/30/2021
Misc
Corrective Action Required
08/30/2021
**NOT READY FOR INSPECTION. COMPLETE ALL EXTERIOR AND INTERIOR BEFORE CALLING FOR AN INSPECTION. REINSPECTION FEE ASSESSED ON 8/30/21
Occupancy Inspection - Codes Residential Failed 8/31/2021 8/31/2021 08/31/2021
Misc
Corrective Action Required
08/30/2021
-Provide erosion control at perimeter of lot before any further inspecitons -Driveway and sidewalk inspections still pending -As graded plot plan required to be submitted and approved -Final grade and sod -Downspouts, gutters, splash blocks, sump extension -Clean debris from window wells -Seal top of meter can, ac disconnects and all exterior penetrations -Complete plumbing at kitchen sink -Complete hood installation at kitchen -Secondary lock required at both sliding glass doors -Fireblock storage room in basement I joists from adjacent spaces -Lockout at range breaker -Set non comustible attic access panel -Flood light required at back of house per security code
Occupancy Inspection - Codes Residential Temporary C of O 9/1/2021 9/1/2021 09/01/2021
Misc
Corrective Action Required
08/31/2021
TCO UNTIL 9-29-21 -Provide erosion control at perimeter of lot before any further inspecitons -Driveway and sidewalk inspections still pending -As graded plot plan required to be submitted and approved -Final grade and sod -Downspouts, gutters, splash blocks, sump extension -Seal top of meter can, ac disconnects and all exterior penetrations
Occupancy Inspection - Codes Residential Failed 4/11/2022 4/11/2022 04/11/2022
Misc
Corrective Action Required
09/01/2021
TCO UNTIL 9-29-21 -sidewalk inspections still pending - obtain sprinkler permit and submit back flow certification
Sidewalk Inspection Failed 4/14/2022 4/14/2022 04/14/2022
Misc
Corrective Action Required
05/07/2021
Forms were placed and aggregate was present and compacted, but not 4 inches deep. Contractor is to remove excess subgrade and add correct amount of aggregate. RP 4-30-21
Misc
Corrective Action Required
05/07/2021
One panel is busted and needs to be replaced. The rest of the sidewalk looks good. RP 5-7-21
Misc
Corrective Action Required
04/14/2022
Busted panel still needs to be removed and replaced. Call in another inspection when ready. RP 4-14-22
Sidewalk Inspection Passed 5/10/2022 5/10/2022 05/10/2022
Misc
Corrective Action Required
04/14/2022
Forms were placed and aggregate was present and compacted, but not 4 inches deep. Contractor is to remove excess subgrade and add correct amount of aggregate. RP 4-30-21
Misc
Corrective Action Required
04/14/2022
One panel is busted and needs to be replaced. The rest of the sidewalk looks good. RP 5-7-21
Misc
Corrective Action Required
04/14/2022
Busted panel still needs to be removed and replaced. Call in another inspection when ready. RP 4-14-22
Misc
Informational
05/10/2022
Damaged sidewalk panel was replaced. Sidewalk meets LS and Ada specs. 5/10/22 ES
Occupancy Inspection - Codes Residential Full C of O 5/10/2022 5/10/2022 05/10/2022
Misc
Resolved
05/10/2022
TCO UNTIL 9-29-21 -sidewalk inspections still pending - obtain sprinkler permit and submit back flow certification
Documents & Images
Date Uploaded File Type Document Name
09/03/2020 Application Form Lot 106 Permit App
09/04/2020 PATTON - Plot Plan (Staked)
09/04/2020 PATTON - Engineered Plans (ANSI D)
09/09/2020 Letter Codes Residential Plan Review
09/09/2020 Plot Plan APPROVED PLOT PLAN
09/16/2020 License Tax Form
09/16/2020 Plans APPROVED HOUSE PLANS
09/16/2020 Plans APPROVED ELEVATIONS
09/16/2020 Letter DS Building Permit
09/16/2020 Receipt Receipt for transaction:2020-006274
10/23/2020 3209 SW Mary St LSMO Pergola Park Lot 106 Bellah P 2020-2812 3rd Party Footing Inspection 10-15-20
11/05/2020 Letter INSPECTION SUMMARY
11/06/2020 Letter INSPECTION SUMMARY
11/12/2020 Letter INSPECTION SUMMARY
11/13/2020 Letter INSPECTION SUMMARY
12/03/2020 Engineer Report/Study Final_2020_11_11_BSlab_LSMO_Cardinal Crest
12/08/2020 Letter INSPECTION SUMMARY
12/09/2020 Drawing 1ST FLOOR IJOIST LAYOUT (APPROVED)
12/09/2020 Drawing APPROVED ROOF TRUSS LAYOUT
12/09/2020 Specifications APPROVED ROOF TRUSS PACKAGE
12/09/2020 Drawing 2ND FLOOR IJOIST LAYOUT (APPROVED)
01/25/2021 Letter INSPECTION SUMMARY
01/25/2021 Letter INSPECTION SUMMARY
01/25/2021 Letter INSPECTION SUMMARY
02/04/2021 Letter INSPECTION SUMMARY
03/08/2021 Letter INSPECTION SUMMARY
03/08/2021 Letter INSPECTION SUMMARY
03/08/2021 Letter INSPECTION SUMMARY
03/08/2021 Letter INSPECTION SUMMARY
03/12/2021 Letter INSPECTION SUMMARY
03/12/2021 Letter INSPECTION SUMMARY
03/16/2021 Letter INSPECTION SUMMARY
03/16/2021 Letter INSPECTION SUMMARY
03/16/2021 Letter INSPECTION SUMMARY
03/17/2021 Double_Wall_B-Flex_Installation_Instructions-L1927 (1)
03/23/2021 Letter INSPECTION SUMMARY
03/25/2021 Letter INSPECTION SUMMARY
03/30/2021 Letter INSPECTION SUMMARY
04/30/2021 Letter INSPECTION SUMMARY
05/07/2021 Letter INSPECTION SUMMARY
08/30/2021 Letter INSPECTION SUMMARY
08/30/2021 Receipt Receipt for transaction:2021-006948
08/31/2021 Letter INSPECTION SUMMARY
09/01/2021 Letter Codes Temporary Certificate of Occupancy
03/15/2022 3209 SW Mary St (Sprinkler Release)
04/04/2022 Pergola Park 106 Final Grading
04/05/2022 Pergola Park 106 Final Grading 22_0405
04/11/2022 Letter INSPECTION SUMMARY
04/14/2022 Letter INSPECTION SUMMARY
05/10/2022 Letter INSPECTION SUMMARY
05/10/2022 Letter Field Certificate of Occupancy
05/10/2022 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home