Summary
PRRES20202304
Building Permit - Residential
Certificate of Occupancy
CMH PARKS INC
NEW SINGLE FAMILY
NEW HOUSE - UNFINISHED BASEMENT - COVERED DECK - ROOF TRUSS
08/13/2020
08/18/2020
06/15/2021
Locations
Contacts
CMH PARKS INC, Address:5000 CLAYTON RD  
CLAYTON PROPERTIES GROUP, INC, Address:10450 Holmes Rd Suite 100, Phone:(816) 246-6700  
PERMITTING@SUMMITHOMESKC.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 08/17/2020 08/18/2020
Dylan Eppert
Drainage swales
Corrective Action Required
08/17/2020

Drainage swales (where required); show spot elevations within the swale as required to conform to the approved master drainage plan (if applicable), must be provide
As-graded plot plan
Corrective Action Required
08/17/2020

A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy.
Residential Plan Review Approved 08/17/2020 08/14/2020
Dylan Eppert
Planning Review (RES) Approved 08/18/2020 08/14/2020
Dylan Eppert
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $1,290.99 $1,290.99 Paid 08/18/2020
8331507-Sewer Connection Fee $600.00 $600.00 Paid 08/18/2020
Water Tap Fee $3,581.00 $3,581.00 Paid 08/18/2020
Water Meter Fee $455.54 $455.54 Paid 08/18/2020
Right of Way Permit Fee $80.00 $80.00 Paid 08/18/2020
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 08/18/2020
3rd and Subsequent Inspection Fee (Per Hour) $100.00 $100.00 Paid 06/04/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 10/2/2020 10/2/2020 10/02/2020
Underslab Plumbing Inspection - Residential Passed 11/4/2020 11/4/2020 11/04/2020
Sewer Service Inspection - R Passed 1/20/2021 (1:00) 1/20/2021 01/20/2021
Water Service Inspection - R Passed 1/21/2021 (Ready Now) 1/21/2021 01/21/2021
Erosion Control Inspection Residential Failed 01/21/2021
Misc
Corrective Action Required
01/21/2021
-Erosion control requires continuous maintenance. Repair damaged sections within two business days -immediate street cleanup required -maintain gravel filter -no further inspections until issues are resolved
All Rough Inspection - Residential Failed 1/25/2021 1/25/2021 01/25/2021
Misc
Corrective Action Required
01/25/2021
INSPECTION DENIED DUE TO EROSION CONTROL DEFICIENCY SEE EROSION CONTROL REPORT FROM 1/21 -Erosion control requires continuous maintenance. Repair damaged sections within two business days -immediate street cleanup required -maintain gravel filter -no further inspections until issues are resolved
Erosion Control Inspection Residential Failed 1/25/2021 1/25/2021 01/25/2021
Misc
Corrective Action Required
01/21/2021
-Erosion control requires continuous maintenance. Repair damaged sections within two business days -immediate street cleanup required -maintain gravel filter -no further inspections until issues are resolved
All Rough Inspection - Residential Failed 1/26/2021 1/26/2021 01/26/2021
Miscellaneous Correction
Corrective Action Required
01/26/2021
-Complete exterior sheathing nailing pattern at back of house -Complete fire blocking at soffit line in garage and seal any gaps -Correct fire blocking at soffit line at nm near entry -Fur down supply lines in garage for insulation -Provide joist hanger at joist over 4’ in garage near DWV -Fire block dead space at garage/ kitchen -Nail all corners and intersecting walls per code -Provide midpoint strap on all DWV 2” and smaller -Provide engineered correction for trusses and hangers nailed to blocks at owner’s entry -BOCCA plate at PEX in bottom plate Bed 5 -Seal gaps in fireblocking at dead space in great room -Fire block soffit line in great room at window and dead spaces -LIB all locations -Missing (2) 2x4 in HVAC chase in kitchen -Missing (4) 2x4 at Home office -Provide security blocking at exterior doors -Correct (3) 2x4 post top plate to provide full bearing at double joist at stairs -Connect 2x6 exterior corner studs at stairway per code -Fireblock gap between walls at bedroom / master bedroom exterior wall -Fireblock dead space at upstairs chase -Truss bracing at trusses E8 and E9 -Missing (2) 2x4 at window bed 5 -Light switch required at top of stairs in upper level and at bottom landing at basement -Missing solid blocking under kitchen island -Support joists for stair landing in basement both sides -Connect GEC to ufer -Provide gauge for gas
Electrical Service Inspection Failed 1/26/2021 1/26/2021 01/26/2021
Miscellaneous Correction
Corrective Action Required
01/26/2021
-Label and connect GEC to Ufer
Gas Piping Inspection - Residential Failed 1/26/2021 1/26/2021 01/26/2021
Miscellaneous Correction
Corrective Action Required
01/26/2021
-provide gauge for pressure test
Gas Service Inspection - Residential Failed 1/26/2021 1/26/2021 01/26/2021
G2417.4.1 Test Pressure
Corrective Action Required
01/26/2021
INSPECTION, TESTING AND PURGING. AMENDED 7-945. The test pressure to be used shall be not less than one and one-half times the proposed maximum working pressure, but not less than 10 psig (68.9kPa) irrespective of design pressure. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure, the test pressure shall not be less than 60 psig. Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe.
Electrical Service Inspection Passed 1/28/2021 1/28/2021 01/28/2021
Miscellaneous Correction
Resolved
01/28/2021
-Label and connect GEC to Ufer
Gas Piping Inspection - Residential Passed 1/28/2021 1/28/2021 01/28/2021
Miscellaneous Correction
Resolved
01/28/2021
-provide gauge for pressure test
Gas Service Inspection - Residential Passed 1/28/2021 1/28/2021 01/28/2021
G2417.4.1 Test Pressure
Resolved
01/28/2021
INSPECTION, TESTING AND PURGING. AMENDED 7-945. The test pressure to be used shall be not less than one and one-half times the proposed maximum working pressure, but not less than 10 psig (68.9kPa) irrespective of design pressure. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure, the test pressure shall not be less than 60 psig. Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe.
All Rough Inspection - Residential Failed 1/28/2021 1/28/2021 01/28/2021
Miscellaneous Correction
Corrective Action Required
01/26/2021
-Complete exterior sheathing nailing pattern at back of house-Southeast side bottom perimeter -Complete fire blocking at soffit line in garage and seal any gaps-block at dwv in garage soffit -Correct fire blocking at soffit line at nm near entry -Fire block dead space at garage/ kitchen-seal gaps -Nail all corners and intersecting walls per code -Provide midpoint strap on all DWV 2” and smaller -Provide engineered correction for trusses and hangers nailed to blocks at owner’s entry -Fire block soffit line in great room at window and dead spaces and seal gaps -LIB all locations-garage west wall under beam & in HVAC chase in kitchen -Missing (4) 2x4 at Home office -Connect 2x6 exterior corner studs at stairway per code -Fireblock gap between walls at bedroom / master bedroom exterior wall-seal gaps -Support joists for stair landing in basement-north side, use proper joist hanger not jack truss connector
All Rough Inspection - Residential Failed 1/29/2021 1/29/2021 01/29/2021
Miscellaneous Correction
Corrective Action Required
01/28/2021
-Maintain gravel filter -Complete exterior sheathing nailing pattern at back of house-Southeast side bottom perimeter -Seal fire block at soffit line in garage at 2” DWV -Provide midpoint strap on all DWV 2” and smaller -Provide engineered correction for trusses and hangers nailed to blocks at owner’s entry -Missing (4) 2x4 at Home office -Connect 2x6 exterior corner studs at stairway-connect both exterior studs 12” OC
All Rough Inspection - Residential Passed 2/2/2021 2/2/2021 02/02/2021
Miscellaneous Correction
Resolved
02/02/2021
Occupancy Inspection - Codes Residential Failed 5/4/2021 5/4/2021 05/04/2021
Misc
Corrective Action Required
05/04/2021
-Maintain erosion control on lot until sod is placed -Resolve outstanding inspection fee(s) before final c of o -driveway inspection required -contact development services to schedule -As graded plot plan required, submit for review -Complete final grade and sod -Seal all penetrations in siding, seal along top of meter can and AC disconnect -Splash blocks at all downspout and sump pump discharge locations, minimum 36" discharge from foundation -GFCI protection at wall receptacle right of range at kitchen -GFCI protection required at dishwasher receptacle -Security screws at back door deck -Bath exhaust fan required at 1st floor bath -Hot water heater must be operational -Hot water heater discharge pipe minimum distance above floor two times pipe diameter up to maximum of 6” -Handrail at deck stairs shall be continuous for the full length of flight, from a point directly above the top riser of flight to a point directly above the lowest riser of flight.
Occupancy Inspection - Codes Residential Failed 6/9/2021 6/9/2021 06/09/2021
Misc
Corrective Action Required
05/04/2021
-driveway inspection required -contact development services to schedule -As graded plot plan required, submit for review -Install cover plate kitchen countertop receptacle -Hot water heater must be operational -Remove pressure gauge from gas line
Driveway Inspection Passed 6/11/2021 6/11/2021 06/11/2021
Misc
Informational
06/11/2021
On Friday, 6-11-2021. I performed a field inspection for the driveway at the location an found the driveway to meet city standards and passes inspection.
Erosion Control Inspection Residential Passed 6/14/2021 6/14/2021 06/14/2021
Misc
Corrective Action Required
01/25/2021
-Erosion control requires continuous maintenance. Repair damaged sections within two business days -immediate street cleanup required -maintain gravel filter -no further inspections until issues are resolved
Occupancy Inspection - Codes Residential Failed 6/14/2021 6/14/2021 06/14/2021
Misc
Corrective Action Required
06/09/2021
-As graded plot plan required, submit for review- As built has not been approved
Plot Plan Inspection Passed 6/15/2021 06/15/2021
Occupancy Inspection - Codes Residential Full C of O 6/15/2021 6/15/2021 06/15/2021
Misc
Resolved
06/15/2021
Documents & Images
Date Uploaded File Type Document Name
08/13/2020 Application Form HT #44 - PERMIT APP
08/13/2020 HT #44 - TRUSS LAYOUT
08/13/2020 LOT 44 FINAL
08/13/2020 HT #44 - Preston Ridge IV - Farmhouse - Sheets- signed
08/13/2020 400423
08/14/2020 Specifications APPROVED TRUSS PACKAGE
08/14/2020 Code Mod Request APPROVED TRUSS LAYOUT
08/14/2020 Plans APPROVED HOUSE AND ELEVATIONS
08/17/2020 Letter Codes Residential Plan Review
08/18/2020 Plot Plan APPROVED PLOT PLAN
08/18/2020 Receipt Receipt for transaction:2020-005339
08/18/2020 Letter DS Building Permit
09/17/2020 44 Hawthorne Ridge Pier Plan-Final - Signed (002)
09/29/2020 44 Hawthorne Ridge Pier Plan-Final - Signed (002)
10/02/2020 Lot 44 Hawthorne Ridge Footing
10/02/2020 Letter INSPECTION SUMMARY
10/15/2020 Lot 44 Hawthorne Ridge Wall Inspection
11/04/2020 Letter INSPECTION SUMMARY
01/20/2021 Letter INSPECTION SUMMARY
01/21/2021 Letter INSPECTION SUMMARY
01/21/2021 Letter INSPECTION SUMMARY
01/25/2021 Letter INSPECTION SUMMARY
01/25/2021 Letter INSPECTION SUMMARY
01/26/2021 Letter INSPECTION SUMMARY
01/26/2021 Letter INSPECTION SUMMARY
01/26/2021 Letter INSPECTION SUMMARY
01/26/2021 Letter INSPECTION SUMMARY
01/28/2021 Letter INSPECTION SUMMARY
01/28/2021 Letter INSPECTION SUMMARY
01/28/2021 Letter INSPECTION SUMMARY
01/28/2021 Letter INSPECTION SUMMARY
01/28/2021 Letter INSPECTION SUMMARY
01/28/2021 44 Hawthorne Ridge Truss Field Issue
01/29/2021 Letter INSPECTION SUMMARY
01/29/2021 Engineer Report/Study ENGINEER REPORT
02/02/2021 Letter INSPECTION SUMMARY
05/04/2021 Letter INSPECTION SUMMARY
06/04/2021 Receipt Receipt for transaction:2021-003953
06/09/2021 Letter INSPECTION SUMMARY
06/11/2021 Letter INSPECTION SUMMARY
06/14/2021 Letter INSPECTION SUMMARY
06/14/2021 Letter INSPECTION SUMMARY
06/14/2021 Plot Plan approved as graded plot plan
06/15/2021 Letter INSPECTION SUMMARY
06/15/2021 Letter Field Certificate of Occupancy
06/15/2021 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.